Emerson 381333234 E User Manual

Page 1
Operator’s
Automatic Transfer Switching Equipment
Manual
D–desi gn 30 through 230 ampere s
WARNING is used in this manual to warn of a hazardous situation which, if not avoided, could result in death or serious injury.
Series 200
Note: Refer to the outli n e and wiring drawings provided with your Series 200 ATSE for all installation and connection details and accessories.
Nameplate / rating Label
The Series 200 A utomatic Transfer Switching Equipment (ATSE) contains a nameplate / rating label which includes data for that specific ATSE. It defines the loads and fault circuit withstand/closing ratings. Refer to the labels on the Trans fer Switc h in g devic e for specific values and use the ATSE only within their limits.
CAUTION is used in this manual to warn of a hazardous situation which, if not avoided, could result in minor or moderate injury.
An experienced licensed electrician should install the ATS E .
Do not exceed the values on the rating label. Exceeding the rating can cause person injury or serious equipment damage.
TABLE OF CONTENTS
section
INSTALLATION 1.........................
SEQUENCE OF OPERATION 2............
TESTING & SERVICE 3...................
ADJUSTMENTS 4........................
CONTROL FEATURES 5..................
INDEX back of manual....................
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
381333–234 E
Page 2
A typical Catalog Number is shown below with its elements explained:
Catalog Number Identification
Typical D–design Series 200 ATS catalog no. for a solid neutral, 3 pole, 100 amp, 400 V, open type:
design prefix letter
D
Neutral
A –solid
B – switching
200
Phase Poles
2 –singleØ 3 –threeØ
C – overlapping
blank – none
* 200 & 230 A are limited to 480 volts
A 3 100 J 5X
Amperes Voltage Controller
30 70
100
150 200 * 230 *
C 208
D 220 E 230
F 240 G 277
H 380
J 400
K 415
L 440
M 460 N 480
5 –standard 5X –if
accessories
ordered
Page 3
SECTION 1 INSTALLATION
The ASCO Series 200 automatic transfer switching equipment (A TSE) consists of a transfer switching device, monitoring and transfer control device (controller), and membrane controls (for door mounting). The ATSE is factory tested. Installation requires mounting the devices into an appropriate size enclosur e and connection of power conductors, engine start signal wires, and auxiliary circuits.
Mounting
The Outline and Mounting Diagram furnished with the ATSE show s all mounting details and instructions.
NOTICE
Protect the automatic transfer switching equipment from construction grit and metal chips to prevent malfunction or shortened life of the transfer switching device.
Mount the transfer switch vertically in the back of the enclosure as shown on the Outline and Mounting Diagram provided. Level all mounting points of t he rigid supporting structure by using flat washers behind the holes to avoid forced distortion of the transfer switch.
Mount the membrane controls and the controller on the inside of the enclosure door as shown on the Outline and Mounting Diagram provided. The membrane controls must be accessible through a cutout in the door. Connect the membrane controls to the right side of the controller with the ribbon cable provided. Then connect the transfer switching device harness plugs to the left side of the controller. See Figures 1–1 and 1–2.
membrane controls
ribbon cable
controller
enclosure
door
controller must be within a steel enclosure
Figure 1-1. Membrane controls and controller mount-
ing on inside of enclosure door. Refer to
Outline & Mounting Diagram for mounting hardware.
gasket
cut out in enclosure
door
An add-on rail is provided for some optional accesso­ries. If provided, mounted it below the controller. Then make the connections shown on the Wiring Diagram.
Grounding
Grounding (earthing) is accomplished by mounting the automatic transfer switching equipment in a metal enclosure. Connect the control panel grounding wire (lower left side) to equipment (enclosure or clean earth) ground. This wire can be connected to the controller’s lower left mounting stud. Because the controller is mounted on a door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges. See Figure 1–3.
Figure 1-2. Membrane controls with gasket
suitable for IP65 enclosure.
2 plugs for transfer switching device harness
ground wire
mounting stud
Figure 1-3. Controller grounding (clean earth)
wire and other connections.
ribbon cable to membrane controls
connections for control features &
options
NOTICE
The controller must be grounded for proper operation.
1-- 1
Page 4
INSTALLATION (continued)
NOTICE
De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine generator starting control in the OFF position. Make sure engine generator is not in operation.
Power connections
A Wiring Diagram is furnished with the Series 200 ATSE. All wiring must be made in accordance with the local codes.
Do not run cables in front of the transfer switching device. Conductors can be bundled on the right side of the transfer switching device. Maintain proper electrical clearance between the live metal parts and grounded metal: 13 mm minimum.
It is not necessary to remove the barriers from the transfer switching device to install the conductors. If you do remove them, however, be sure to reinstall the barriers carefully.
Connect main source and load conductors to clearly marked power terminals on the transfer switching device. Be careful when stripping insulation from the conductors; avoid nicking or ringing the conductor. Remove surface oxides from conductors by cleaning with a wire brush. Follow conductor manufacturer’s instructions when aluminum conductor is used. Apply joint compound to conductor, then carefully wipe away excess compound. Tighten the terminals to the torque specified on the label on the transfer switching device.
Three conductor spacers must be located as shown for 150, 200, and 230 ampere transfer switching devices.
conductor spacers
38 mm approximate
conductor spacer
Figure 1-4. Required conductor spacers for
150, 200, & 230 amp transfer switching devices.
