Battery Monitoring
For Business-Critical Continuity™
Alber® BDSi
™
Battery Monitoring System For UPS Battery Cabinet Integration
Alber technologies by Emerson Network Power are designed
to prevent battery failure, optimize useful battery life, reduce
maintenance costs and increase safety.
The Alber BDSi is designed specically for factory integration
into Liebert UPS battery cabinets for 12 and 16 volt battery
applications. A factory installed monitor continuously scans
and reports all critical battery parameters, providing detailed
reports that allow proactive battery management. The result:
a reliable, effective system that is efcient to deploy.
Key Features of Alber BDSI:
Flexibility
Web-based monitoring interface allows
easy user access to data and reports
A single controller unit communicates
with up to six DCM/LM units, for
monitoring of a total of six battery
cabinets
Factory installed, or eld installation
kits available for Liebert UPS battery
cabinets
Higher Availability
Alber BDSi Battery Monitoring provides real time
information for proactive battery management
Factory installation and testing ensures
proper operation at start up
Data tracking and detailed reports
allow analysis for proactive prevention
of battery failure
Lowest Total Cost of Ownership
Replace batteries when they are at
the end of their service life — not
by calculations that could result in
premature or late replacement
The Alber BDSi system consists of two units: a Controller, and a Data Collector
User-friendly software
provides easy to
interpret data
Battery Monitor Data
Manager (BMDM) Computer
Software is included with
every system. With the
software you can program
thresholds, view graphs
and trends to identify
failing batteries, set alarms
notications and distribute
reports. The reports have
built-in decision support
that analyzes the data and
provides suggestions for the
best corrective action.
Module/Load Module (DCM/LM).
The DCM/LM unit collects individual cell
data and performs the resistance test.
The Alber BDSi
Controller stores
the data, provides
alarms, power and
communication
connections
Easy to interpret graphs
make data understandable
and manageable
The rst battery cabinet includes both an Alber BDSi Controller and Alber BDSi
DCM/LM. Each additional battery cabinet uses only an Alber BDSi DCM/LM unit
linked to the single Controller Unit in the rst battery cabinet. A Controller can
communicate with up to six DCM/LM units or battery cabinets. Communication
options are by Ethernet network card, RS-232 or dial-up modem.
Liebert NXL battery cabinet with Alber
BDSi Battery Monitor. First battery
cabinet (center) with Controller and
DCM/LM. Additional battery cabinet
(right) with DCM/LM only.
Liebert APM battery
cabinet with DCM/LM
(top) and Controller
(bottom)
BDSi Specications
Sealed batteries are sensitive to temperature and float voltage settings.
Monitoring these conditions can considerably extend useful battery life.
A Liebert battery monitor provides the user with detailed information, allowing for cost savings by optimizing useful
battery life. Instead of waiting for an inevitable failure or replacing batteries prematurely to prevent problems, you
can continue to utilize your batteries longer and with condence by knowing their true internal condition.
It is essential to detect deterioration at an early stage to prevent catastrophic failures when dealing with sealed
batteries. This makes measurement technology the most important consideration when selecting a monitoring
system. Other battery monitors’ internal ohmic readings become inconsistent as the UPS load varies because of
variations in AC ripple on the battery. The Albér DC resistance test method is not inuenced by ripple and thus
provides data that is repeatable and reects the true condition of the battery.
Power
Less than 2.0 amps at 115 VAC ±10% 60Hz or 230 VAC +/- 10% 60Hz
Congurations: 40, 12-volt or 30, 16-volt jars per string
Inputs
Remote alarm reset: User-supplied 12 to 32V signal. (Less than 50ma.)
Momentarily applying voltage initiates the reset action
Outputs
24 VAC power: For up to six Data Collector Module Units
Alarm contacts: Two Form C: 2A at 30VDC.(One for critical alarm; one for maintenance alarm.)
Communication
Modbus protocol, ASCII to PC, and SNMP via Ethernet Local/LAN port, RS-232 DB-9 connec tor (rear panel)
LAN por t, RJ-45 RJ-11 Telco line, internal modem (optional)
USB for local PCV connection.
Data Storage
SRAM (8 MB) nonvolatile memory for all conguration settings and test data
Holds up to one year’s worth of data
Flash memor y for rmware upgrades
Operating Environment
Temperature range: 5°C to 40°C (41°F to 104°F) Indoor use only
Parameters/Features
Number of cell channels: Up to six strings of 40, 12 volt jars or 30, 16 volt jars
Measurement Range/Accuracy
Cell voltage: 0 - 16V, 0.15% of reading ±4mV Current transducer is required.
Cell Resistance 0 - 32000 μ½, 5% of reading ±5μ½ Transducer accuracy affects overall current reading accuracy.
String voltage: 0 - 400V, 0.1% of reading ±.1V 0 - 600V, 0.2% of reading
±.5V
Discharge Current: 0 - 600V, 0.1% of reading ±6A 0 -1000V, 0.1% of
reading ±10A
Float Current: 0 - 5000mA, ±0.1% of reading (Optional)
Packaging
Controller unit: 19.5”W (495.3mm) x 11.81”D (299.9mm) x 3.38”H (85.9mm)
Data Collector Module unit: 19.5”W (495.3mm) x 12.06”D (306.3mm) x 5.09”H (129.3mm)
Agency Approvals
UL listed CE approved
Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader
in enabling Business- Critical Continuity™ from grid to chip for telecommunication
networks, data centers, health care and industrial facilities. Emerson Network
Power provides innovative solutions and expertise in areas including AC and DC
power and precision cooling systems, embedded computing and power, integrated
racks and enclosures, power switching and controls, monitoring, and connectivity.
All solutions are supported globally by local Emerson Network Power service
technicians. Liebert AC power, precision cooling and monitoring products and
services from Emerson Network Power deliver Efficiency Without Compromise™
by helping customers optimize their data center infrastructure to reduce costs and
deliver high availability.
Emerson Network Power
Liebert Corporation
World Headquarters
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
United States Of America
800 877 9222 Phone (U.S. & Canada Only)
614 888 0246 Phone (Outside U.S.)
614 841 6022 FAX
Emerson Network Power
European Headquarters
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
Italy
39 049 9719 111 Phone
39 049 5841 257 FAX
Emerson Network Power Asia Pacific
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
+63 2 730 9572 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone
614 841 6755 (outside U.S.)
While every precaution has been taken to ensure accuracy
and completeness in this literature, Liebert Corporation
assumes no responsibility, and disclaims all liability for
damages resulting from use of this information or for any
errors or omissions.