DANGER is used in this manual to warn of a
hazard situation which, if not avoided, will result
in death or serious injury .
WARNING is used in this manual to warn of a
hazardous situation which, if not avoided, could
result in death or serious injury.
Series 200
Note: Refer to the outli n e and wiring drawings
provided with your Series 200 ATSE for all
installation and connection details and accessories.
Nameplate / rating Label
The Series 200 A utomatic Transfer Switching Equipment
(ATSE) contains a nameplate / rating label which includes
data for that specific ATSE. It defines the loads and fault
circuit withstand/closing ratings. Refer to the labels on the
Trans fer Switc h in g devic e for specific values and use the
ATSE only within their limits.
CAUTION is used in this manual to warn of a
hazardous situation which, if not avoided, could
result in minor or moderate injury.
An experienced licensed electrician should install the
ATS E .
Do not exceed the values on the rating label.
Exceeding the rating can cause person injury or
serious equipment damage.
TABLE OF CONTENTS
section
INSTALLATION1.........................
SEQUENCE OF OPERATION2............
TESTING & SERVICE3...................
ADJUSTMENTS4........................
CONTROL FEATURES5..................
INDEXback of manual....................
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA
For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
381333–234 E
Page 2
A typical Catalog Number is shown below with its elements explained:
Catalog Number Identification
Typical D–design Series 200 ATS catalog no. for a solid neutral, 3 pole, 100 amp, 400 V, open type:
design
prefix
letter
D
Neutral
A –solid
B – switching
200
Phase Poles
2 –singleØ
3 –threeØ
C – overlapping
blank – none
* 200 & 230 A are limited to 480 volts
A3100J5X
AmperesVoltageController
30
70
100
150
200 *
230 *
C 208
D 220
E 230
F 240
G 277
H 380
J 400
K 415
L 440
M 460
N 480
5 –standard
5X –if
accessories
ordered
Page 3
SECTION 1INSTALLATION
The ASCO Series 200 automatic transfer switching
equipment (A TSE) consists of a transfer switching device,
monitoring and transfer control device (controller), and
membrane controls (for door mounting). The ATSE is
factory tested. Installation requires mounting the devices
into an appropriate size enclosur e and connection of
power conductors, engine start signal wires, and auxiliary
circuits.
Mounting
The Outline and Mounting Diagram furnished with the
ATSE show s all mounting details and instructions.
NOTICE
Protect the automatic transfer switching
equipment from construction grit and metal chips
to prevent malfunction or shortened life of the
transfer switching device.
Mount the transfer switch vertically in the back of the
enclosure as shown on the Outline and MountingDiagram provided. Level all mounting points of t he
rigid supporting structure by using flat washers behind
the holes to avoid forced distortion of the transfer
switch.
Mount the membrane controls and the controller on the
inside of the enclosure door as shown on the Outlineand Mounting Diagram provided. The membrane
controls must be accessible through a cutout in the
door. Connect the membrane controls to the right side
of the controller with the ribbon cable provided. Then
connect the transfer switching device harness plugs to
the left side of the controller. See Figures 1–1 and 1–2.
membrane
controls
ribbon
cable
controller
enclosure
door
controller
must be within a
steel enclosure
Figure 1-1. Membrane controls and controller mount-
ing on inside of enclosure door. Refer to
Outline & Mounting Diagram for mounting hardware.
gasket
cut out in
enclosure
door
An add-on rail is provided for some optional accessories. If provided, mounted it below the controller. Then
make the connections shown on the Wiring Diagram.
Grounding
Grounding (earthing) is accomplished by mounting the
automatic transfer switching equipment in a metal
enclosure. Connect the control panel grounding wire
(lower left side) to equipment (enclosure or clean earth)
ground. This wire can be connected to the controller’s
lower left mounting stud. Because the controller is
mounted on a door, a conductive strap must be used
between the enclosure and the door. This connection
provides proper grounding which does not rely upon the
door hinges. See Figure 1–3.
Figure 1-2. Membrane controls with gasket
suitable for IP65 enclosure.
2 plugs for
transfer
switching
device
harness
ground
wire
mounting
stud
Figure 1-3. Controller grounding (clean earth)
wire and other connections.
ribbon cable
to membrane
controls
connections
for control
features &
options
NOTICE
The controller must be grounded for proper
operation.
1-- 1
Page 4
INSTALLATION(continued)
NOTICE
De–energize the conductors before making
any line or auxiliary circuitry connections.
Be sure that Normal and Emergency line
connections are in proper phase rotation.
Place engine generator starting control in the
OFF position. Make sure engine generator is not
in operation.
Power connections
A Wiring Diagram is furnished with the Series 200
ATSE. All wiring must be made in accordance with the
local codes.
Do not run cables in front of the transfer switching
device. Conductors can be bundled on the right side of
the transfer switching device. Maintain proper electrical
clearance between the live metal parts and grounded
metal: 13 mm minimum.
It is not necessary to remove the barriers from the
transfer switching device to install the conductors. If
you do remove them, however, be sure to reinstall the
barriers carefully.
Connect main source and load conductors to clearly
marked power terminals on the transfer switching
device. Be careful when stripping insulation from the
conductors; avoid nicking or ringing the conductor.