Engine Starting Contacts
The engine control contact connections (if used) are located on the transfer switching device. Connect signal wires to appropriate terminals as specified in Table A and shown in Figure 1–5.
Table A. Engine start connections
When normal
source fails
contact closes TB1 and TB2
contact opens TB1 and TB3
Te r m i na l s o n
transfer switching device
Three conductor spacers are included with 150, 200, and 230 ampere transfer switching devices. When installing power conductors, run them through the conductor spacers as shown in Figure 1–4. Position the spacers within 38 mm o f the power terminals.
ENGINE STARTING CONTACTS
( SHOWN DE–ENERGIZED )
TOP
STUD
MIDDLE
STUD
BOTTOM
STUD
1
TS
2
NR
3
NR
TB 1
TB 3
TB 2
Figure 1-5. Engine starting contact label and
location on left side of transfer switching device.
Interconnecting harness
Connect the plug–in harness (two plugs) from the transfer switching device to left side of the controller, if not already connected.
Auxiliary Circuits
Connect auxiliary circuit wires (if necessary) to appropriate terminals by referring to the Wiring Diagram.
1-- 2
Page 5
Functional Test
INSTALLATION (continued)
The Functional Test consists of three checks: manual operation, voltage checks, and electrical operation.
NOTICE
Do these checks in the order presented to avoid damaging the automatic transfer switching equipment.
Read all instructions on the Wiring Diagrams and labels affixed to the ATS. Note the control features that are provided and review their operation before proceeding .
1 – Manual Operation
A detachable manual operator handle is provided on the Transfer Switching device for maintenance purposes only. Manual operation of the transfer switching device must be checked before it is operated electrically.
Do not manually operate the transfer switching device until both power sources are disconnected: open both circuit breakers.
Position of the transfer switch is indicated here
weight marked N (normal) and E (emergency)
maintenance handle
weight
floating weight
With ALL POWER OFF grasp
maintenance handle and turn it
quickly with your thumb and fingers.
1. After deenergizing both power sources, open the enclosure door. Locateandthemaintenance handle on the left side of the transfer switching device. See Figure 1–6.
2. Grasp the attached maintenance handle and turn it with thumb and fingers as shown to manually operate it . The maintenance handle turns the opposite direction of the weight. Turn it up o r down as shown to manually operate the transfer switching device. It should o perate smoothly wit hout any binding. If it does not, check for shipping damage or construction debris.
3. Return the transfer switching device to the N (normal) position.
Now continue to 2–VoltageCheckson next page.
Figure 1-6. Maintenance handle and positions.
1-- 3
Page 6
INSTALLATION (continued)
Figure 1–7. Standard controls and indicators.
observe these lights
2–VoltageChecks
First check nameplate on transfer switching device; rated voltage must be the same as normal and emergency line voltages.
Use extreme caution when using a meter to measure voltages in the following steps. Do not touch power terminals; shock, burns, or death could result !
Perform steps 1 through 6 at the right. Observe the status lights. See Figure 1–7.
O Black circle means light is on.
P White circle means light is off.
* If necessary, adjust voltage regulator on the generator according to the manufacturer’s recommendations. The Automatic Transfer S witching Equipment will respond only to the rated voltage specified on the Transfer Switching device nameplate.
Also see page 4–1 for the HI–LOW voltage adjust setting in the controller. The LOW setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V.
Close the normal source circuit breaker. The Normal T ransfer Switch Position and the Normal
1
Source Accepted lights should come on.
Use an accurate voltmeter to check phase to phase and phase to neutral voltages pres-
2
entatthetransferswitchingde­vice normal source terminals.
Close the emergency source circuit breaker. (Start generator, if necessary.) The Emergency
3
Source Accepted light should come on.
Use an accurate voltmeter to check phase to phase and phase to neutral voltages pres-
4
entatthetransferswitchingde­vice emergency source termi­nals.*
Useaphaserotationmeterto check phase rotation of emer-
5
gency source; it must be the same
as the normal source.
Source Accepted
Normal
Emergency
Source Accepted
Normal
Emergency
W
V
U
1-- 4
Shut down the engine–genera­tor , if applicable. The Emergen- cy Source Accepted light should go off. Then put the starting
6
control selector switch (on the
Source Accepted
Normal
Emergency
generator set) in the automatic position. Close enclosure door.
Now continue to 3 – Electrical Operation on next page.
Page 7
pressthisbutton
INSTALLATION (continued)
observe these lights
Figure 1–8. Standard controls and indicators.
3 – Electrical Operation
This procedure will check the electrical operation of the Automatic Transfer Switching Equipment.
Close the automatic transfer switching equipment enclosure door and tighten the screws before you test electrical operation.
Tr ansfer Test
Both normal and emergency sources must be available and the emergency source generator (if used) must be capable of being started in this procedure.
Perform steps 1 through 8 at the right. Observe the status lights. See Figure 1–8.
O Black circle means light is on.
P White circle means light is off.
NOTE: If Motor Load Transfer feature is activated, then transfer may not occur i mmediately after the respective time delays. Transfer will only occur when the phase relationship betweensourcesiscorrect.
NOTE: The operating transfer time of the transfer switching device is 0,17 second maximum, which is measured from the time that power is applied to the operating coil of the transfer switching device until the main contacts close on the alternative source.
