Emerson ASCO 185 User Manual

Operator’s
Manual
DANGER is used in this manual to warn of high voltages capable of causin g shock, burns, or death.
WARNINGisusedinthismanualtowarn of possible personal injury.
CAUTIONisusedinthismanualtowarn of possible equipment damage.
An experienced licensed electrician must install the A TS.
100 throu gh 400 ampe re sizes
Series 185
Refer to the outline and wiring drawings provided with your ASCO Series 185 ATS for all installation details.
ASCO Series 185 Automatic Transfer Switches (ATSs) are Listed under Underwriter’s Laboratories Standard for Transfer Switch Equipment, UL–1008. They are intended for use only in optional standby system s in accordanc e with the National Electrical Code, NEC/NFPA 70, Article 702. This ATS is for use with 2–wire automatic start generators only.
Refer to Application Informaton 381339–292 to confirm that you have selected tha appropriate product for the intended installatio n .
This automatic transfer switch is intended for standby power applicato n s in residential / lig h t commercial use only.
This product is not intended for emergency or life–support systems.
If you have more stringen t applicatio n requirements contact ASCO Pow er Technolog ies for other produc ts suitable for critical applications.
Rating Label
Each automatic transfer switch contains a rating label to define the loads and fault circuit withstand / closing ratings. Refer to the label on the transfer switch for specific values.
Do not exceed the values on the rating label. Exceeding the rating can cause personal injury or serious equipment damage.
TABLE OF CONTENTS
page
INSTALLATION 1..........................
CONTROLLER 2–5........................
FUNCTIONAL TEST 6......................
SEQUENCE OF OPERATION 7.............
TROUBLESHOOTING 8–9..................
100–230 ampere sizes
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3 telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO) www.asco.ca
INDEX 10.................................
381333–319 A
Series 185
Nameplate
The Transfer Switch nameplate includes data for each specific ASCO Series 185 ATS. Use the ATS only within the limits shown on this nameplate.
D 185 A 2 200 F 4 C
Neutral
A –standard
Phase Poles
2 –singleØ
Amperes Voltage Controller Enclosure
100
200
230
260 400
clock battery
cable spacers (see INSTALLATION)
Catalog Number Identification
A typical Catalog Number is shown below with its elements explained. The example is for a D–design, 2 pole, 200 A, 220–240 V, in a Type 1 indoor enclosure:
F 220--- 240
4 –standard
4X
–if
accessories
ordered
load power connections
C –Type1
M –Type3R
emergency power connections
neutral connections
terminals
for optional
switch
position
contacts
(shown
installed)
Transfer
Switch
ground
connections
200 ampere size in typical enclosure with location of customer connections
381333–319 A
membrane
controls
generator control connections
Controller
harness plug
utility power connections
INSTALLATION
Series 185
Installation of the ASCO Series 185 automatic transfer switch (ATS) must be performed by a licensed electrician. It must be installed according to the National Electrical Code (NEC) and all local electrical code requirements. Remove the enclosure cover and inspect the ATS for shipping damage. If damage is evident do not install the ATS .
1 --- M o u n t i n g
Refer to the enclosure outline drawing. Mount the ATS according to details and instructions shown on this diagram. Mount the ATS vertically to a rigid supporting structure. Level all mounting points by using flat washers behind the holes to avoid distortion of the enclosure.
MALFUNCTION or SHORTENED LIFE Protect the ATS from construction grit and metal chips to prevent malfunction or shortened life.
Transfer switches rated 260 and 400 amperes are mounted on an insulator backing piece (installed behind the transfer switch). If the transfer switch is removed from the enclosure and then reinstalled, this insulator must be placed behind the transfer switch. See Figure 1.
2 --- Electrical Power Connections
Refer to the wiring diagram. The ATS must be protected by suitably sized circuit breakers feeding the utility and generator source terminals. The rating of the circuit breakers must be based on the requirements of the National Electrical Code for its nameplate ampere and short circuit withstand ratings.
ELECTROCUTION HAZARD Turn off utility power and turn off the generator to prevent electrocution when wiring the transfer switch.
Cable Spacers for 200 and 230 A
Three cable spacers are included with 200 and 230 ampere transfer switches. Run the copper power cables throughthecablespacersasshowninFigure2. Position the cable spacers approximately 1½ inches from the terminal lugs.
