Emerson 1000VA, 1500VA User Manual

Liebert® PSA
Quick-Start Guide - 1000VA/1500VA, 120V

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and maintenance of the UPS.
• Intended for installation in a controlled environment.
• Maximum ambient temperature 104°F (40°C).
CAUTION
!
To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in accordance with the national code, ANSI/NFPA 70.
• Do not connect equipment that may overload the UPS or demand half-wave rectification, such as a laser printer.

SETUP

Step 1 Inspect the Package

Inspect the package and the UPS upon receipt. Notify the carrier and dealer of visible damage.
Liebert
shutdown
software
CD
UPS

Step 2 Decide Where to Place the UPS

Quick-start
guide
USB
cable
• Connect the UPS only to an earthed / grounded outlet that meets national and local electrical safety guidelines.
• Locate the UPS near a wall outlet. Do not use an extension cord between the UPS and the outlet.
• The Liebert PSA has been designed for small office/home office use only; it is NOT recommended for use in life-support applications.
• In the event of an emergency, press the OFF button and disconnect the power cord from the AC power supply to properly disable the UPS.
• Do not attach power strips or surge suppressors to the UPS.
• Do not attempt to service any parts inside the UPS except the batteries. Failure to adhere to this could cause personal injury or equipment malfunction and void the warranty.
• For technical support:
• Visit www.liebert.com or
• Send an e-mail to upstech@emersonnetworkpower.com.

Step 5 Check the Site Wiring Fault Indicator

USB
SITE WIRING
See figure at right for the location of the Site Wiring Indicator on the rear of the UPS.
FAULT
IN OUT
• Check the rear of the UPS to make sure the Site Wiring Fault indicator is NOT illuminated.
Caution: If the Site Wiring Fault indicator is illuminated, have a qualified
Battery Power Supply
Full Time Surge Protection
AC OUTPUT
AC INPUT BREAKER
AC INPUT
electrician check the wall receptacle wiring and fix any problems.

Step 6 Connect the Loads

The UPS has three battery backup outlets that provide power when the UPS operates on battery (see Figure 2 below).
• Plug the loads into the battery backup outlets on the rear of the UPS.
Caution: Do not connect a laser printer to the UPS.
USB
SITE WIRING
FAULT
IN OUT
Battery Power Supply
Full Time Surge Protection
AC OUTPUT
AC INPUT BREAKER
AC INPUT
The UPS must be placed indoors, protected from water, direct sunlight and excessive heat.
Provide at least 4" (100mm) of clearance on all sides of the unit for proper ventilation.
Step 3 Charge the UPS Battery Before
Use
The UPS battery is not charged before shipping. It MUST be charged before use.
• Connect the UPS power cord to a wall outlet and charge for at least eight hours.
Note: If battery is placed in storage, charge the battery every six months if kept at 5°F to 85°F (-15°C to 29°C)—or every three months if kept at 86°F (30°C) or higher.

Step 4 Start the UPS

After the battery is fully charged:
• Turn on the UPS by pressing the On/Off button (see Figure 1 below).
LED 1 should be illuminated (green), indicating the UPS is operating in Normal Mode.

UPS CONTROLS AND CONNECTIONS

Step 7 Connect the Network Surge Protection

The UPS has two RJ-45 jacks for network lines (see Figure 2 below).
• Connect a single-line network cable into the RJ-45 network surge protection IN jack on the rear of the UPS.
• Connect an RJ-45 cable from the OUT jack on the rear of the UPS to a port on a PC or network device such as a router.
SITE WIRING
USB
RS232
FAULT
IN OUT
Battery Power Supply
Full Time Surge Protection
AC INPUT
AC OUTPUT
BREAKER
AC INPUT

Step 8 Set Up Liebert shutdown software

To start using the Liebert shutdown software:
• Install the Liebert shutdown software. See the software user manual for installation instructions.
• Connect one end of the USB cable (supplied) to the USB port on the rear of the UPS. Connect the other end to a USB port on the computer. See the software user manual for operating instructions.
SITE WIRING
USB
FAULT
IN OUT
Battery Power Supply
Full Time Surge Protection
AC INPUT
AC OUTPUT
BREAKER
AC INPUT
Utility
symbol
Battery symbol
Figure 2 - Rear PanelFigure 1 - Front Panel LEDs
LED 1
(green)
EMERSON
LED 2
(amber)
Network Power
On/Off button
LED 3
(amber)
Liebert
AC Power System
LED 4
(red)
!
PSA
®
Fault symbol
Overload symbol
USB
interface
Battery backup
outlets (6)
NEMA 5-15R
Input
breaker
NEMA
5-15P
AC INPUT BREAKER
AC INPUT
Battery Power Supply
USB
AC OUTPUT
SITE WIRING
FAULT
IN OUT
Full Time Surge Protection
Site Wiring Fault indicator
RJ-45 jacks (2) ­network protection
Surge outlets (2) NEMA 5-15R
UPS Status, Alarm Conditions and Alerts
Condition LED Color Solid/Flashing Audible Alarm
Normal Mode LED 1 Green Solid (steady glow) (None)
Battery Mode LED 2 Amber Flashes every 3 seconds Every 3 seconds
Battery Low LED 2 Amber Flashes every 1 second till end of discharge (EOD) Every 1 second
Overload LED 3 Amber Solid (steady glow) until load drops or breaker trips Continuous
Battery Replacement LED 4 Red Flashes every 1 second for 5 seconds only Every 1 second for 5 seconds only
Fault LED 4 Red Solid (steady glow) until UPS shuts down after 5 seconds Continuous until UPS shuts down