This completes the Functional T e st of the ASCO Series 200 A u tom atic Tr ans fer Switching Equipment. Leave the engine–generator starting control in the automatic position.
The normal source must be available and the generator must be ready to start.
1
Check that the Normal Source Accepted light is on.
Press and hold the Transfer Test button until the engine starts
2
and runs. This should happen within 15 sec.
The Emergency Source
3
Accepted light should come on.
The transfer switching device should transfer to the Emergency position. The
Emergency Transfer Switch
4
Position light should come on and the Normal light should go off.
If the transfer to emergency delay is used the transfer should occurs after a time delay
5
(up to 5 minutes). Forimmediatetransferpress the Bypass Time Delay button.
The transfer switching device should transfer back to the Normal position. The Normal
6
Transfer Switch Position light should come on and the Emergency light should go off.
If the retransfer to normal delay is used the retransfer should occur after a time delay
7
(up to 30 minutes). Forimmediateretransferpress the Bypass Time Delay button.
The unloaded running delay keeps the generator running for 5 minutes (cool–down period).
8
Then the generator should stop and the Emergency Source Accepted light should go off.
Source Accepted
Normal
Emergency
Trans fer
Tes t
Source Accepted
Normal
Emergency
Trans fer Switch
Position
Normal
Emergency
Bypass
Time Delay
Trans fer Switch
Position
Normal
Emergency
Bypass
Time Delay
Source Accepted
Normal
Emergency
1-- 5
Page 8
SECTION 2 SEQUENCE OF OPERATION
Lights show position of transfer switching device.
Transfer To Emergency
Thesequenceforloadtransferto emergency source begins automatically when normal source voltage falls below the preset dropout point or when Transfer Test button is pressed. An under voltage cond ition on any phase of the normal source is detected by the sensor.
When the no rmal source voltage fails or the Transfe r Test button is pressed, the SE relay de-ener­gizes and relay NR begins its timing cycle (1 or 3 seconds,
momentary n o rmal source outage delay) . The NR relay is provided with a time
delay on dropout to override momentary outages and prevent nuisance starting of the engine-driven generator. If the normal source vol tag e returns abov e the sensor dropout setting before the time delay expires, the NR relay timing cycle is reset to zero and relay SE energizes.
If the normal source voltage does not return above the sensor dropout setting before the time delay expires, the NR relay de-energizes and signals the engine-driven generator to start. At the same time, a voltage and frequency sensor begins monitoring the emergency source. The sensor will accept the emergency source only when both voltage and frequency reach preset pickup points. Usually about ten seconds elapse from dropout of the NR relay to acceptance by the sensor. This time span occurs because the engine-driven generator must crank, start, and run up to nominal pickup points. For this reason, if the Transfer Test buttonispresseditmustbe held for 15 seconds. If the emergency source is available immediately, the sensor may accept it as soon as NR relay drops out.
When the emergency source is accepted by the sensor, relay ER begins its timing cycle (transfer to emergency delay). ER relay is provided with an adjustable (0 to 5 minutes) time delay on pickup to delay transfer of the load to the emergency source. F or immediate transfer press Bypass Time Delay button.
ER relay energizes, the TS coil is energized, the transfer switching device operates, and all switch contacts (mains, controls, auxiliaries) reverse position. The transfer switch is now supplying the load from the emergency source.
The tra nsfer switching device will remai n i n the Emergencyposition untilthe normal source is restored. If the Transfer Test button is used, the transfer switching device will remain on emergency until the retransfer to normal delay times out.
Hold 15 sec.to start the engine generator and to transfer the load to emergency.
Press to cancel the active exercise period (stops engine now or after cooldown) See page 5–1.
Lights show the sources accepted.
Light for built–in
engine exercise timer:
³ blinks rapidly when
button is held 5 sec.
while being set
³ blinks slowly when
button is released (set) and during 20 min. exercise period.
³ stays on after engine
stops (exerciser is
enabled for weekly
operation)
Seepage5–1
Hold 5 sec 20 min. engine exercise period immediately (engine starts) and weekly thereafter.
.toset
for complete
instructions
Figure 2–1. Membrane controls and indicator lights.
Retransfer to Normal
The sequence for load retransfer to the normal source automatically begins when the voltage sensor detects restoration of the normal source. The voltage level must rise above the preset pickup point on all phases before the sensor will accept the normal source.
When the normal source is accepted by the sensor, relay SE begins its timing cycle (adjustable 1 sec. to 30 min., retransfer to normal delay). For immediate retransfer press Bypass Time Delay button. SE relay is provided with a time delay on pickup to prevent immediate load retransfer to the normal source. The delay insures that the normal source has stabilized before reconnection of vital loads. If the normal source voltage falls below the present dropout point before the time delay expires, the timing cycle is reset to zero. If the emergency source fails for more than 4 seconds duringthe timingcycle, ER relay drops out and the load is immediately retransferred to the normal source, if that source is acceptable.
SE relay energizes and ER relay is dropped out. The TS coil is energized, the transfer switching device oper­ates, and all switch contacts (mains, controls, auxilia­ries) reverse position. The transfer switching device i s now supplying the load from the normal source again.
Upon retransfer to the normal source, NR relay begins its timing cycle (unloaded running delay [engine cool- down] ). NR relay is provided with a 5 minute time delay on pickup to keep the engine running for a cool-down period.