Remove surface oxides from conductors by cleaning
with a wire brush. Follow conductor manufacturer’s
instructions when aluminum conductor is used. Apply
joint compound to conductor, then carefully wipe away
excess compound. Tighten the terminals to the torque
specified on the label on the transfer switching device.
Three conductor spacers must be located as
shown for 150, 200, and 230 ampere transfer
switching devices.
conductor spacers
38 mm approximate
conductor spacer
Figure 1-4. Required conductor spacers for
150, 200, & 230 amp transfer switching devices.
Engine Starting Contacts
The engine control contact connections (if used) are
located on the transfer switching device. Connect signal
wires to appropriate terminals as specified in Table A
and shown in Figure 1–5.
Table A. Engine start connections
When normal
source fails
contact closesTB1 and TB2
contact opensTB1 and TB3
Te r m i na l s o n
transfer switching device
Three conductor spacers are included with 150, 200,
and 230 ampere transfer switching devices. When
installing power conductors, run them through the
conductor spacers as shown in Figure 1–4. Position the
spacers within 38 mm o f the power terminals.
ENGINE STARTING CONTACTS
( SHOWN DE–ENERGIZED )
TOP
STUD
MIDDLE
STUD
BOTTOM
STUD
1
TS
2
NR
3
NR
TB 1
TB 3
TB 2
Figure 1-5. Engine starting contact label and
location on left side of transfer switching device.
Interconnecting harness
Connect the plug–in harness (two plugs) from the
transfer switching device to left side of the controller, if
not already connected.
Auxiliary Circuits
Connect auxiliary circuit wires (if necessary) to
appropriate terminals by referring to the WiringDiagram.
1-- 2
Page 5
Functional Test
INSTALLATION(continued)
The Functional Test consists of three checks: manual
operation, voltage checks, and electrical operation.
NOTICE
Do these checks in the order presented to avoid
damaging the automatic transfer switching
equipment.
Read all instructions on the Wiring Diagrams and labels
affixed to the ATS. Note the control features that are
provided and review their operation before proceeding .
1 – Manual Operation
A detachable manual operator handle is provided on the
Transfer Switching device for maintenance purposes only.
Manual operation of the transfer switching device must
be checked before it is operated electrically.
Do not manually operate the transfer switching
device until both power sources are
disconnected: open both circuit breakers.
Position of the transfer switch is indicated here
weight marked N (normal)
and E (emergency)
maintenance
handle
weight
floating
weight
With ALL POWER OFF grasp
maintenance handle and turn it
quickly with your thumb and fingers.
1.After deenergizing both power sources, open the
enclosure door. Locateandthemaintenance
handle on the left side of the transfer switching
device. See Figure 1–6.
2.Grasp the attached maintenance handle and turn it
with thumb and fingers as shown to manually
operate it . The maintenance handle turns the
opposite direction of the weight. Turn it up o r down
as shown to manually operate the transfer switching
device. It should o perate smoothly wit hout any
binding. If it does not, check for shipping damage
or construction debris.
3.Return the transfer switching device to the N
(normal) position.
Now continue to 2–VoltageCheckson next page.
Figure 1-6. Maintenance handle and positions.
1-- 3
Page 6
INSTALLATION(continued)
Figure 1–7. Standard controls and indicators.
observe these lights
2–VoltageChecks
First check nameplate on transfer switching device;
rated voltage must be the same as normal and
emergency line voltages.
Use extreme caution when using a meter to
measure voltages in the following steps.
Do not touch power terminals; shock, burns, or
death could result !
Perform steps 1 through 6 at the right. Observe the status
lights. See Figure 1–7.
O Black circle means light is on.
P White circle means light is off.
* If necessary, adjust voltage regulator on the generator
according to the manufacturer’s recommendations. The
Automatic Transfer S witching Equipment will respond
only to the rated voltage specified on the Transfer
Switching device nameplate.
Also see page 4–1 for the HI–LOW voltage adjust
setting in the controller. The LOW setting shifts all
voltage settings down 4.2%; for example, 240 V to 230
V.
Close the normal source circuit
breaker. The Normal T ransferSwitch Position and the Normal
1
Source Accepted lights should
come on.
Use an accurate voltmeter to
check phase to phase and
phase to neutral voltages pres-
2
entatthetransferswitchingdevice normal source terminals.
Close the emergency source
circuit breaker. (Start generator,
if necessary.) The Emergency
3
Source Accepted light should
come on.
Use an accurate voltmeter to
check phase to phase and
phase to neutral voltages pres-
Useaphaserotationmeterto
check phase rotation of emer-
5
gency source; it must be the
same
as the normal source.
Source Accepted
Normal
Emergency
Source Accepted
Normal
Emergency
W
V
U
1-- 4
Shut down the engine–generator , if applicable. The Emergen-cy Source Accepted light should
go off. Then put the starting
6
control selector switch (on the
Source Accepted
Normal
Emergency
generator set) in the automatic
position. Close enclosure door.
Now continue to 3 – Electrical Operation on next page.
Page 7
pressthisbutton
INSTALLATION(continued)
observe these lights
Figure 1–8. Standard controls and indicators.