CABLE LOOSENING DUE TO SHORT CIRCUIT Install three cable spacers 1 1/2 inches from the power terminals to prevent the cables from loosening during a short–short condition.
FLASH HAZARD – DAMAGE Be sure that the insulator piece is installed behind the 260 and 400 ampere transfer switches.
insulator backing piece
Figure 1. Insulator for 260 and 400 A.
cable spacers
1 ½ inch approximate
use copper power cables only for 200 and 230 A
cable spacer
Figure 2. Cable spacers for 200 and 230 A.
1
381333–319 A
CONTROLLERSeries 185
The Group 4 digital Controller is used in ASCO Series 185 automatic transfer switches. It provides the sensing, timing, and control functions for the ATS. This micro– processor–based controller includes built–in control buttons and st atus lights for control of the ATS and generator.
clock battery cover seepage3
Utility Acceptable light
Trans fer Tes t button
Load on Utility light
1 --- P u s h B u t t o n s
On the front control display are three push buttons that control the operation of the generator and the ATS .
Before using the transfer test button, be sure that conditions are safe for running the generator and for load transfer.
Transfer Test
Use this button to test the system. This operation starts the generator and transfers the load. Be sure that conditions are safe to do this operation.
Bypass Time Delay
Use this button to cancel the active time delay or exercise period (stops the generator after cooldown).
Set Engine Exerciser
Use this button to set the automatic generator exerciser (page 3).
2 --- I n d i c a t o r L i g h t s
Bypass Time Delay button
Set Exerciser button
Automatic Generator Exerciser light
Load on Generator light
Generator Acceptable light
Figure 3. Front view of controller.
On the f ront control display are five lights that indicate the status of the sources and the ATS.
Utility Acceptable
This light i ndicates that the utility voltage is acceptable for connection to the load.
Generator Acceptable
This light indicates that the generator voltage is acceptable for connection to the load.
Load on Utility
This light indicates that the generator voltage is acceptable for connection to the load.
Load on Generator
This light indicates that the generator voltage is acceptable for connection to the load.
Automatic Generator Exerciser
When the utility is acceptable and the load is on the utility, this light flashes the number of days until the next exercise period. When i t is off, no exerciser period is set. The light is also off when the generator is running.
381333–319 A
2
CONTROLLER
Series 185(continued)
3 --- Generator Starting Contacts
The generator starting contacts connections are on the controller. Refer to the generator manual. Disconnect the generator battery and verify that the ignition switch is in the OFF position. Connect the generator starting wires to the appropriate terminals on terminal block TB7 as shown on the wiring diagram. For wiring convenience terminalblockTB7hasaremovableplug. SeeFigure4 and Table A.
123456789
TB7–4, TB7–5, TB7–6
Figure 4. TB7 generator starting contact terminals.
TB7
removable
terminal block
5 --- Automatic Generator Exerciser
The built–in automatic generator exerciser can be set to exercise the generator for 20 minutes once every week.
Clock Battery
Be sure a fresh battery is installed and turned on. It will maintain the ex erciser clock for about 24 hours in case of a power outage.
Recommended9voltalkalinebatteriesare(seeFigure
5): Duracell MN 1404, Everready 522, Panasonic 6AM6
Turn on battery by putting S2 DIP switch actuator 10 in the on position (up). See Table B and Figure 6.
Exercise with or without Load
The generator should be exercised under load or follow the recommendations of the generator manufacturer. Be sure the exerciser is turned on. Then select either exercise with or without load. The ATS will transfer the load to the generator when the exercise with load is selected. See Figure 6 and Table B.
Table A. Generator Start Connections
When the Utility fails Terminals on Controller
contact closes TB7–4 and TB7–5
contact opens TB7–5 and TB7–6
4 --- S e t t i n g s
ThetimedelayandsensorsettingintheGroup4 controller are accessible on the inside. Refer to Tables B and C and to Figures 6 and 7. Use a ball–point pen or other pointed tool to slide the DIP switch actuators up or down to match setting shown.
All power must be off before making any changes.