NR relay energizes after the time delay and signals the engine-driven generator to shut down. All circuits are reset for any future normal source failure.
Activation of standard control features shown in Section 5 will alter the sequence of operation and introduce additional time delays during transfer operations.
2 --- 1
Page 9
SECTION 3 TESTING & SERVICE
PREVENTIVE MAINTENANCE
Reasonable care in preventive maintenance will insure high reliability and long life for the automatic transfer switch.
Operate the switch at least once a month.Performthis four step Electrical Operation Test. This is a test with load transfer.
Transfer Switch Test
1. Press and hold the door-mounted TRANSFER SWITCH TEST button until the engine starts and
runs. This should happen within 15 seconds.
2. The transfer switching device will operate to the Emergency position. If the Transfer To Emer- gency Delay isused, the transfer willoccur after a time delay (up to 5 minutes). For immediate transfer press BYPASS TIME DELAY button.
3. The transfer sw itching device will operate back to Normal position after the Retransfer To Nor- mal Delay (up to 30 minutes). For immediate retransfer press BYPASS TIME DELAY button.
4. Unloaded Running (Engine Cooldown) Delay allows engine to run unloaded for 5 minutes.
Clean and inspect the switch once a year. De-energize all sources, then brush and vacuum away any excessive dust accumulation. Remove the transfer switch barriers and check contact condition. The non–replaceable main contacts are designed to last the life of the transfer switch. Rein stal l the barriers carefully.
Maintain transfer switch lubrication.Thetransfer switch has been properly lubricated, and under normal operating conditions no further lubricating is required. Renew factory lubrication if the switch is subjected to severe dust or abnormal operating conditions. Re l u b r icate the solenoid oper ato r if a coil is replac ed . Do not use oil. Order lubrication 625550–001 (Castrol EndurexR 4000 lubricant).
DISCONNECTING THE CONTROLLER
The harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged. If the controller must be isolated, follow these steps carefully.
Disconnecting the Plugs
1. Observe the position of the transfer switching device. a. If the transfer switching device is in the Normal
position, place standby engine starting control in the off position. Then open the emergency source circuit breaker.
b. If the transfer switching device is in the Emergency
position, open the normal source circuit breaker. Place the engine starting control in the test or run position.
2. Separate the quick disconnect plugs by squeezing
the latches. Do not pull on the harness wires.
3. Label, remove, and tape the signal wires connected
to the engine start terminals on the transfer switch­ing device: TB1 and TB3, or TB1 and TB2.
Reconnecting the Plugs
1. Observe the position of the transfer switching device. a. If the transfer switch is in the Normal position, be
sure that the standby engine starting control is still in the off position. The emergency source circuit breaker still should be open.
b. If the transfer switch is in the Emergency position,
normal source circuit breaker still should be open.
2. Reconnect the signal wires connected to the
appropriate engine start terminals on the transfer switch. See Section 1, Engine Starting Contacts.
3. The harness plugs and sockets are keyed. Caref ully
align the plugs with the sockets and press straight in until both latches click.
4. Restore the opposite source as follows: a. If the transfer switch is in the Normal position,
place the standby engine starting control in the automatic position. Then close the emergency source circuit breaker.
b. IfthetransferswitchisintheEmergency position,
close the normal source circuit breaker. The load will be automatically retransferred to the normal source after the Retransfer to Normal Delay. F or immediate retransfer, press BYPASS TIME DELAY button. Place the engine starting control in the automatic position.
Replacement parts. Replacement parts are available in kit form. When ordering parts provide the Serial No. and Catalog No. from the transfer switch nameplate. Contact your local ASCO Power Technologies sales office.
3-- 1
Page 10
TESTING & SERVICE
PROBLEM
(continued)
MANUAL LOAD TRANSFER
This procedure will manually transfer the load if the controller is disconnected.
Do not manually operate the transfer switching device until both power sources are disconnected: open both circuit breakers.
TROUBLE-SHOOTING
Note the control features that are activated or furnished on the switch and review their operation. Refer to Section 5, Control Features.
Table 3-1. Trouble-Shooting Checks.
1OPERATION 2 GEN-SET 3VOLTAGE
Gen-Set does not start when the TRANSFER SWITCH TEST button is pressed and held for 15 seconds or when the normal source fails.
T ransfer switching device does not transfer the load to emergency source after the gen-set starts.
T ransfer switching device does not transfer the load to normal source when normal returns or when TRANSFER SWITCH TEST button is released.
Gen-Set does not stop after load retransfer to the normal source.
Hold the TRANSFER SWITCH TEST button 15 sec. or the outage must be long enough to allow for the 1 or 3 sec.
Momentary Normal Source Outage Delay plus engine
cranking and starting time.
Wait for T ransfer to Emergen- cy Delay (0 to 5 min.) to time out. For immediate transfer, press the BYPASS TIME DELAY button. If Motor Load Transfer is active, wait for in­phase condition (see below).
Wait for Retransfer to Normal Delay (1 sec. to 30 min.) to time out. For immediate re– transfer, press BYPASS TIME DELAY button. If Motor Load Transfer is active, wait for in­phase condition (see below).
Wait for the 5 minute Unloaded Running Delay to time out.
1. Open normal and emergency source circuit
breakers.
