Emerson Alber BDSi Brochures and Data Sheets

Battery Monitoring For Business-Critical Continuity™
Alber® BDSi
Battery Monitoring System For UPS Battery Cabinet Integration
Alber technologies by Emerson Network Power are designed to prevent battery failure, optimize useful battery life, reduce maintenance costs and increase safety.
The Alber BDSi is designed specically for factory integration into Liebert UPS battery cabinets for 12 and 16 volt battery applications. A factory installed monitor continuously scans and reports all critical battery parameters, providing detailed reports that allow proactive battery management. The result: a reliable, effective system that is efcient to deploy.
Key Features of Alber BDSI:
Flexibility
Web-based monitoring interface allows
easy user access to data and reports
A single controller unit communicates
with up to six DCM/LM units, for monitoring of a total of six battery cabinets
Factory installed, or eld installation
kits available for Liebert UPS battery cabinets
Higher Availability
Alber BDSi Battery Monitoring provides real time information for proactive battery management
Factory installation and testing ensures
proper operation at start up
Data tracking and detailed reports
allow analysis for proactive prevention of battery failure
Lowest Total Cost of Ownership
Replace batteries when they are at
the end of their service life — not by calculations that could result in premature or late replacement
Complete factory installation
eliminates requirement of eld installation
Ideally Suited for:
Liebert UPS external battery cabinets
Liebert NXL Liebert NX Liebert APM Liebert 16V battery cabinet
Simple hardware conguration
The Alber BDSi system consists of two units: a Controller, and a Data Collector
User-friendly software provides easy to interpret data
Battery Monitor Data Manager (BMDM) Computer Software is included with every system. With the software you can program thresholds, view graphs and trends to identify failing batteries, set alarms notications and distribute reports. The reports have built-in decision support that analyzes the data and provides suggestions for the best corrective action.
Module/Load Module (DCM/LM).
The DCM/LM unit collects individual cell
data and performs the resistance test.
The Alber BDSi
Controller stores the data, provides alarms, power and communication connections
Easy to interpret graphs make data understandable and manageable
The rst battery cabinet includes both an Alber BDSi Controller and Alber BDSi DCM/LM. Each additional battery cabinet uses only an Alber BDSi DCM/LM unit linked to the single Controller Unit in the rst battery cabinet. A Controller can communicate with up to six DCM/LM units or battery cabinets. Communication options are by Ethernet network card, RS-232 or dial-up modem.
Liebert NXL battery cabinet with Alber BDSi Battery Monitor. First battery cabinet (center) with Controller and DCM/LM. Additional battery cabinet (right) with DCM/LM only.
Liebert APM battery cabinet with DCM/LM (top) and Controller (bottom)
BDSi Specications
Sealed batteries are sensitive to temperature and float voltage settings. Monitoring these conditions can considerably extend useful battery life.
A Liebert battery monitor provides the user with detailed information, allowing for cost savings by optimizing useful battery life. Instead of waiting for an inevitable failure or replacing batteries prematurely to prevent problems, you can continue to utilize your batteries longer and with condence by knowing their true internal condition.
It is essential to detect deterioration at an early stage to prevent catastrophic failures when dealing with sealed batteries. This makes measurement technology the most important consideration when selecting a monitoring system. Other battery monitors’ internal ohmic readings become inconsistent as the UPS load varies because of variations in AC ripple on the battery. The Albér DC resistance test method is not inuenced by ripple and thus provides data that is repeatable and reects the true condition of the battery.
Power
Less than 2.0 amps at 115 VAC ±10% 60Hz or 230 VAC +/- 10% 60Hz
Congurations: 40, 12-volt or 30, 16-volt jars per string
Inputs
Remote alarm reset: User-supplied 12 to 32V signal. (Less than 50ma.)
Momentarily applying voltage initiates the reset action
Outputs
24 VAC power: For up to six Data Collector Module Units
Alarm contacts: Two Form C: 2A at 30VDC.(One for critical alarm; one for maintenance alarm.)
Communication
Modbus protocol, ASCII to PC, and SNMP via Ethernet Local/LAN port, RS-232 DB-9 connec tor (rear panel)
LAN por t, RJ-45 RJ-11 Telco line, internal modem (optional)
USB for local PCV connection.
Data Storage
SRAM (8 MB) nonvolatile memory for all conguration settings and test data
Holds up to one year’s worth of data
Flash memor y for rmware upgrades
Operating Environment
Temperature range: 5°C to 40°C (41°F to 104°F) Indoor use only
Parameters/Features
Number of cell channels: Up to six strings of 40, 12 volt jars or 30, 16 volt jars
Measurement Range/Accuracy
Cell voltage: 0 - 16V, 0.15% of reading ±4mV Current transducer is required.
Cell Resistance 0 - 32000 μ½, 5% of reading ±5μ½ Transducer accuracy affects overall current reading accuracy.
String voltage: 0 - 400V, 0.1% of reading ±.1V 0 - 600V, 0.2% of reading
±.5V
Discharge Current: 0 - 600V, 0.1% of reading ±6A 0 -1000V, 0.1% of
reading ±10A
Float Current: 0 - 5000mA, ±0.1% of reading (Optional)
Packaging
Controller unit: 19.5”W (495.3mm) x 11.81”D (299.9mm) x 3.38”H (85.9mm)
Data Collector Module unit: 19.5”W (495.3mm) x 12.06”D (306.3mm) x 5.09”H (129.3mm)
Agency Approvals
UL listed CE approved
Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business- Critical Continuity™ from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls, monitoring, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. Liebert AC power, precision cooling and monitoring products and services from Emerson Network Power deliver Efficiency Without Compromise™ by helping customers optimize their data center infrastructure to reduce costs and deliver high availability.
Emerson Network Power
Liebert Corporation World Headquarters 1050 Dearborn Drive P.O. Box 29186 Columbus, Ohio 43229 United States Of America 800 877 9222 Phone (U.S. & Canada Only) 614 888 0246 Phone (Outside U.S.) 614 841 6022 FAX
Emerson Network Power European Headquarters Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy 39 049 9719 111 Phone 39 049 5841 257 FAX
Emerson Network Power Asia Pacific 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 +63 2 730 9572 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone 614 841 6755 (outside U.S.)
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2011 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.
® Liebert is a registered trademark of the Liebert Corporation. SL-29206 (R08/11) Printed in USA
Emerson Network Power. The global leader in enabling Business-Critical Continuity
AC Power Connectivity DC Power
Embedded Computing Embedded Power
Infrastructure Management & Monitoring
EmersonNetworkPower.com
.
Outside Plant Power Switching & Controls Precision Cooling
Racks & Integrated Cabinets Services Surge Protection
Loading...