The factory default settings are shown in Table G on page 5.
cover must be removed to replace 9V battery (use alkaline type)
screw
Table B. Generator Exercise Settings
Function
clock
battery
exerciser off S1 7
with load or
without load
Factory
Setting
off S2 10
without
load
DIP
Switch
S1 8
DIP
Actuator
Actuator
Position
on (up)
off (down)
on (up)
off (down)
without (up) with (down)
To S e t E x e rci s e r
Press and hold (5 seconds) the Set Engine Exerciser button. The exercise period occurs immediately
and at the same time weekly thereafter. The status light below the button blinks rapidly to indicate that the exerciser has been set. The number of flashes indicates the number of days until the next exercise period (at approximately
thesametimethebuttonwaspressed).
To Cancel an Active Exercise Period
Press the Set Engine Exerciser button t o stop a n exercising generator. If exercise with load is set, the ATS retransfers the load to the utility, then stops the generator after cooldown.
Figure 5. Battery replacement.
3
381333–319 A
Series 185
overridemomentary
3
overridemomentary
unloadedrunning
f
l60
H
198
V
198V*
ili
1
87V
d
1
87V
176
V
154V
d
j
b
le–––
d
j
b
le–––
CONTROLLER
(continued)
S1 DIP switch
S2 DIP switch
S3 DIP switch
Figure 6. DIP switches S1 and S2 at the top right.
The time delay settings are shown in Figures 6 and 7 and in Table C. The sensor settings are shown in Figure 6 and in Table D. The standard (factory) settings are showninTablesC,D,andH.
Figure 7. DIP switch S3 at the bottom center.
TableC. TimeDelaySettings
Time Delay Description Factory Setting Settings DIP Switch DIP Actuator Actuator Position
override momentary utility outages
transfer to generator 10 seconds (approx.)
override momentary generator outages
transfer to utility 15 minutes (approx.)
unloaded running (generator cooldown)
seconds
4seconds
5minutes
1second S2 1 on (up)
3seconds S2 1 off (down)
4second S3 9 on (up)
0 S3 9 off (down)
5 minutes S1 10 on (up)
0 S1 10 off (down)
Table D. Voltage and Frequency Settings
Setting Description Setting Factory Setting Settings DIP Switch DIP Actuator Actuator Position
voltage 220 – 240 V non–adjustable S2 2 on (up)
requency nomina
phase single non–adjustable S1 2 off (down)
pickup
ut
ty voltage
ropout
generator voltage
generator frequency pickup
pickup 198 V
dropout 165 V
57 Hz (nom 60 Hz) 48 Hz (nom 50 Hz)
dropout
51 Hz (nom 60 Hz) 43 Hz (nom 50 Hz)
z
50 Hz S1 4 on (up)
60 Hz S1 4 off (down)
198 V S1 3 on (up)
209 V * S1 3 off (down)
S1 1 off (down)
S1 2 off (down)
S1 1 on (up)
S1 2 off (down)
S1 1 off (down)
S1 2 on (up)
S1 1 on (up)
S1 2 on (up)
non–a
non–a
*
usta
usta
* If the dropout voltage is set to 198 V, the pickup voltage must be set to 209 V.
381333–319 A
4
CONTROLLER
disable
d
disable
d
disable
d
S
1
S
2
S
3
Series 185(continued)
6 --- Remote Control Features
These remote control features require a customer– supplied normally–closed contact suitable for a 5 V dc low energy circuit. Refer to the wiring diagram provided withtheATS. ActivatetheappropriateDIPswitchS3 actuators as shown in Tables E, F, or G. See Figure 7.
Remote test
Normally–closed input. When opened, it simulates a utility failure. The generator is signalled to start immediately and the load transfers to the generator (if acceptable). If the generator fails, the load stays on the generator until the remote test circuit is closed.
TableE. Remotetest
Function
disabled
enabled
Factory Setting
disabled
(on)
DIP
Switch
S3 3
DIP
Actuator
Actuator Position
on (up)
off (down)
Remote test (with automatic retransfer)
Normally–closed input. When opened, it simulates a utility failure. The generator is signalled to start immediately and the load transfers to the generator (if acceptable). If the generator fails, the load transfers back to the utility (if acceptable).
Table F. Remote transfer to generator
Function
disabled
enabled
Factory Setting
disabled
(on)
DIP
Switch
S3 2
DIP
Actuator
Actuator Position
on (up)
off (down)
Bypass load transfer to utility time delay
Normally–closed input. When opened, it bypasses or cancels the generator to utility load transfer time delay. The load transfers back to the utility.