3 – Electrical Operation
This procedure will check the electrical operation of the
Automatic Transfer Switching Equipment.
Close the automatic transfer switching
equipment enclosure door and tighten the
screws before you test electrical operation.
Tr ansfer Test
Both normal and emergency sources must be available
and the emergency source generator (if used) must be
capable of being started in this procedure.
Perform steps 1 through 8 at the right. Observe the status
lights. See Figure 1–8.
O Black circle means light is on.
P White circle means light is off.
NOTE: If Motor Load Transfer
feature is activated, then transfer may
not occur i mmediately after the
respective time delays. Transfer will
only occur when the phase relationship
betweensourcesiscorrect.
NOTE: The operating transfer time of the transfer
switching device is 0,17 second maximum, which is
measured from the time that power is applied to the
operating coil of the transfer switching device until the
main contacts close on the alternative source.
This completes the Functional T e st of the ASCO
Series 200 A u tom atic Tr ans fer Switching Equipment.
Leave the engine–generator starting control in the
automatic position.
The normal source must be
available and the generator
must be ready to start.
1
Check that the Normal SourceAccepted light is on.
Press and hold the Transfer Test
button until the engine starts
2
and runs. This should happen
within 15 sec.
The Emergency Source
3
Accepted light should come on.
The transfer switching device
should transfer to the
Emergency position. The
Emergency Transfer Switch
4
Position light should come on
and the Normal light should go
off.
If the transfer to emergencydelay is used the transfer
should occurs after a time delay
5
(up to 5 minutes).
Forimmediatetransferpress
the Bypass Time Delay button.
The transfer switching device
should transfer back to the
Normal position. The Normal
6
Transfer Switch Position light
should come on and the
Emergency light should go off.
If the retransfer to normal delay
is used the retransfer should
occur after a time delay
7
(up to 30 minutes).
Forimmediateretransferpress
the Bypass Time Delay button.
The unloaded running delay
keeps the generator running for
5 minutes (cool–down period).
8
Then the generator should stop
and the Emergency SourceAccepted light should go off.
Source Accepted
Normal
Emergency
Trans fer
Tes t
Source Accepted
Normal
Emergency
Trans fer Switch
Position
Normal
Emergency
Bypass
Time Delay
Trans fer Switch
Position
Normal
Emergency
Bypass
Time Delay
Source Accepted
Normal
Emergency
1-- 5
Page 8
SECTION 2SEQUENCE OF OPERATION
Lights show position of transfer switching device.
Transfer To Emergency
Thesequenceforloadtransferto
emergencysourcebegins
automaticallywhennormal
source voltage falls below the
preset dropout point or when
Transfer Test button is pressed. An
under voltage cond ition on any
phase of the normal source is
detected by the sensor.
When the no rmal
source voltage fails
or the Transfe r Test
button is pressed, the
SE relay de-energizes and relay NR
begins its timing
cycle (1 or 3 seconds,
momentary n o rmal
source outage delay) . The NR relay is provided with a time
delay on dropout to override momentary outages and
prevent nuisance starting of the engine-driven generator.
If the normal source vol tag e returns abov e the sensor
dropout setting before the time delay expires, the NR
relay timing cycle is reset to zero and relay SE energizes.
If the normal source voltage does not return above the
sensor dropout setting before the time delay expires, the
NR relay de-energizes and signals the engine-driven
generator to start. At the same time, a voltage and
frequency sensor begins monitoring the emergency
source. The sensor will accept the emergency source only
when both voltage and frequency reach preset pickup
points. Usually about ten seconds elapse from dropout of
the NR relay to acceptance by the sensor. This time span
occurs because the engine-driven generator must crank,
start, and run up to nominal pickup points. For this
reason, if the Transfer Test buttonispresseditmustbe
held for 15 seconds. If the emergency source is available
immediately, the sensor may accept it as soon as NR relay
drops out.
When the emergency source is accepted by the sensor,
relay ER begins its timing cycle (transfer to emergencydelay). ER relay is provided with an adjustable (0 to 5
minutes) time delay on pickup to delay transfer of the
load to the emergency source. F or immediate transfer
press Bypass Time Delay button.
ER relay energizes, the TS coil is energized, the
transfer switching device operates, and all switch
contacts (mains, controls, auxiliaries) reverse position.
The transfer switch is now supplying the load from the
emergency source.
The tra nsfer switching device will remai n i n the
Emergencyposition untilthe normal source is restored.
If the Transfer Test button is used, the transfer switching
device will remain on emergency until the retransfer tonormal delay times out.
Hold 15 sec.to
start the engine
generator and to
transfer the load
to emergency.
Press to cancel the
active exercise period
(stops engine now or
after cooldown) See
page 5–1.
Lights show the sources accepted.
Light for built–in
engine exercise timer:
³ blinks rapidly when
button is held 5 sec.
while being set
³ blinks slowly when
button is released (set)
and during 20 min.
exercise period.
³ stays on after engine
stops (exerciser is
enabled for weekly
operation)
Seepage5–1
Hold 5 sec
20 min. engine exercise
period immediately (engine
starts) and weekly thereafter.
