Emerson ASCO 108D10C DC Relay Panel, ASCO 173A19 Brochures and Data Sheets

ASCO Relay Control Panels
Applications
ASCO relay control panels were originally designed to New York City Board of Education specica­tions to operate ASCO DC solenoid valves controlling gas ow to school kitchens, domestic cooking classes, ceramic and metal shops. Because of its many features and silent opera­tion, the ASCO relay panel has also been used in many other similar institutions and schools outside New York City. Vandalism and malicious mischief have caused some city governments to make it mandatory that the gas supply be secured during hours when schools are closed. Other governmental bodies and consult­ing engineers have also recognized this need, and specify the ASCO relay panel even when not mandated by code. ASCO relay panels may also be used in industrial and commercial installa­tions where control of various gases and uids are important.
ASCO Relay Panel Catalog No 108D10C Input Voltage: 120 volts, 60Hz Output Voltage: 80 volts DC Output Current: 0.8 amp maximum
Operations
Operating the key switch on the control station energizes the relay, opening a normally closed ASCO DC solenoid valve which turns on the gas ow.
Panel Features
Reliability ASCO’s long experience in control assures a highly dependable system especially when used in combination with ASCO valves. If the control volt­age is lost completely, or reduces to approximately 50% of normal value, the relay de-energizes the normally­closed valve to shut off the gas ow. The gas may also be shut off by depressing the normally closed push­button switch located on the control station.
The valve will not open at restora­tion of voltage until an authorized person operates the key switch on the control station. This eliminates the danger of gas unknowingly escaping.
For convenience, auxiliary push-but­tons, ASCO Catalog numbers 173A19 and 173A20 may be located at various access points throughout the building, for immediate shutoff under emergency conditions.
Silent Operation Utilization of DC output provided by the relay panel to the valves elimi­nates constant AC hum.
Appearance Shallow-depth NEMA Type 1 ush mounted enclosure permits in-stalla­tion directly into the wall for conve­nience, and elimination of obstruc­tions in corridors or high trafc areas.
Long Life ASCO dust-tight industrial relay and solid-state rectier are designed to provide long life.
Ease of Installation Clearly marked terminals and instal­lation drawings located on inside of door.
Approvals Originally designed for and approved by the New York City Board of Education for use in public schools.
AC Relay Control Panel
Catalog No. 108D90C provides the same features as the DC panels previously described, except with 120/60 AC voltage output for AC valves. Features a key-operated switch with manual “on” and “off” buttons directly on the cover. 108D90C is for ush mount applica­tions and supports surface mount installations. The 108D90C is also available with 24 VAC, 24 VDC, 208 VAC, and 240 VAC output. Contact ASCO for further details.
Relay Control Panels
Dimensions
Control System Schematic
Master Control Station
Catalog No. 216C89 consists of a key-operated, normally-open switch and a normally-closed pushbutton mounted in a stainless steel faceplate for ush installation. Switches are labeled “Open” over the key switch and “Shut” over the pushbutton. Four inch square wall box is not included. Required for use with 108D10C; not applicable to 108D90C installs.
108D10C
216C89
Control Stations
Catalog No. 173A19 (ush mounted) and Catalog No 173A20 (surface mounted) consist of a mo­mentary mushroom push-button labeled “Emergency Stop”. When the button is depressed power to valves is shut off, cutting off gas ow in less than 0.1 seconds.
Solenoid Valves
Series 8215 Solenoid Valves feature 2-way normally-closed operation for gas service. They are explosion proof and designed to handle low pressure city gas. Control voltage is 80 to 90 volts DC or 120/60 volts AC.
173A19
DC Valves for use with Panel 108D10C
Pipe
Size
(ins.)
1/2 EF8215G20 25 4.4 11.6
3/4 EF8215G30 25 5.1 11.6
1 1/4 EF8215B60 25 32 14.9
1 1/2 EF8215B70 25 35 14.9
Catalog
Number
1 EF8215B50 25 21 14.9
2 EF8215B80 15 60 14.9
Max.
Pressure (psi)
CV
Flow
Factor
Holding
Watts
AC Valves for use with Panel 108D90C (replaces AEP7200)
Pipe Size
(ins.)
1/2 EF8215G20 50 4.4 10.1
3/4 EF8215G30 50 5.1 10.1
1 1/4 EF8215B60 25 32 15.4
1 1/2 EF8215B70 25 35 15.4
Catalog
Number
1 EF8215B50 25 21 15.4
2 EF8215B80 25 60 15.4
Max.
Pressure (psi)
CV
Flow
Factor
Holding
Watts
Solenoid Valves Order by Catalog Number and Voltage (Ex. EF8215G20 80-90VDC)
Contact ASCO Valve, Inc. at 800-972-2726 www.ascovalve.com
Gas Panels, Master Stations, and Control Stations Order by Catalog Number (Ex. 108D10C)
Contact ASCO Power Technologies at 800-800-2726 www.ascopower.com
Emerson Network Power