Table G. Bypass load transfer to utility time
delay
Function
disabled
enabled
Factory Setting
disabled
(on)
DIP
Switch
S3 1
DIP
Actuator
Actuator Position
on (up)
off (down)
7 --- F a c t o r y S e t t i n g s --- S u m m a r y
Table H. Factory Settings – Summary
DIP Switch DIP Actuator Actuator Position
1 on (up)
2 off (down)
3 on (up)
4 off (down)
5 off (down)
6 on (up)
7 off (down)
8 off (down)
9 off (down)
10 on (up)
1 off (down)
2 on (up)
3 off (down)
4 on (up)
5 on (up)
6 on (up)
7 on (up)
8 on (up)
9 off (down)
10 off (down)
1 on (up)
2 on (up)
3 on (up)
4 on (up)
5 on (up)
6 off (down)
7 on (up)
8 on (up)
9 on (up)
10 on (up)
5
381333–319 A
FUNCTIONAL TESTSeries 185
After installing the Series 185 automatic transfer switch (ATS) perform the following three–part functional test.
1 --- M a n u a l O p e r a t i o n
A handle is provided on the transfer switch for mainte­nance purposes only. Manual operation of the transfer switch should be checked before it is energized (operated electrically).
Do not manually operate the transfer switch until both power sources are disconnected: open both circuit breakers.
1. Turn OFF both the utility and generator circuit breakers feeding the ATS. Verify that ALL POWER
IS OFF!
2. 100–230 A Grasp the maintenance handle and turn it quickly with your thumb and fingers to manually operate the transfer switch.
260–400 A
Insert the maintenance handle into the hole in the shaft, left side of the operator. Move the handle as shown to manually operate the transfer switch.
3. The switch should operate smoothly without binding. If it does not, check for shipping damage or construction debris.
4. Aft er checking the manual operation, use the handle again to return the transfer switch to the utility source position. 100–230 A seeFigure8. The letter P (utility) on the round weight is facing you. 260–400 A seeFigure9. The letter N (utility) on the round weight is facing you. Remove the maintenance handle and store it on the transfer switch in the place provided.
260–400 A Remove the maintenance handle before proceeding!
2 --- V o l t a g e C h e c k s
The ATS is rated for 220–240 V ac 60 or 50 Hz. Verify that both the utility and generator sources are 220–240 V ac 60 or 50 Hz.
maintenance handle
With ALL POWER OFF grasp maintenance handle and turn it quickly with your thumb and fingers.
weight marked P (utility) and A (generator)
Figure 8. Maintenance handle for 100–230 A.
hole
maintenance
handle
shaft
Figure 9. Maintenance handle for 260–400 A.
3 --- Electrical Operation
This procedur e checks the elec tr ic al operation of the ATS.
1. Install the enclosure cover and tighten the screws.
2. Verify that the generator battery is connected and that the generator’s starting controls are set for automatic.
3. Turn on both the utility and generator circuit breakers.
4. Verify that the Utility Acceptable and Load on Utility lights are on.
5. This step will start the gene rator. Press and hold the Tra ns f er Te st button until the Generator Acceptable light comes on and stays on. Then release the button.
6. Aft er the Generator Acceptable light comes on, the ATS transfers the load from the uti lity to the generator (after approx. 10 second delay). The Load on Generator light comes on.
7. The ATS stays connected to the generator for 15 minutes (approx.). The utility must be acceptable for 15 minutes continuously. Then the load i s trans­ferred back to the utility. To bypass time delay, press the Bypass Time Delay button.
8. After load retransfer to utility, the generator runs 5 minutes (without load), then shuts down. The Generator Acceptable light goes off indicating that the generator is off.
This completes the Func tional Test.
381333–319 A
6
generator runs
unloaded for 5 min.
¥
electrical loads
switched back
to utility
Sequence of Operation --- Utility Failure
¡
generator
stops
utility acceptable
load on utility
Utility power good.