.toset
for complete
instructions
Figure 2–1. Membrane controls and indicator lights.
Retransfer to Normal
The sequence for load retransfer to the normal source
automatically begins when the voltage sensor detects
restoration of the normal source. The voltage level
must rise above the preset pickup point on all phases
before the sensor will accept the normal source.
When the normal source is accepted by the sensor,
relay SE begins its timing cycle (adjustable 1 sec. to 30
min., retransfer to normal delay). For immediate
retransfer press Bypass Time Delay button. SE relay is
provided with a time delay on pickup to prevent
immediate load retransfer to the normal source. The
delay insures that the normal source has stabilized
before reconnection of vital loads. If the normal source
voltage falls below the present dropout point before the
time delay expires, the timing cycle is reset to zero. If
the emergency source fails for more than 4 seconds
duringthe timingcycle, ER relay drops out and the load
is immediately retransferred to the normal source, if
that source is acceptable.
SE relay energizes and ER relay is dropped out. The TS
coil is energized, the transfer switching device operates, and all switch contacts (mains, controls, auxiliaries) reverse position. The transfer switching device i s
now supplying the load from the normal source again.
Upon retransfer to the normal source, NR relay begins
its timing cycle (unloaded running delay [engine cool-down] ). NR relay is provided with a 5 minute time
delay on pickup to keep the engine running for a
cool-down period.
NR relay energizes after the time delay and signals the
engine-driven generator to shut down. All circuits are
reset for any future normal source failure.
Activation of standard control features shown in Section
5 will alter the sequence of operation and introduce
additional time delays during transfer operations.
2 --- 1
Page 9
SECTION 3TESTING & SERVICE
PREVENTIVE MAINTENANCE
Reasonable care in preventive maintenance will insure
high reliability and long life for the automatic transfer
switch.
Operate the switch at least once a month.Performthis
four step Electrical Operation Test. This is a test with
load transfer.
Transfer Switch Test
1. Press and hold the door-mounted TRANSFER
SWITCH TEST button until the engine starts and
runs. This should happen within 15 seconds.
2. The transfer switching device will operate to the
Emergency position. If the Transfer To Emer-gency Delay isused, the transfer willoccur after
a time delay (up to 5 minutes). For immediate
transfer press BYPASS TIME DELAY button.
3. The transfer sw itching device will operate back
to Normal position after the Retransfer To Nor-mal Delay (up to 30 minutes). For immediate
retransfer press BYPASS TIME DELAY button.
4. Unloaded Running (Engine Cooldown) Delay
allows engine to run unloaded for 5 minutes.
Clean and inspect the switch once a year. De-energize
all sources, then brush and vacuum away any excessive
dust accumulation. Remove the transfer switch barriers
and check contact condition. The non–replaceable main
contacts are designed to last the life of the transfer switch.
Rein stal l the barriers carefully.
Maintain transfer switch lubrication.Thetransfer
switch has been properly lubricated, and under normal
operating conditions no further lubricating is required.
Renew factory lubrication if the switch is subjected to
severedustorabnormaloperatingconditions.
Re l u b r icate the solenoid oper ato r if a coil is replac ed .
Do not use oil. Order lubrication 625550–001 (Castrol
EndurexR 4000 lubricant).
DISCONNECTING THE CONTROLLER
The harness disconnect plugs are furnished for repair
purposes only and should not have to be unplugged. If the
controller must be isolated, follow these steps carefully.
Disconnecting the Plugs
1. Observe the position of the transfer switching device.
a. If the transfer switching device is in the Normal
position, place standby engine starting control in the
off position. Then open the emergency source circuit
breaker.
b. If the transfer switching device is in the Emergency
position, open the normal source circuit breaker.
Place the engine starting control in the test or run
position.
2. Separate the quick disconnect plugs by squeezing
the latches. Do not pull on the harness wires.
3. Label, remove, and tape the signal wires connected
to the engine start terminals on the transfer switching device: TB1 and TB3, or TB1 and TB2.
Reconnecting the Plugs
1. Observe the position of the transfer switching device.
a. If the transfer switch is in the Normal position, be
sure that the standby engine starting control is still
in the off position. The emergency source circuit
breaker still should be open.
b. If the transfer switch is in the Emergency position,
normal source circuit breaker still should be open.
2. Reconnect the signal wires connected to the
appropriate engine start terminals on the transfer
switch. See Section 1, Engine Starting Contacts.
3. The harness plugs and sockets are keyed. Caref ully
align the plugs with the sockets and press straight in
until both latches click.
4. Restore the opposite source as follows:
a. If the transfer switch is in the Normal position,
place the standby engine starting control in the
automatic position.Then close the emergency
source circuit breaker.
b. IfthetransferswitchisintheEmergency position,
close the normal source circuit breaker. The load will
be automatically retransferred to the normal source
after the Retransfer to Normal Delay. F or immediate
retransfer, press BYPASS TIME DELAY button.
Place the engine starting control in the automatic
position.
Replacement parts. Replacement parts are available in
kit form. When ordering parts provide the Serial No. and
Catalog No. from the transfer switch nameplate.
