Emerson 381333234 E User Manual

Operator’s
Automatic Transfer Switching Equipment
Manual
D–desi gn 30 through 230 ampere s
WARNING is used in this manual to warn of a hazardous situation which, if not avoided, could result in death or serious injury.
Series 200
Note: Refer to the outli n e and wiring drawings provided with your Series 200 ATSE for all installation and connection details and accessories.
Nameplate / rating Label
The Series 200 A utomatic Transfer Switching Equipment (ATSE) contains a nameplate / rating label which includes data for that specific ATSE. It defines the loads and fault circuit withstand/closing ratings. Refer to the labels on the Trans fer Switc h in g devic e for specific values and use the ATSE only within their limits.
CAUTION is used in this manual to warn of a hazardous situation which, if not avoided, could result in minor or moderate injury.
An experienced licensed electrician should install the ATS E .
Do not exceed the values on the rating label. Exceeding the rating can cause person injury or serious equipment damage.
TABLE OF CONTENTS
section
INSTALLATION 1.........................
SEQUENCE OF OPERATION 2............
TESTING & SERVICE 3...................
ADJUSTMENTS 4........................
CONTROL FEATURES 5..................
INDEX back of manual....................
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
381333–234 E
A typical Catalog Number is shown below with its elements explained:
Catalog Number Identification
Typical D–design Series 200 ATS catalog no. for a solid neutral, 3 pole, 100 amp, 400 V, open type:
design prefix letter
D
Neutral
A –solid
B – switching
200
Phase Poles
2 –singleØ 3 –threeØ
C – overlapping
blank – none
* 200 & 230 A are limited to 480 volts
A 3 100 J 5X
Amperes Voltage Controller
30 70
100
150 200 * 230 *
C 208
D 220 E 230
F 240 G 277
H 380
J 400
K 415
L 440
M 460 N 480
5 –standard 5X –if
accessories
ordered
SECTION 1 INSTALLATION
The ASCO Series 200 automatic transfer switching equipment (A TSE) consists of a transfer switching device, monitoring and transfer control device (controller), and membrane controls (for door mounting). The ATSE is factory tested. Installation requires mounting the devices into an appropriate size enclosur e and connection of power conductors, engine start signal wires, and auxiliary circuits.
Mounting
The Outline and Mounting Diagram furnished with the ATSE show s all mounting details and instructions.
NOTICE
Protect the automatic transfer switching equipment from construction grit and metal chips to prevent malfunction or shortened life of the transfer switching device.
Mount the transfer switch vertically in the back of the enclosure as shown on the Outline and Mounting Diagram provided. Level all mounting points of t he rigid supporting structure by using flat washers behind the holes to avoid forced distortion of the transfer switch.
Mount the membrane controls and the controller on the inside of the enclosure door as shown on the Outline and Mounting Diagram provided. The membrane controls must be accessible through a cutout in the door. Connect the membrane controls to the right side of the controller with the ribbon cable provided. Then connect the transfer switching device harness plugs to the left side of the controller. See Figures 1–1 and 1–2.
membrane controls
ribbon cable
controller
enclosure
door
controller must be within a steel enclosure
Figure 1-1. Membrane controls and controller mount-
ing on inside of enclosure door. Refer to
Outline & Mounting Diagram for mounting hardware.
gasket
cut out in enclosure
door
An add-on rail is provided for some optional accesso­ries. If provided, mounted it below the controller. Then make the connections shown on the Wiring Diagram.
Grounding
Grounding (earthing) is accomplished by mounting the automatic transfer switching equipment in a metal enclosure. Connect the control panel grounding wire (lower left side) to equipment (enclosure or clean earth) ground. This wire can be connected to the controller’s lower left mounting stud. Because the controller is mounted on a door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges. See Figure 1–3.
Figure 1-2. Membrane controls with gasket
suitable for IP65 enclosure.
2 plugs for transfer switching device harness
ground wire
mounting stud
Figure 1-3. Controller grounding (clean earth)
wire and other connections.
ribbon cable to membrane controls
connections for control features &
options
NOTICE
The controller must be grounded for proper operation.
1-- 1
INSTALLATION (continued)
NOTICE
De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine generator starting control in the OFF position. Make sure engine generator is not in operation.
Power connections
A Wiring Diagram is furnished with the Series 200 ATSE. All wiring must be made in accordance with the local codes.
Do not run cables in front of the transfer switching device. Conductors can be bundled on the right side of the transfer switching device. Maintain proper electrical clearance between the live metal parts and grounded metal: 13 mm minimum.
It is not necessary to remove the barriers from the transfer switching device to install the conductors. If you do remove them, however, be sure to reinstall the barriers carefully.