Electrical loads on utility
utility acceptable
load on utility
generator off
Utility fails
(longer than
3sec.)
utility off
load off
Series 185
light is on
light is off
©
start
generator
wait 15 min.
for utility
to stabilize
¤
utility
returns
generator acceptable
utility acceptable
load on generator
generator acceptable
waiting for utility
to return
observe these power lights
utility off
load on generator
generator acceptable
£
electrical loads
switched to generator
observe these switch lights
generator off
utility off
load on utility
generator acceptable
wait 10 sec.
for generator
to warm up
generator
starting
¢
generator
acceptable
7
381333–319 A
TROUBLESHOOTINGSeries 185
This troubleshooting guide describes some of the simple causes of problems with the installation of the automatic transfer switch. Troubleshooting beyond the scope of this guide should not be attempted by the installer. A licensed electrician must perform all internal troubleshooting. ASCO Power Technologies can be contacted at: 1–800–800–2726 or customercare@asco.com
ELECTROCUTION FLASH HAZARD Do not work on the transfer switch until both the utility and generator are off. Turn OFF both circuit breakers.
Problem
The Utility Acceptable light does not come on when utility power i s connected to the ATS.
The generator does not crank when the utility source fails or when the Transfer Test button is pressed.
The generator cranks but does not start and run when the util­ity source fails or when the Transfer Test button is pressed.
The generator starts and runs but the Generator Acceptable light does not come on.
The generator starts and runs but the ATS does not transfer the load to the generator.
Cause and Solution
1. Verify that the utility feed is connected and that its circuit breaker is ON.
2. With ALL POWER OFF, verify that the utility feed is 220–240 V ac and 60 Hz. Check DIP switch S2 actuator 2, and DIP S1 actuator 4. See Table D for voltage and frequency settings.
3. With ALL POWER OFF, verify that the utility feed is wired to the terminal lugs on the bottom of the transfer switch marked L1 and L5. See the wiring diagram.
4. With ALL POWER OFF, verify that the transfer switch harness is connected properly to the controller (plug and receptacle tight).
1. Hold the Transfer Test button for at least 15 seconds.
2. Verify that the generator starting controls are set for automatic operation (not in manual mode).
3. Verify that the generator battery is connected and that the battery voltage meets the generator manufacturer’s recommendation.
4. Verify that the correct contact (normally open or normally closed) is being utilized (see the generator manual).
5. With ALL POWER OFF, verify engine start low voltage wiring between the controller terminal block and the generator. See the wiring diagram. Check that the plug is properly seated in the receptacle on the controller.
1. Verify proper generator o peration (fuel in tank, oil level, spark plugs --- see generator manual).
2. With ALL POWER OFF, verify engine start low voltage wiring between the controller terminal block and the generator. See the wiring diagram. Check that the plug is properly seated in the receptacle.
1. Verify that the generator feed i s connected and that its circuit breaker is ON.
2. With ALL POWER OFF, verify that the generator feed is 220–240 V ac and 60 Hz. Check DIP switch S2 actuator 2, and DIP S1 actuator 4. See Table D for voltage and frequency settings.
3. With ALL POWER OFF, verify that the generator feed is wired to the terminal lugs on the top of the transfer switch marked L2 and L6. See the wiring diagram.
4. With ALL POWER OFF, verify that the transfer switch harness is connected properly to the controller (plug and receptacle tight).
5. Verify generator ac output (voltage and frequency --- see generator manual).
1. Verify that the Generator Accepted light is on. If it is off, see previous trouble­shooting problem. The AT S will not transfer the load to an unacceptable source.
2. With ALL POWER OFF, verify that the transfer switch harness is connected properly to the controller (plug and receptacle tight).
381333–319 A
8
Problem Cause and Solution
The ATS does not i mmediately transfer the load to the generator.
The ATS transfers the load to the generator, but the genera­tor bogs down (struggles or slows down). The ATS retran­sfers back to the utility.
The generator stops after a running for awhile. The ATS retransfers back to the utility (if acceptable).
The ATS does not retransfer the load back to the utility.
The ATS retransfers the load back to the utility but the generator keeps running.
The generator exerciser does not seem to work.
The generator exerciser does not transfer the load to the generator.
TROUBLESHOOTING
1. Verify that the Generator Accepted light is on. If it is off, see previous trouble-
shooting problem. The AT S will not transfer the load to an unacceptable source.
2. Wait approximately 10 seconds for the transfer to generator time delay. This
fixed delay allows the generator output to stabilize before a load is applied to i t.
3. Press the Bypass Time Delay butto n for immediate load transfer to the generator.
1. The generator may be overloaded. Check to see if the generator circuit breaker
tripped. Check the sum of the loads to be sure it does not exceed the capacity of the generator. Some motor loads require three times more power for starting.