Contact your local ASCO Power Technologies sales
office.
3-- 1
Page 10
TESTING & SERVICE
PROBLEM
(continued)
MANUAL LOAD TRANSFER
This procedure will manually transfer the load if the
controller is disconnected.
Do not manually operate the transfer switching
device until both power sources are
disconnected: open both circuit breakers.
TROUBLE-SHOOTING
Note the control features that are activated or
furnished on the switch and review their operation.
Refer to Section 5, Control Features.
Table 3-1. Trouble-Shooting Checks.
1OPERATION2 GEN-SET3VOLTAGE
Gen-Set does not start when
the TRANSFER SWITCH TEST
button is pressed and held for
15 seconds or when the
normal source fails.
T ransfer switching device
does not transfer the load to
emergency source after the
gen-set starts.
T ransfer switching device
does not transfer the load to
normal source when normal
returns or when TRANSFERSWITCH TEST button is
released.
Gen-Set does not stop after
load retransfer to the normal
source.
Hold the TRANSFER SWITCHTEST button 15 sec. or the
outage must be long enough
to allow for the 1 or 3 sec.
Momentary Normal Source
Outage Delay plus engine
cranking and starting time.
Wait for T ransfer to Emergen-cy Delay (0 to 5 min.) to time
out. For immediate transfer,
press the BYPASS TIMEDELAY button. If Motor Load
Transfer is active, wait for inphase condition (see below).
Wait for Retransfer to NormalDelay (1 sec. to 30 min.) to
time out. For immediate re–
transfer, press BYPASS TIMEDELAY button. If Motor Load
Transfer is active, wait for inphase condition (see below).
Wait for the 5 minute
Unloaded Running Delay to
time out.
1. Open normal and emergency source circuit
breakers.
2. Use the maintenance handle to manually operate
transfer switching device to the opposite source.
See page 1–4, Manual Operation Test.
3. If the transfer switching device is in the
Emergency position manually start the engine
generator and then close the emergency source
circuit breaker.
Proceed with care! The automatic transfer
switching equipment is energized.
CHECK IN NUMERICAL SEQUENCE
Starting control must be in
automatic position. Batteries
must be charged and
connected. Check wiring to
engine starting contacts.
Generator output circuit
breaker must be closed.
Generator frequency must be
at least 95% of nominal
(48Hzfora50Hzsystem).
—
Starting control must be in
automatic position.
Voltmeter should read at least
90% of nominal phase to
phase voltage between
transfer switch terminals U2
and W2 (or L1 and L5 for 2
pole switches). *
* These are factory settings.
Voltmeter should read at least
90% of nominal phase to
phase voltage between
transfer switching device
terminalsV1andW1,W1and
U1, and U1 and V1 (or L2 and
L6 for 2 pole switches).
—
—
Trouble-Shooting the Motor Load Transfer Feature (refer to page 5–3)
3. Press and hold
should transfer to emergency source when meter
Use extreme caution when using a meter to
measure voltages in the following steps. Do not
touch powe r terminals; shock, burns, or death
could result !
1. Connect a voltmeter (set for twice system
phase–to–phase voltage) between transfer
switching device terminals U1 and U2 (for 3 pole)
or L1 and L2 (for 2 pole).
2. Manually start generator. Voltmeter needle should
sweep back and forth at a regular rate between 0
needle is near 0 volts. If transfer does not occur,
Motor L oad Transfer feature is not operating.
4. Release the Tra n sf e r Te s t button. The load should
retransfer back to the normal source after the
Retransfer to Normal Delay,ifused. Theretransfer
should occur when the needle is near 0 volts. If
retransfer does not occur after the time delay, the
Motor L oad Transfer feature is not operating.
5. For immediate retransfer, press the Bypass TimeDelay button. Then disconnect the voltmeter.
and about twice system voltage.
If the problem is isolated to circuits on the controller or the transfer switching device, call your local ASCO
Power Te ch no lo gi es sa le s office. Furnish Serial No., B i ll of Ma t e rial (B O M ) No., & C a talog No . from t h e
transfer switching device nameplate.
3-- 2
the Tr a n s fe r Tes t button. The load
Page 11
SECTION 4ADJUSTMENTS
y
OverrideMomentary
TDE
S
—
T
TIMER
0minute
s
0to
5
——P
R
lTIME
R
30minutes
1secondto
——P
DESCRIPTIONLABELSSETTIN
G
S1DIP
PU/NP
ick
EmergencySourceVolt
equecy60/50
Vol
P
h
LOW/
Vol
Adj
)
LOW
/
H
I
Time Delay Adjustment
Standard time delays are set to customer specifications
(if none specified, standard factory settings are used).
Table4-1.TimeDelaySettings
DESCRIPTIONLABELS
Override Momentar
Normal Source Outages
ransfer toEmergency
Override Momentary
Emergency S. Outages
etransfer toNorma
Unloaded Running
(Engine Cooldown)
FACTORY
SETTING
3seconds
TIMER0 minutes0to5
N/E
—4secondsnon-adjustable———
TIMER30 minutes1secondto
E/N
—5 minutesnon-adjustable———
(full ccw)
(full cw)
ADJUSTMENT
RANGE
1secondActuator 1 on
3secondsActuator 1 off
minutes
30 minutes
Sensor Adjustments
Voltage and frequency sensor pickup and dropout
points are set to customer specifications (if none
specified, stan dard factory settings are used). To change
a setting, follow procedure on page 4–2. Use Tables 4-2
and 4–3 for settings and corresponding DIP switch
actuators.
