Emerson 3750-6250 KVA LCV Container Brochures and Data Sheets

Avtron LCV
Resistive/Reactive Load Bank - 3125 to 6250 KVA
Testing Your Emergency Standby Generator with a Load Bank Means Reliability When it Matters Most.
Key Features
• Highest Capacity in the Industry
• Provides Resistive and Reactive Loading
• PLC Based Load Control
• Local and Remote Load Control
• Easy Interconnection and Operation
Superior Avtron quality combined with simple operation and maintenance will provide years of trouble free service.
Avtron’s extensive line of Load Bank and Industrial Resis tor Products are solid performers used throughout the world.
The Avtron Model LCV Load Bank is used for high power resistive/reactive testing of AC generating systems.
The Avtron LCV load bank is designed to provide high capacity resistive and reactive loading of AC power systems such as diesel generator sets, turbines, or Uninterruptible Power Supplies (UPS). Many specifications and local codes demand that such testing be performed at less than unity power factor, typically 0.8 p.f. lagging. The LCV load bank is ideal for high power resistive and reactive testing of AC generating systems in factory production lines or in the field after installation.
The LCV load bank combines resistive load (KW) with reactive load (KVAR) to achieve a 0.8 p.f. This combination provides a true test of the actual generator or UPS nameplate rating (KVA) and simulates a “real-world” load.
The LCV incorporates state-of-the-art load bank design features with the highest capacity in the industry (20' [6096] container). The resistor elements, iron-core reactors, blowers, and controls are all manufactured from the highest quality components available.
For total technical support or additional information, please contact Avtron at (216) 573-7600 or LBsales@Emerson.com.
Quality System Certified to ISO 9001
LCV 3750 KVA Resistive/ Reactive Avtron Load Bank.
Avtron LCV
LOAD CONNECTION COMPARTMENT
ABC
Resistive/Reactive Load Bank - 3125 to 6250 KVA
Specications subject to change without notice.
Construction
The load bank consists of a rugged ISO style container housing the resistive and reactive components, blowers, associated controls, and interconnections. The container features air intakes on the sides of the container with vertical exhaust through the roof.
Resistor Elements
The resistive elements are manufactured of a corrosion resistant chromium alloy wire and are fully supported with stainless steel rods for long life.
Reactive Elements
The reactive elements are of non-saturating single and 3 phase iron-core construction impregnated with high dielectric varnish.
Control Power
120 VAC, single phase, 60 Hz provided by an integral control transformer.
Metering
Digital metering with data logging is provided to measure voltage, current, frequency, KW, KVAR, and power factor.
Cooling
The resistive elements are cooled by inte­grally mounted blower motors each rated 10 HP, 460 VAC, 3 phase, 60 Hz.
Controls
The LCV load bank features both local and remote load control. The remote hand held controller is rugged and compact (7"x 7"x 2"). The controller is easy to operate and load values are activated by pressing a membrane style keypad. All resistive and reactive func­tions are displayed on a LCD display. A hard wired E-stop push button is also provided. The remote controller communicates with the Load Bank PLC via 200' of control cable in (2) 100' increments with MS style connectors.
Protection
This load bank features branch circuit fusing on all load steps and overtemperature protec­tion. Air switches on the blowers are electri­cally interlocked to remove load if the airflow is not sufficient to provide proper cooling.
Emerson Network Power
Avtron 6255 Halle Drive, Cleveland, Ohio 44125, U.S.A.
216-573-7600 • FAX: 216-573-5953 • LBsales@Emerson.com
EmersonNetworkPower.com/loadbank
Typical Capacity Ratings
Available Load Step Resolution: 25KW, 18.75 KVAR
Total Load
KVA at
0.8 p.f.
NOTE Standard voltage is 480 VAC, 3 phase, 60 Hz. Other
voltages and frequencies are available. Consult factory.
Resistive Load KW
3125 2500 1875
3750 3000 2250
5000 4000 3000
6250 5000 3750
Reactive
Load KVAR
Load Bank Weight (approx.)
3125 or 3750 KVA: 28,600 lbs. [13,000 kg] 5000 KVA: 32,700 lbs. [14,800 kg] 6250 KVA: 36,300 lbs. [16,500 kg]
Options
• SIGMA™ Network Control
• Heavy Duty Dual Axle Trailer
COMPARTMENT
BOLTED & HINGED ENTRY DOOR FOR SERVICE/ACCESS
VERTICAL EXHAUST AIR VERTICAL EXHAUST AIR
Emerson. Consider it Solved and Emerson Network Power are trademarks of Emerson Electric Co.
or one of its afliated companies. All the other marks are the property of their respective owners.
Communicator EXT™ is a trademark of Electro Industries/GaugeTech. ADMS™ is a trademark of Avtron. SIGMA™ is a trademark of NJ Froment & Co. Ltd. Specications subject to change without notice.
©2015 Emerson Network Power Bulletin 432• Rev. D
238.50 [6058.00]
• Cable Reels
CONTROL
96.00 [2438.00]
17.00 MAX [432.00]
102.00
[2591.00]
EXHAUST HATCHES
(MAY BE REMOVED FOR SHIPPING)
BOLT-ON ACCESS PANELS
EXTERNAL BLOWER CONTROL POWER CONNECTION BOX
AIR INTAKE
(TYPICAL)
FORKLIFT POCKETS
All dimensions are in inches [millimeters].
Loading...