2. Use the maintenance handle to manually operate
transfer switching device to the opposite source. See page 1–4, Manual Operation Test.
3. If the transfer switching device is in the
Emergency position manually start the engine generator and then close the emergency source circuit breaker.
Proceed with care! The automatic transfer switching equipment is energized.
CHECK IN NUMERICAL SEQUENCE
Starting control must be in automatic position. Batteries must be charged and connected. Check wiring to engine starting contacts.
Generator output circuit breaker must be closed. Generator frequency must be at least 95% of nominal (48Hzfora50Hzsystem).
Starting control must be in automatic position.
Voltmeter should read at least 90% of nominal phase to phase voltage between transfer switch terminals U2 and W2 (or L1 and L5 for 2 pole switches). *
* These are factory settings.
Voltmeter should read at least 90% of nominal phase to phase voltage between transfer switching device terminalsV1andW1,W1and U1, and U1 and V1 (or L2 and L6 for 2 pole switches).
Trouble-Shooting the Motor Load Transfer Feature (refer to page 5–3)
3. Press and hold should transfer to emergency source when meter
Use extreme caution when using a meter to measure voltages in the following steps. Do not touch powe r terminals; shock, burns, or death could result !
1. Connect a voltmeter (set for twice system phase–to–phase voltage) between transfer switching device terminals U1 and U2 (for 3 pole) or L1 and L2 (for 2 pole).
2. Manually start generator. Voltmeter needle should sweep back and forth at a regular rate between 0
needle is near 0 volts. If transfer does not occur, Motor L oad Transfer feature is not operating.
4. Release the Tra n sf e r Te s t button. The load should retransfer back to the normal source after the Retransfer to Normal Delay,ifused. Theretransfer should occur when the needle is near 0 volts. If retransfer does not occur after the time delay, the Motor L oad Transfer feature is not operating.
5. For immediate retransfer, press the Bypass Time Delay button. Then disconnect the voltmeter.
and about twice system voltage.
If the problem is isolated to circuits on the controller or the transfer switching device, call your local ASCO Power Te ch no lo gi es sa le s office. Furnish Serial No., B i ll of Ma t e rial (B O M ) No., & C a talog No . from t h e transfer switching device nameplate.
3-- 2
the Tr a n s fe r Tes t button. The load
Page 11
SECTION 4 ADJUSTMENTS
y
OverrideMomentary
TDE
S
T
TIMER
0minute
s
0to
5
——P
R
lTIME
R
30minutes
1secondto
——P
DESCRIPTIONLABELSSETTIN
G
S1DIP
PU/NP
ick
EmergencySourceVolt
equecy60/50
Vol
P
h
LOW/
Vol
Adj
)
LOW
/
H
I
Time Delay Adjustment
Standard time delays are set to customer specifications (if none specified, standard factory settings are used).
Table4-1.TimeDelaySettings
DESCRIPTION LABELS
Override Momentar
Normal Source Outages
ransfer toEmergency
Override Momentary
Emergency S. Outages
etransfer toNorma
Unloaded Running
(Engine Cooldown)
FACTORY
SETTING
3seconds
TIMER 0 minutes 0to5
N/E
4seconds non-adjustable
TIMER 30 minutes 1secondto
E/N
5 minutes non-adjustable
(full ccw)
(full cw)
ADJUSTMENT
RANGE
1second Actuator 1 on
3seconds Actuator 1 off
minutes
30 minutes
Sensor Adjustments
Voltage and frequency sensor pickup and dropout points are set to customer specifications (if none specified, stan dard factory settings are used). To change a setting, follow procedure on page 4–2. Use Tables 4-2 and 4–3 for settings and corresponding DIP switch actuators.
To change a setting, follow procedure on page 4-2. Use Table 4-1 as a guide to time delay values and their corre­sponding adjustment DIP switch or potentiometer.
S3 DIP
SWITCH
1
1
ADJUSTMENT
POTENTIOMETER
2
1
NOTICE
Any change in these settings may affect the normal operation of the automatic transfer switching equipment. This change could allow the load circuits to remain connected to a low voltage source.
Table 4-2. Voltage and Frequency Settings. ( Shaded DIP switches are standard factory settings).
Normal Source Voltage
EmergencySource Volt-
age
Emergency Source
Frequency
tage
ases 3 4 ,14 3 4/1 4 3 4
%ofnominal
FACT. S ET ADJ RANGE
up 90 %
DO/N Dropout
–– Pickup 90 % non-adjustable –– Dropout 75 % non-adjustable –– Pickup 95 % non-adjustable –– Dropout 85 % non-adjustable
60/50
Hz
60/50Hz 60Hz
85 %
95 % * Actuator 3 off
90 % Actuator 3 on
90 % *
85 %
80 %
70 %
60 Hz Actuator 4 off
50 Hz Actuator 4 on
3phase Actuator 6 off
1phase Actuator 6 on
Actuator 1 off Actuator 2 off
Actuator 1 on Actuator 2 off
Actuator 1 off Actuator 2 on
Actuator 1 on Actuator 2 on
––
––
S1 DIP
SWITCH
* If dropout voltage is set to 90%, the pickup voltage must be set to 95%.
3
3
21
21
21
21
4
4
6
6
Table 4-3. Transformer Voltage Adjust.