To change a setting, follow procedure on page 4-2. Use
Table 4-1 as a guide to time delay values and their corresponding adjustment DIP switch or potentiometer.
S3 DIP
SWITCH
1
1
ADJUSTMENT
POTENTIOMETER
2
1
NOTICE
Any change in these settings may affect the
normal operation of the automatic transfer
switching equipment. This change could allow
the load circuits to remain connected to a low
voltage source.
Table 4-2. Voltage and Frequency Settings. (Shaded DIP switches are standard factory settings).
* If dropout voltage is set to 90%, the pickup voltage must be set to 95%.
3
3
21
21
21
21
4
4
6
6
Table 4-3. Transformer Voltage Adjust.
(Low setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V, or 480 V to 460 V)
DESCRIPTIONLABELSFAC TORY SET TINGADJUSTMENTS3 DIP SWITCH
tage
ust(4.2%
HI
LOWActuator 2 off
HIActuator 2 on
4-- 1
2
2
Page 12
ADJUSTMENTS
(continued)
NOTICE
Do not make any setting changes while the
controller is energized.
How to Change a Setting
1. Prevent the transfer switching device from operating by disconnecting one source first, then the
other, as follows:
a.If the transfer switching device is in the Normal
position, ope n the emergency source circuit
breaker. Turn the engine starting control to off.
Then open the normal source circuit breaker.
b.If the transfer switching device is in the
Emergency position, open the normal source
circuit breaker. Turn engine starting control to
test or run. Then open the emergency source
circuit breaker.
2. Disconnect bot h harness plugs from controller by
squeezing the latches. Do not pull on the wires.
3. Remove cover from the controller by releasing latch
on right side with your thumb. See Figure 4-1.
4. Locate the appropriate adjustment potentiometer or
DIP switch for the setting that you want to change.
Refer to Table 4-1 and Table 4–2 on page 4-1 and
Figure 4-2, Figure 4–3, Figure 4–4 on page 4–2.
5. Use a small screwdriver to turn the potentiometer
clockwise to increase the time delay or counterclockwisetodecreaseit. SeeFigure4-3.
6. Use a ball-point pen (or similar pointed tool) to
slide the switch actuators left or right so they match
the illustrationnext to the setting(left = off, right=
on). Recheck the setting. See Figure 4-4.
7. Install the cover on the controller by hooking it on
the left side and latching the right side.
8. Reconnect both harness plugs to the controller by
aligning and pressing straight in until lat ches click.
Close the automatic transfer switching
equipment enclosure door and tighten the
screws before restoring power.
9. Close the enclosure door, then restore bothsources:
a.If the transfer switching device is in the Normal
position first close the normal source circuit
breaker, then close the emergency source circuit breaker.
b.If the transfer switching device is in the
Emergency position, close the normal source
circuit breaker. The load will be automatically
retransferred to the normal source. Then close
the emergency source circuit breaker.
cover
thumb
latch
hook on
left side
Figure 4-1. Controller cover latch.
J5
harness
plugs
retransfer
to normal
time delay
S3 DIP
switch
S1 DIP
switch
S2 DIP
switch
transfer to
emergency
time delay
Figure 4-2. Location of potentiometers,
DIP switches, battery, and battery jumper.
clockwise to
increase
P1 or P2
potentiometer
counterclockwise
to decrease
Figure 4-3. Changing time delay potentiometers.
DIP
switches
SW1
SW2
SW3
actuator
(8 on each DIP switch)
onoff
Figure 4-4. Setting DIP switch actuators.
9volt
alkaline
battery
battery
on/off
jumper
P1
P2
10. Turn the engine starting control to automatic.
4-- 2
Page 13
SECTION 5 CONTROL FEATURES – ENGINE EXERCISERS
These ti mers periodically exercise the emergency engine-generator plant. They can be set to exercise with or without
load transfer, or they can be completelydisabled. The engine-generator should be exercised under load once a week for
a minimum time period of 20 minutes, or follow the recommendations of the e ngine-generator set manufacturer. Refer
to page 4–2 for location of DIP switches, battery (provided), and jumper block in the controller.
BUILT–IN ENGINE EXERCISER
The engineexerciser included in the Series 200 automatic
transfer switching device provides a once a week
20–minute exercise period. It occurs immediately
the SET ENGINE EXERCISER push button is pressed
(and held
for at least 5 seconds), and then at the same
time weekly thereafter.A 9 volt alkaline battery
(DuracellR MN1604, EverreadyR 522, or PanasonicR
6AM6) is furnished and installed in the controller to
maintain the setting. T he battery jumper block must
shifted to the ON position
. See Figure 4–2 on page 4–2.
Fill in day and time set. Week Day ______ Time _______.
Press to cancel an active exercise
period (stops generator).