2. Check for short circuit in a connected load.
3. Observe the Load on Utility and Load on Generator lights.
1. Verify proper generator operation; it may have run o ut of fuel or shut down
because of low oil level (see generator manual).
2. The generator may be overloaded. Check to see if the generator circuit breaker
tripped. Check the sum of the loads to be sure it does not exceed the capacity of the generator. Some motor loads require three times more power for starting.
3. Check for short circuit in a connected load.
4. Observe the Load on Utility and Load on Generator lights.
1. Verify that the Utility Accepted light is on. The ATS will not transfer the load to
an unacceptable source.
2. Wait approximately 15 minutes for the retransfer to utility time delay. The utility
must be acceptable for 15 minutes continuously.
3. Press the Bypass Time Delay button for immediate load retransfer to the utility.
1. Wait approximately 5 minutes for the unloaded running (engine cooldown) time
delay.
2. The engine cooldown fixed time delay is important to prevent generator damage.
1. Verify that the Automatic Generator Exerciser light is blinking. When the utility is
acceptable and the load is on t he utility, this light flashes the number of days until the next exercise period. When the light is off, no exercise period is set. The light is also off when the generator is running.
2. With ALL POWER OFF, verify that the exerciser is turned on. Check DIP switch
S1 actuator 7, and S2 actuator 10. See Table B for generator exerciser settings.
3. With ALL POWER OFF,checkthe9voltbattery. Replace,ifnecessary,witha
quality alkaline battery: Duracell MN1404, Everready 522, Panasonic 6AM6, or equivalent. See Figure 5.
1. With ALL POWER OFF, verify that exercise with load is turned on. Check DIP
switch S1 actuator 8. See Table B for generator exerciser settings.
(continued)
Series 185
9
381333–319 A
Series 185
INDEX
A
Automatic Generator Exerciser, light,
2
B
battery,clock,3
buttons, push, 2
Bypass Time Delay, button, 2, 6
C
cable spacers, 1
catalog number, inside cover
clock battery, 3
connections
electrical power, 1 engine control contact, 1
contacts
engine control, 1
control features, remote, 5
controller, 2–5
D
DIP switches, 3–5
dropout, 4
E
electrical operation, 2, 6
electrical power connections, 1
engine exerciser, 3
engine starting contacts, 3
F
features, see control features
frequency, pi ckup and dropout, 4
functional test, 6
G
generator
frequency, 4 settings, 4 starting contacts, 3 voltage, 4
GeneratorAcceptable,light,2,7
ground connection, inside cover
H
handle, maintenance, 6
warning, 6
harness, inside cover
HELP
800–800–2726 (ASCO) customercare@asco.com
I
indicator lights, 2
installation, 1
insulator, backing piece, 1
illustration of, 6 warning, 6
L
labels,
operator, transfer switch, 6 rating, cover
lights,2,7
Load on Generator, light, 2, 7
Load on Utility, light, 2, 7
M
manual operation, 6
illustration of, 6 warning, 6
mounting, 1
O
operation
electrical, 6 manual, 6 sequence of, 7
override momentary outages, 4
P
pickup, 4
problem, 8–9
R
rating label, cover
remote control features, 5
bypass transfer time delay, 5 remote test, 5 remote transfer to emergency, 5
S
service,
800–800–2726 (ASCO) customercare@asco.com
Set Engine Exerciser, button, 2, 3
settings
c h a n g i n g , 3 --- 5 f a c t o r y , 3 --- 5 frequency, 3, 4 phase, 4 time delay, 3, 4 voltage, 3, 4
source acceptable lights, 2
spacer, cable, 1
switches,DIP,3–5
T
TB7 generator start connections, 3
terminal block, 1
test, functional, 6
time delay
adjustment,3,4 gen–set cooldown, 4 how to change, 3 override momentary outages, 4 settings, 3–5 transfer to emergency, 4 transfer to normal, 4
timer (gen exerciser), how to set, 3
transfer switch position lights, 2
Transfer Test, button, 2, 6
troubleshooting, 8–9
U
unloadedrunning,gen.cooldown,4
Utility
failure, 7 frequency, 4 settings, 4 voltage, 4
Utility Acceptable, light, 2, 7
V
voltage, phase, 4
voltage, pickup & dropout settings, 4
voltage checks, 6
381333–319 A
Printed in U.S.A.
10
Copyright --- ASCO Power Technologies, L.P. 2008
Loading...