(Low setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V, or 480 V to 460 V)
DESCRIPTION LABELS FAC TORY SET TING ADJUSTMENT S3 DIP SWITCH
tage
ust(4.2%
HI
LOW Actuator 2 off
HI Actuator 2 on
4-- 1
2
2
Page 12
ADJUSTMENTS
(continued)
NOTICE
Do not make any setting changes while the controller is energized.
How to Change a Setting
1. Prevent the transfer switching device from operat­ing by disconnecting one source first, then the other, as follows:
a. If the transfer switching device is in the Normal
position, ope n the emergency source circuit breaker. Turn the engine starting control to off. Then open the normal source circuit breaker.
b. If the transfer switching device is in the
Emergency position, open the normal source circuit breaker. Turn engine starting control to test or run. Then open the emergency source circuit breaker.
2. Disconnect bot h harness plugs from controller by squeezing the latches. Do not pull on the wires.
3. Remove cover from the controller by releasing latch on right side with your thumb. See Figure 4-1.
4. Locate the appropriate adjustment potentiometer or DIP switch for the setting that you want to change. Refer to Table 4-1 and Table 4–2 on page 4-1 and Figure 4-2, Figure 4–3, Figure 4–4 on page 4–2.
5. Use a small screwdriver to turn the potentiometer clockwise to increase the time delay or counter­clockwisetodecreaseit. SeeFigure4-3.
6. Use a ball-point pen (or similar pointed tool) to slide the switch actuators left or right so they match the illustrationnext to the setting(left = off, right= on). Recheck the setting. See Figure 4-4.
7. Install the cover on the controller by hooking it on the left side and latching the right side.
8. Reconnect both harness plugs to the controller by aligning and pressing straight in until lat ches click.
Close the automatic transfer switching equipment enclosure door and tighten the screws before restoring power.
9. Close the enclosure door, then restore bothsources:
a. If the transfer switching device is in the Normal
position first close the normal source circuit breaker, then close the emergency source cir­cuit breaker.
b. If the transfer switching device is in the
Emergency position, close the normal source circuit breaker. The load will be automatically retransferred to the normal source. Then close the emergency source circuit breaker.
cover
thumb latch
hook on left side
Figure 4-1. Controller cover latch.
J5
harness
plugs
retransfer to normal
time delay
S3 DIP
switch
S1 DIP
switch
S2 DIP
switch
transfer to
emergency
time delay
Figure 4-2. Location of potentiometers,
DIP switches, battery, and battery jumper.
clockwise to
increase
P1 or P2
potentiometer
counterclockwise
to decrease
Figure 4-3. Changing time delay potentiometers.
DIP
switches
SW1 SW2 SW3
actuator
(8 on each DIP switch)
onoff
Figure 4-4. Setting DIP switch actuators.
9volt
alkaline
battery
battery on/off
jumper
P1
P2
10. Turn the engine starting control to automatic.
4-- 2
Page 13
SECTION 5 CONTROL FEATURES – ENGINE EXERCISERS
These ti mers periodically exercise the emergency engine-generator plant. They can be set to exercise with or without load transfer, or they can be completelydisabled. The engine-generator should be exercised under load once a week for a minimum time period of 20 minutes, or follow the recommendations of the e ngine-generator set manufacturer. Refer to page 4–2 for location of DIP switches, battery (provided), and jumper block in the controller.
BUILT–IN ENGINE EXERCISER
The engineexerciser included in the Series 200 automatic transfer switching device provides a once a week 20–minute exercise period. It occurs immediately the SET ENGINE EXERCISER push button is pressed (and held
for at least 5 seconds), and then at the same
time weekly thereafter. A 9 volt alkaline battery (DuracellR MN1604, EverreadyR 522, or PanasonicR 6AM6) is furnished and installed in the controller to maintain the setting. T he battery jumper block must shifted to the ON position
. See Figure 4–2 on page 4–2.
Fill in day and time set. Week Day ______ Time _______.
Press to cancel an active exercise period (stops generator).
If Exercise with Load is set, retransfers load to Normal, then stops generator after min. cooldown.
when
be
FUNCTION
Std. Timer
Enabled
Std. Timer
Disabled
Exercise
without
Load
Exercise
with Load
Shaded DIP switches are standard factory settings.
DIP Switch Settings
S1 DIP
SWITCH
Actuator
7on
Actuator
7off
Actuator
8off
Actuator
8on
status light
Press and hold for 5 sec blinks rapidly to set exercise period immediately and every week hereafter (generator starts).
7
7
8
8
. or until status light
If Exerciser with Load is set, transfers load to Emergency.
SWITCH
Actuator
5on
Actuator
5on
S2 DIP
5
5
Figure 5-1. Operator panel pushbuttons and light.
Select below either Exercise without Load or Exercise with Load according to the setting of DIP switchS1, actuator 8. The load transfers from the Normal source to Emergency source (generator) and back again if Exercise with Load is selected.
Exercise without Load, DIP Switch S1, Actuator 8 off
8
How to Set Built–In Timer
Step Function Explanation
Push Button Status Light
SET ENGINE
1
EXERCISER
hold
5sec.
2 release
press BYPASS
3
TIME DELAY
blinks rapidly
FfFfFf
blinks slowly
FffFff
set exercise period
exercise period now active Generator starts and runs.
Exercise the generator now and
every week at this time hereafter.
F stays on cancel active exercise period Generator stops.