If Exercise with Load is set, retransfers load to
Normal, then stops generator after min. cooldown.
when
be
FUNCTION
Std. Timer
Enabled
Std. Timer
Disabled
Exercise
without
Load
Exercise
with Load
Shaded DIP switches are standard factory settings.
DIP Switch Settings
S1 DIP
SWITCH
Actuator
7on
Actuator
7off
Actuator
8off
Actuator
8on
status light
Press and hold for 5 sec
blinks rapidly to set exercise period immediately
and every week hereafter (generator starts).
7
7
8
8
. or until status light
If Exerciser with Load is set,
transfers load to Emergency.
SWITCH
Actuator
5on
Actuator
5on
S2 DIP
5
5
Figure 5-1. Operator panel pushbuttons and light.
Select below either Exercise without Load or Exercise with Load according to the setting of DIP switchS1, actuator 8. The
load transfers from the Normal source to Emergency source (generator) and back again if Exercise with Load is selected.
Exercise without Load, DIP Switch S1, Actuator 8 off
8
How to Set Built–In Timer
StepFunctionExplanation
Push ButtonStatus Light
SET ENGINE
1
EXERCISER
hold
5sec.
2release
press BYPASS
3
TIME DELAY
blinks rapidly
FfFfFf
blinks slowly
FffFff
set exercise period
exercise period now activeGenerator starts and runs.
Exercise the generator now and
every week at this time hereafter.
F stays oncancel active exercise periodGenerator stops.
4—F stays ongenerator offExerciser enabled; repeats every 7 days.
Exercise with Load, DIP Switch S1, Actuator 8 on
8
How to Set Built–In Timer
StepFunctionExplanation
Push ButtonStatus Light
SET ENGINE
1
EXERCISER
hold
5sec.
2release
press BYPASS
3
TIME DELAY
blinks rapidly
FfFfFf
blinks slowly
FffFff
blinks slowly
FffFff
set exercise period
exercise period now active
cancel active exercise period
Exercise the generator now and
every week at this time hereafter.
Generator starts and runs;
the load transfers to Emergency.
The load retransfers to Normal; then
generator runs for 5 minute cooldown
( light blinks slowly during cooldown ).
4—F stays ongenerator offExerciser enabled; repeats every 7 days.
NOTE:EverytimeSET ENGINE EXERCISER push button is pressed (held 5 seconds) the exercise period is changed.
The optional programmable engine exerciser provides
seven days of different exercise periods. The timer is
connected and mounted below the controller. A
permanent backup battery maintains the setting; when
power is lost to timer, output switch deenergizes.
DIP Switch Settings
FUNCTION
Opt. Timer
Enabled
Opt. Timer
Disabled
Exercise
without
Load
Exercise
with
Load
SWITCH
Actuator
7off
Actuator
7off
Actuator
8off
Actuator
8on
S1 DIP
7
7
8
8
Shaded DIP switches are standard factory settings.
SWITCH
Actuator
5off
Actuator
5on
S2 DIP
5
5
The Accessory 11CD Programmable Engine Exerciser
incorporates a 7 day time base, and therefore, each day of
the week can be uniquely programmed to test the engine
generator set either with or without load. The proper
controller settings must be made to determine whether or
not the test will be conducted with or without load (refer
topage5–1forproperselection). Forconvenience,Block
Programming is also provided,wherebyuptosevendays
can be grouped together if the ON and OFF times are the
same.
See next page for instructions on setting the timer.
5-- 2
Page 15
CONTROL FEATURES (continued)
g
p
g
How to Set Optional Programmable Engine Exerciser (Accessory 11CD)
on/off button
reset
Proceed with care! The automatic transfer
switching equipment is energized.
Setting the Clock (Time and Day)
StepPress ButtonDisplayMeaning
1234567 (blink)
1reset
2
hold h,then
press ±1h
↓
NoteRepeat step 2 to toggle between
military (blank display) and AM/PM time.
hold ¬
(clock symbol)
3
±1h once
4
5
6
7
8release ¬:blinking
(if Daylight
Saving Time)
h (hold for
fast count)
m (hold for
fast count)
DayMo Tu We Th Fr
00 00
¬ f
1234567
AM 12 00
¬ f
1234567 (blink)
00 00
¬ f
±1h
[00] 00hour
00 [00]minute
Sa Su
after self-test,
clears memory
military 24 hr
or AM/PM
12 hr time
hold ¬ while
setting thru
step 7
do nothing if it
is Standard
Time.
day
time & date set,
clock starts
Programming Engine On-Off Period(s)
StepPress ButtonDisplayMeaning
1
2hand¬on
3hstart hour
4mstart minute
5Daystart day
NoteSuccessive pressing displays blocks of days:
6
7
8hstop hour
9mstop minute
10Daystop day
11¬:blinkingprogram set
Prog.
(do not
hold)
Mon–Sat, Mon–Fri, Sat & Sun (1 is Monday)
Prog.1234567
Press hand
(2 times)
1234567
–– : ––
–– : ––
f
begin
start engine
begin
off
stop engine
button
program
button
display
clock
button
Figure 5-2. Exerciser display and push buttons
Changing or Checking Time Programs
By operating the Prog. butto n, the individual commands
as programmed can, at any time, be brought consecutively
into the display for revision or checking. Revisions are
accomplished by programming over the existing programs
using the steps at the left.