REPLACING THE BATTERY

To replace the battery:
1. Turn off all connected loads, then turn off the UPS (batteries are NOT hot-swappable).
2. Use a Phillips head screwdriver to remove the two top cover screws from the back of the UPS.
3. Slide the top panel backward 1/2" (13mm). Slide the front panel upward, then pull outward to remove it.
4. Gently pull the batteries out of the UPS.
5. Remove the black wire from the negative (-) terminal and the red wire from the positive (+) terminal.
6. Verify that the replacement battery matches the dimensions and battery type in the Specifications section below.
7. Connect the battery leads to the new batteries. Be sure to reconnect the red wire to the positive (+) terminal and the black wire to the negative (-) terminal.
Note: Small sparks may occur at the battery connectors during reconnection.
8. Slide the batteries into the UPS.
9. Reposition the front panel and slide downward until it slides into place. Slide the top panel forward until flush with the front panel. Reinsert the two top cover screws removed in Step 2.
Dispose of the old batteries properly at an appropriate recycling facility.
Steps 2 and 3
Steps 4 and 5
-

TROUBLESHOOTING

If the UPS malfunctions during operation, check the following chart for proper adjustment. For further assistance, please contact your local Emerson Network Power representative.
Problem Possible Causes Solutions
The UPS may not be turned on.
Utility power is normal, but LED 1 is not illuminated.
LED 2 flashes (amber) every 3 seconds, but there is no output power.
Alarm buzzer beeps continuously although utility power is normal.
UPS does not provide expected backup time. The UPS battery reached end of life. • Replace the internal battery.
The UPS is on and connected to input power, but fails to operate properly.
The power cord may not be connected properly.
The upstream input circuit breaker may be tripped.
Battery voltage may be too low. • Recharge the UPS for 8 hours.
The UPS may be overloaded (check LED 2). • Disconnect some equipment from the UPS.
Utility power may be outside the unit’s operating range.
• Press the On/Off button to turn on the UPS.
• Connect the power cord securely into a wall outlet.
• Reset the input circuit breaker.
• If utility power is normal, try reconnecting input power and restarting the UPS.

SPECIFICATIONS

Model Number PSA1000MT3-120U PSA1500MT3-120U
Capacity (VA/W) 1000/600 1500/900
Net Weight, lb. (kg) 23.8 (10.8) 27.8 (12.6)
Shipping Weight, lb. (kg) 26.0 (11.8) 30.0 (13.6)
Dimensions - W x D x H, in. (mm) 5.8 x 14.2 x 9.2 (147 x 360 x 234)
On-Line Input Voltage 84-140VAC
On-Line Frequency 50/60Hz ±5Hz
Output Voltage (Mains Normal) Typical 97-129VAC
Output Voltage (Battery Operation) 120VAC ±5%
On-Battery Wave Form Stepped sinewave
Battery Type - VDC x Ah x Quantity 12V x 7Ah x 2 12V x 9Ah x 2
Typical Recharge Time 6-8 hours to 90%
Battery Run Time* - Full Load 6 minutes
Battery Run Time* - Half Load 12-13 minutes
Audible and Visual Audible alarm / LED
Backup Outlets NEMA 5-15R (6)
Surge Outlets NEMA 5-15R (2)
Operating Temperature, °F (°C) 32 to 104 (0 to 40)
Storage Temperature, °F (°C) 5 to 104 (-15 to 40)
Operating / Storage Relative Humidity 0%-90%, non-condensing
EMI Classification FCC Part 15 Class B
Agency
Safety UL 1778, c-UL Listed
Transportation ISTA Procedure 1A Certification
* Battery run time may vary depending on load
© 2008 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-23301_REV0_04-08
Technical Support / Service United States
800-222-5877 (Outside U.S. 614-841-6755) upstech@emersonnetworkpower.com Web site: www.liebert.com