4 F stays on generator off Exerciser enabled; repeats every 7 days.
Exercise with Load, DIP Switch S1, Actuator 8 on
8
How to Set Built–In Timer
Step Function Explanation
Push Button Status Light
SET ENGINE
1
EXERCISER
hold
5sec.
2 release
press BYPASS
3
TIME DELAY
blinks rapidly
FfFfFf
blinks slowly
FffFff
blinks slowly
FffFff
set exercise period
exercise period now active
cancel active exercise period
Exercise the generator now and
every week at this time hereafter.
Generator starts and runs;
the load transfers to Emergency.
The load retransfers to Normal; then
generator runs for 5 minute cooldown
( light blinks slowly during cooldown ).
4 F stays on generator off Exerciser enabled; repeats every 7 days.
NOTE:EverytimeSET ENGINE EXERCISER push button is pressed (held 5 seconds) the exercise period is changed.
5-- 1
Page 14
CONTROL FEATURES (continued)
OPTIONAL PROGRAMMABLE ENGINE EXERCISER (Accessory 11CD)
The optional programmable engine exerciser provides seven days of different exercise periods. The timer is connected and mounted below the controller. A permanent backup battery maintains the setting; when power is lost to timer, output switch deenergizes.
DIP Switch Settings
FUNCTION
Opt. Timer
Enabled
Opt. Timer
Disabled
Exercise
without
Load
Exercise
with
Load
SWITCH
Actuator
7off
Actuator
7off
Actuator
8off
Actuator
8on
S1 DIP
7
7
8
8
Shaded DIP switches are standard factory settings.
SWITCH
Actuator
5off
Actuator
5on
S2 DIP
5
5
The Accessory 11CD Programmable Engine Exerciser incorporates a 7 day time base, and therefore, each day of the week can be uniquely programmed to test the engine generator set either with or without load. The proper controller settings must be made to determine whether or not the test will be conducted with or without load (refer topage5–1forproperselection). Forconvenience,Block Programming is also provided,wherebyuptosevendays can be grouped together if the ON and OFF times are the same.
See next page for instructions on setting the timer.
5-- 2
Page 15
CONTROL FEATURES (continued)
g
p
g
How to Set Optional Programmable Engine Exerciser (Accessory 11CD)
on/off button
reset
Proceed with care! The automatic transfer switching equipment is energized.
Setting the Clock (Time and Day)
Step Press Button Display Meaning
1234567 (blink)
1 reset
2
hold h,then
press ±1h
Note Repeat step 2 to toggle between
military (blank display) and AM/PM time.
hold ¬
(clock symbol)
3
±1h once
4
5
6
7
8 release ¬ :blinking
(if Daylight
Saving Time)
h (hold for
fast count)
m (hold for
fast count)
Day Mo Tu We Th Fr
00 00
¬ f
1234567 AM 12 00
¬ f
1234567 (blink)
00 00
¬ f
±1h
[00] 00 hour
00 [00] minute
Sa Su
after self-test,
clears memory
military 24 hr
or AM/PM 12 hr time
hold ¬ while
setting thru
step 7
do nothing if it
is Standard
Time.
day
time & date set,
clock starts
Programming Engine On-Off Period(s)
Step Press Button Display Meaning
1
2 hand ¬ on
3 h start hour
4 m start minute
5 Day start day
Note Successive pressing displays blocks of days:
6
7
8 h stop hour
9 m stop minute
10 Day stop day
11 ¬ :blinking program set
Prog.
(do not
hold)
Mon–Sat, Mon–Fri, Sat & Sun (1 is Monday)
Prog. 1234567
Press hand
(2 times)
1234567
–– : ––
–– : ––
f
begin
start engine
begin
off
stop engine
button
program button
display
clock button
Figure 5-2. Exerciser display and push buttons
Changing or Checking Time Programs
By operating the Prog. butto n, the individual commands as programmed can, at any time, be brought consecutively into the display for revision or checking. Revisions are accomplished by programming over the existing programs using the steps at the left.
Canceling Time Programs
After the selecting the desired program, use the h and m buttons to set hours and minutes to zero; the ––:–– will
be displayed. This program has been made ineffective and will no longer be carried out. To cancel all programs, press the Res. (reset) button. This clears all memory including the time base and program storage.
Manual Override
Do not manually override the exerciser unless you are sure that the controller has been set for exercisewithoutload(seepage5–2).Failuretodo so could result in possible injury if the transfer switch operates whil e the enclosur e door is open.
Step Press Button Display Meaning
1 hand ¬ hand on
2 hand [ ¬ ] permanent on
3 hand [ f ] permanent off
4 hand ¬ f back to automatic
Daylight Savings / Standard Time Change
To change to Daylight Savings time (Summertime), press the ¦1h button once. Clock advances by one hour and +1h appears in display. To change to Standard Time (Greenwich mean time in UK, Middle European time in Germany), press the ¦1h button again; the clock sets back one hour and +1h disappears.
±1h button
hour button
minute button
day button
5-- 3
Page 16
CONTROL FEATURES (continued)
INPHASE MONITOR
FOR MOTOR LOAD TRANSFER
Inphase monitoring logic controls transfer and retransfer of motor loads, so that inrush currents do not exceed normal starting currents. It avoids nuisance tripping of circuit breakers and mechanical damage to motor couplings.