Canceling Time Programs
After the selecting the desired program, use the h and
m buttons to set hours and minutes to zero; the ––:–– will
be displayed. This program has been made ineffective
and will no longer be carried out. To cancel all programs,
press the Res. (reset) button. This clears all memory
including the time base and program storage.
Manual Override
Do not manually override the exerciser unless you
are sure that the controller has been set for
exercisewithoutload(seepage5–2).Failuretodo
so could result in possible injury if the transfer
switch operates whil e the enclosur e door is open.
StepPress ButtonDisplayMeaning
1hand¬ handon
2hand[ ¬ ]permanent on
3hand[ f ]permanent off
4hand¬ fback to automatic
Daylight Savings / Standard Time Change
To change to Daylight Savings time (Summertime), press the
¦1h button once. Clock advances by one hour and +1h
appears in display.
To change to Standard Time (Greenwich mean time in UK,
Middle European time in Germany), press the ¦1h button
again; the clock sets back one hour and +1h disappears.
±1h
button
hour
button
minute
button
day
button
5-- 3
Page 16
CONTROL FEATURES (continued)
INPHASE MONITOR
FOR MOTOR LOAD TRANSFER
Inphase monitoring logic controls transfer and retransfer
of motor loads, so that inrush currents do not exceed
normal starting currents. It avoids nuisance tripping of
circuit breakers and mechanical damage to motor
couplings.
The Motor Load Transfer feature is built into the
controller.DIP switch S1 (actuator 5) activates this
feature: right = ON, left = OFF.
FUNCTIONS1 DIP SWITCH
enableActuator 5 on
disableActuator 5 off
Shaded DIP switches are standard factory settings.
Note
If the Motor Load Transfer feature is enabled,
it will be activated following
the Load
Disconnect Feature Delay Before Transfer
delay.
5
5
LOAD DISCONNECT FEATURE
Connect external circuits to the terminals indicated on
the Wiring Diagram provided with the ATSE.
The double throw (Form C) contact is rated for 28 VDC
or 120 VAC (5 amps resistive). The contact operates prior
to a selectable 0, 3, 10, or 20 second delay before transfer
of the automatic transfer switching device. The contact
resets either immediately following transfer or after the
same
delay as set for pre–signal before transfer.
Time delay between the load disconnect control signal
and initiation of transfer i s set on the controller with DIP
switch S2 (actuators 6, 7, 8) as shown below:
Delay Before Transfer
LD TDBTS2 DIP SWITCH
0 (disable)
3seconds
10 seconds
20 seconds
Actuator 7 on
Actuator 8 on
Actuator 7 on
Actuator 8 off
Actuator 7 off
Actuator 8 on
Actuator 7 off
Actuator 8 off
87
87
87
87
Shaded DIP switches are standard factory settings.
Delay After Transfer*
LD TDATS2 DIP SWITCH
enableActuator 6 on
disableActuator 6 off
6
6
*Enabling the Delay After Transfer wi ll cause the control
signal to reset after the same delay
as set for the Delay
Before Transfer.
REMOTE CONTROL FEATURES
These remote control features require a customer–supplied normally closed contact suitable for a 5 V dc low energy
circuit. Refer to the Wiring Diagram provided with the ATS. Activate appropriate DIP switch S2 actuators below.
Remote Test (terminals CP6–7)
RTSWS2 DIP SWITCH
disableActuator 3 on
enableActuator 3 off
3
3
Remote Transfer to Emergenc y (CP8–9)
RT /ES2 DIP SWITCH
disableActuator 2 on
enableActuator 2 off
2
2
Bypass Transfer Time Delay (CP12–13)
TD E/N BYP.S2 DIP SWITCH
disableActuator 1 on
enableActuator 1 off
1
1
Inhibit Transfer to Emergency (CP10–11)
N/E INHIB.S2 DIP SWITCH
disableActuator 4 on
enableActuator 4 off
5-- 4
4
4
Page 17
Page 18
INDEX
A
accessories, 5–2, 5–3, 5–4
auxiliary circuits, 1–3
B
barriers, 1–2
battery, 4–2, 5–1
buttons, push, 3–1
bypass time delay, 1–5, 2–1, 3–1
C
catalog number, inside cover
cleaning, 3–1
conductors
preparation, 1–2
terminals, 1–2
connections
engine control contact, 1–2
power, 1–2
control features, 5–1
load disconnect, 5–4
motor load transfer, 5–4
plant exerciser, 5–1
adjustment, 4–1
gen–set cooldown, 4–1
how to change, 4–2
override momentary outages, 4–1
settings, 4–1
transfer to emergency, 4–1
transfer to normal, 4–1
timer (plant exerciser), how to set,
5–1
transfer switch test, 1–5, 3–1
trouble–shooting, 3–2
inphase monitor, 5–4
V
voltage, phase, 4–1
voltage, pickup and dropout set-
tings, 4–1
Printed in U.S.A.
E 2011 ASCO Power Technologies, L.P.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.