Connect main source and load conductors to clearly marked power terminals on the transfer switching device. Be careful when stripping insulation from the conductors; avoid nicking or ringing the conductor. Remove surface oxides from conductors by cleaning with a wire brush. Follow conductor manufacturer’s instructions when aluminum conductor is used. Apply joint compound to conductor, then carefully wipe away excess compound. Tighten the terminals to the torque specified on the label on the transfer switching device.
Three conductor spacers must be located as shown for 150, 200, and 230 ampere transfer switching devices.
conductor spacers
38 mm approximate
conductor spacer
Figure 1-4. Required conductor spacers for
150, 200, & 230 amp transfer switching devices.
Engine Starting Contacts
The engine control contact connections (if used) are located on the transfer switching device. Connect signal wires to appropriate terminals as specified in Table A and shown in Figure 1–5.
Table A. Engine start connections
When normal
source fails
contact closes TB1 and TB2
contact opens TB1 and TB3
Te r m i na l s o n
transfer switching device
Three conductor spacers are included with 150, 200, and 230 ampere transfer switching devices. When installing power conductors, run them through the conductor spacers as shown in Figure 1–4. Position the spacers within 38 mm o f the power terminals.
ENGINE STARTING CONTACTS
( SHOWN DE–ENERGIZED )
TOP
STUD
MIDDLE
STUD
BOTTOM
STUD
1
TS
2
NR
3
NR
TB 1
TB 3
TB 2
Figure 1-5. Engine starting contact label and
location on left side of transfer switching device.
Interconnecting harness
Connect the plug–in harness (two plugs) from the transfer switching device to left side of the controller, if not already connected.
Auxiliary Circuits
Connect auxiliary circuit wires (if necessary) to appropriate terminals by referring to the Wiring Diagram.
1-- 2
Functional Test
INSTALLATION (continued)
The Functional Test consists of three checks: manual operation, voltage checks, and electrical operation.
NOTICE
Do these checks in the order presented to avoid damaging the automatic transfer switching equipment.
Read all instructions on the Wiring Diagrams and labels affixed to the ATS. Note the control features that are provided and review their operation before proceeding .
1 – Manual Operation
A detachable manual operator handle is provided on the Transfer Switching device for maintenance purposes only. Manual operation of the transfer switching device must be checked before it is operated electrically.
Do not manually operate the transfer switching device until both power sources are disconnected: open both circuit breakers.
Position of the transfer switch is indicated here
weight marked N (normal) and E (emergency)
maintenance handle
weight
floating weight
With ALL POWER OFF grasp
maintenance handle and turn it
quickly with your thumb and fingers.
1. After deenergizing both power sources, open the enclosure door. Locateandthemaintenance handle on the left side of the transfer switching device. See Figure 1–6.
2. Grasp the attached maintenance handle and turn it with thumb and fingers as shown to manually operate it . The maintenance handle turns the opposite direction of the weight. Turn it up o r down as shown to manually operate the transfer switching device. It should o perate smoothly wit hout any binding. If it does not, check for shipping damage or construction debris.
3. Return the transfer switching device to the N (normal) position.
Now continue to 2–VoltageCheckson next page.
Figure 1-6. Maintenance handle and positions.
1-- 3
INSTALLATION (continued)
Figure 1–7. Standard controls and indicators.
observe these lights
2–VoltageChecks
First check nameplate on transfer switching device; rated voltage must be the same as normal and emergency line voltages.
Use extreme caution when using a meter to measure voltages in the following steps. Do not touch power terminals; shock, burns, or death could result !
Perform steps 1 through 6 at the right. Observe the status lights. See Figure 1–7.
O Black circle means light is on.
P White circle means light is off.
* If necessary, adjust voltage regulator on the generator according to the manufacturer’s recommendations. The Automatic Transfer S witching Equipment will respond only to the rated voltage specified on the Transfer Switching device nameplate.
Also see page 4–1 for the HI–LOW voltage adjust setting in the controller. The LOW setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V.
Close the normal source circuit breaker. The Normal T ransfer Switch Position and the Normal
1
Source Accepted lights should come on.
Use an accurate voltmeter to check phase to phase and phase to neutral voltages pres-
2
entatthetransferswitchingde­vice normal source terminals.
Close the emergency source circuit breaker. (Start generator, if necessary.) The Emergency
3
Source Accepted light should come on.
Use an accurate voltmeter to check phase to phase and phase to neutral voltages pres-
4
entatthetransferswitchingde­vice emergency source termi­nals.*
Useaphaserotationmeterto check phase rotation of emer-
5
gency source; it must be the same
as the normal source.
Source Accepted
Normal
Emergency
Source Accepted
Normal
Emergency
W
V
U
1-- 4
Shut down the engine–genera­tor , if applicable. The Emergen- cy Source Accepted light should go off. Then put the starting
6
control selector switch (on the
Source Accepted
Normal
Emergency
generator set) in the automatic position. Close enclosure door.
Now continue to 3 – Electrical Operation on next page.
Loading...
+ 12 hidden pages