The Motor Load Transfer feature is built into the controller. DIP switch S1 (actuator 5) activates this feature: right = ON, left = OFF.
FUNCTION S1 DIP SWITCH
enable Actuator 5 on
disable Actuator 5 off
Shaded DIP switches are standard factory settings.
Note
If the Motor Load Transfer feature is enabled, it will be activated following
the Load Disconnect Feature Delay Before Transfer delay.
5
5
LOAD DISCONNECT FEATURE
Connect external circuits to the terminals indicated on the Wiring Diagram provided with the ATSE.
The double throw (Form C) contact is rated for 28 VDC or 120 VAC (5 amps resistive). The contact operates prior to a selectable 0, 3, 10, or 20 second delay before transfer of the automatic transfer switching device. The contact resets either immediately following transfer or after the same
delay as set for pre–signal before transfer.
Time delay between the load disconnect control signal and initiation of transfer i s set on the controller with DIP switch S2 (actuators 6, 7, 8) as shown below:
Delay Before Transfer
LD TDBT S2 DIP SWITCH
0 (disable)
3seconds
10 seconds
20 seconds
Actuator 7 on Actuator 8 on
Actuator 7 on Actuator 8 off
Actuator 7 off Actuator 8 on
Actuator 7 off Actuator 8 off
87
87
87
87
Shaded DIP switches are standard factory settings.
Delay After Transfer*
LD TDAT S2 DIP SWITCH
enable Actuator 6 on
disable Actuator 6 off
6
6
*Enabling the Delay After Transfer wi ll cause the control signal to reset after the same delay
as set for the Delay
Before Transfer.
REMOTE CONTROL FEATURES
These remote control features require a customer–supplied normally closed contact suitable for a 5 V dc low energy circuit. Refer to the Wiring Diagram provided with the ATS. Activate appropriate DIP switch S2 actuators below.
Remote Test (terminals CP6–7)
RTSW S2 DIP SWITCH
disable Actuator 3 on
enable Actuator 3 off
3
3
Remote Transfer to Emergenc y (CP8–9)
RT /E S2 DIP SWITCH
disable Actuator 2 on
enable Actuator 2 off
2
2
Bypass Transfer Time Delay (CP12–13)
TD E/N BYP. S2 DIP SWITCH
disable Actuator 1 on
enable Actuator 1 off
1
1
Inhibit Transfer to Emergency (CP10–11)
N/E INHIB. S2 DIP SWITCH
disable Actuator 4 on
enable Actuator 4 off
5-- 4
4
4
Page 17
Page 18
INDEX
A
accessories, 5–2, 5–3, 5–4
auxiliary circuits, 1–3
B
barriers, 1–2
battery, 4–2, 5–1
buttons, push, 3–1
bypass time delay, 1–5, 2–1, 3–1
C
catalog number, inside cover
cleaning, 3–1
conductors
preparation, 1–2 terminals, 1–2
connections
engine control contact, 1–2 power, 1–2
control features, 5–1
load disconnect, 5–4 motor load transfer, 5–4 plant exerciser, 5–1
controller (control panel), 4–1, 4–2
codes, cover cover removal, 4–2 disconnecting, 3–1 time delay potentiometers, 4–2
D
DIP Switches, 4–1, 4–2, 5–1, 5–2,
5–4
E
electrical operation, 1–5
engine exerciser, 5–1, 5–2, 5–3
engine starting contacts, 1–2
F
failure
see trouble-shooting, 3–2
features, see control features
frequency, pi ckup and dropout
settings, 4–1
functional test, 1–3, 1–4, 1–5
H
harness, 1–1
disconnect plugs, 3–1
HELP
800–800–2726 (ASCO) customercare@asco.com
I
inphase monitor, 5–4
inspection, 3–1
installation, 1–1
L
labels,
rating, cover
lights, 1–5, 5–1
load disconnect feature, 5–4
lubrication, 3–1
M
maintenance, preventive, 3–1
manual load transfer, 3–2
warning, 3–2
manual operation, 1–3
illustration of, 1–3 warning, 1–3
motorloadtransferfeature,5–3
N
nameplate, cover
O
operation
electrical, 1–5 manual, 1–3
illustration of, 1–3 warning, 1–3
sequence of, 2–1
P
parts, 3–1
problem, 3–2
programmableengineexerciser,
5–2, 5–3
R
remote control features, 5–4
bypass transfer time delay, 5–4 inhibit transfer to emergency,
5–4 remote test, 5–4 remote transfer to emergency,
5–4
replacement parts, 3–1
S
service
800–800–2726 (ASCO) customercare@asco.com
set engine exerciser, 5–1
settings
changing, 4–1 factory, 4–1 frequency, 4–1 phase, 4–1 time delay, 4–1 voltage, 4–1
T
terminal block, 1–3
test, functional, 1–3, 1–4, 1–5
time delay
adjustment, 4–1 gen–set cooldown, 4–1 how to change, 4–2 override momentary outages, 4–1 settings, 4–1 transfer to emergency, 4–1 transfer to normal, 4–1
timer (plant exerciser), how to set,
5–1
transfer switch test, 1–5, 3–1
trouble–shooting, 3–2
inphase monitor, 5–4
V
voltage, phase, 4–1
voltage, pickup and dropout set-
tings, 4–1
Printed in U.S.A.
E 2011 ASCO Power Technologies, L.P.
Loading...