EMC FC-610-001 Installation Manual

Page 1
©2015 EMS Security Group Ltd. All rights reserved Page 2 of 2 TSD050 Iss 12 09/02/2016 AJM
1 Pre Installation 2 Components
Part No Product Description
!
4x Lid Fixing Screws Front Lid
3
Back Box
FC-610-001 Wireless Dual Input/Output Unit
Wireless Input Output Unit Installation Guide
DUAL I/O UNIT
FC-610-001
FC-610-001
DUAL I/O UNIT
IDENT REV
DATE
FC-610-001
EN300 200-2
0359
!
20K
4K7
C
N/O
20K = Red/Bl 4k7 = Yellow
EOL Resistor Conguration
ANTENNA
2
1
3 Remove Cable Entry Points 4 Fix to the Wall
Use all four circled fixing positions to ensure a firm fixing.
Use suitable fasteners and fixings.
INPUT 1 INPUT 2
IP- IP+ IP- IP+
20k
4k7
C
N/O
Drill the cable entry points as necessary.
Cable glands should be used.
DO NOT leave excess cable in the device.
ON
INPUT 1
INPUT 2
EXPAN1
EXPAN2
OUTPUT 2
OUTPUT 1
IP- IP+ IP- IP+
3VDC
SET
RST
N/O
COM
N/C
3VDC
SET
RST
N/O
COM
N/C
Do Not Use
=
Available
Cable Entry
Points
=
Installation must conform to applicable local installation codes and
should only be installed by a fully trained
competent person.
Ensure that the device is installed as per the site survey.
The use of a non-metallic spacer should be considered if mounting the device on to a metal surface.
Do NOT Press the Log On button on a pre-programmed device, as this will cause communication with the Control Panel to be lost. Should this happen, delete the device from the system and add it back on.
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE
1
2
3
ANTENNA
KEEP CABLES AWAY FROM THIS AREA
LOGON
OUTPUT 2OUTPUT 1
3VDC
SET RST
INPUT 1 INPUT 2
LED
ENABLE
POWER
INPUT
INPUT
FAULT
CLOSED
0 1
1
64 F-SAFE
N/O COM
N/C
IP- IP+ IP- IP+
3VDC
SET RST
N/O COM
N/C
EXPAN1
EXPAN2
RELAY ON
RELAY ON
2 4 8 16 32
ON
1 2 3 4 5 6 7 8
012ABC
Fixing position location within cavity
6 Output Wiring
Two resistor monitored inputs are available.
Both inputs monitor; closed (alarm), open and short circuit conditions.
Each input is factory fitted with an
end of line 20kΩ resistor.
To connect inputs to external devices, wire as shown below. I.e. Input 1, using the resistor pack provided.
If an input is not being used, leave
the 20kΩ resistor as factory fitted.
EOL
Resistor
Setup
Remote Monitored Device
Note: Max
Cable Length
of 10m
OUTPUT 2OUTPUT 1
N/O COM N/C N/O COM N/C
Two outputs are also available.
Both outputs are voltage free and rated 2A @ 24Vdc.
WARNING. DO NOT CONNECT TO MAINS.
!
Page 2
Page 2 of 2
7 Power Device
When fitting / replacing batteries; observe correct polarity, using only specified batteries.
Connect the power jumper across the PIN header.
8 Configuration
Once powered, reassemble the device.
The device’s loop address is configured within the menu structure of the Radio Hub.
Refer to the programming manual (Doc Ref: MK98) for full programming information.
Free to download from
www.emsgroup.co.uk
OUTPUT 2OUTPUT 1
3VDC
SET RST
INPUT 1 INPUT 2
LED
ENABLE
PO WER
INPUT 1
INPUT 2
FAULT
CLOSED
0 1
1
64 F-SAFE
N/O COM N/C
IP- IP+ IP- IP+
3VDC SET RST N/O COM N/C
EXPAN1
EXPAN2
RELAY ON
RELAY ON
2 4 8 16
32
device
unpowered
(pins unlinked)
device
powered
(both pins linked)
9 LED Operation
The device has six indication LEDs. Pressing the LED enable button enables their illumination for 10 minutes before automatically timing out.
2x Input Fault: YELLOW LED ON = FAULT
2x Input Closed: RED LED ON = ACTIVE
2x Output: RED LED ON = ACTIVE
CLOSED
FAU LT
INPUT 1
INPUT 2
Input 2 LEDs
Input 1 LEDs
Output 1 LED
Output 2 LED
Operating Temperature -10°C to 55°C
Storage Temperature 5°C to 30°C
Humidity Up to 95% non-condensing
Supply 6x AA Alkaline (Panasonic LR6AD Powerline / Varta
4006 Industrial)
CAUTION! Fitting of an incorrect battery type invalidates the product certification and may result in poor performance.
Output rating 2A @ 24Vdc
IP Rating IP65
Operating Frequency 868MHz
Output Transmitter Power Auto adjusting 0 - 14 dBm (0 - 25 mW)
Dimensions 270mm (W) 205mm (H) 75mm (D)
Weight 0.95kg
Location Type A: For indoor use
2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For recycling, return this product to your local supplier upon purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see www.recyclethis.info Dispose of your batteries in an environmentally friendly manner according to your local regulations.
European Union directives
EMS Security Group Ltd hereby declares that this device is in compliance with the essential requirements and other relevant provisions of Directive 2014/53/EU (R&TTE directive).
Approved to
EN54-18:2005. Fire detection and fire alarm systems. Part 18: Input/output devices.
EN54-25:2008. Incorporating corrigenda September 2010 and March 2012. Fire detection and fire alarm systems. Part 25: Components using radio links.
Certification
Certification body
CPR Certificate DOP 0359-CPR-0039
EMS Security Group Ltd. Technology House, Herne Bay, Kent, CT6 8JZ, United Kingdom
Manufacturer
Year of manufacture See devices serial number label
0359
10
Specification Regulatory Information
Loading...