In order to achieve the optimum, safe operation of the Dragonfly and Butterfly servoamplifiers, it is imperative that you implement the safety procedures included in this
installation guide. This information is provided to protect you and to keep your work
area safe when operating the Dragonfly and Butterfly and accompanying equipment.
Please read this chapter carefully before you begin the installation process.
Before you start, ensure that all system components are connected to earth ground.
Electrical safety is provided through a low-resistance earth connection.
Only qualified personnel may install, adjust, maintain and repair the servo drive. A
“qualified person” has the knowledge and authorization to perform tasks such as
transporting, assembling, installing, commissioning and operating motors.
The Dragonfly and Butterfly servo drive contain electrostatic-sensitive components that
can be damaged if handled incorrectly. To prevent any electrostatic damage, avoid
contact with highly insulating materials, such as plastic film and synthetic fabrics. Place
the product on a conductive surface and ground yourself in order to discharge any
possible static electricity build-up.
To avoid any potential hazards that may cause severe personal injury or damage to the
product during operation, keep all covers and cabinet doors shut.
The following safety symbols are used in this manual:
Warning:
This information is needed to avoid a safety hazard, which might cause
bodily injury.
Caution:
This information is necessary for preventing damage to the product or
to other equipment.
Note:
This is auxiliary information that ensures the correct operation of the
equipment.
Dragonfly/B utterfly Installation Guide Safety Information
MAN-DRBUIG (Ver. 1.1)
1.1 Warnings
Cleaning after soldering
To avoid the damage of the product's acrylic coating the
Dragonfly/Butterfly must not be cleaned after soldering by dissolving
solvents and /or "water" cleaning process. For more details:
http://www.elmomc.com/applicat ions/ar ti cl e/Sol der ing-and Cleaning_Application-Note.pdf
To avoid electric arcing and hazards to personnel and electrical contacts,
never connect/disconnect the servo drive while the power source is on.
Power cables can carry a high voltage, even when the motor is not in
motion. Disconnect the Dragonfly and Butterfly from all voltage sources
before they are opened for servicing.
1-2
The Dragonfly and Butterfly servo drive cont ain ground ing condui ts for
electric current protection. Any disruption to these conduits may cause
the instrument to become hot (live) and dangerous.
After shutting off the power and removing the power source from your
equipment, wait at least 1 minute before touching or disconnecting parts
of the equipment that are normally loaded with electrical charges (such as
capacitors or contacts). Measuring the electrical contact points with a
meter, before touching the equipment, is recommended.
1.2 Cautions
The Dragonfly and Butterfly servo drives contain hot surfaces and
electrically-charged components during operation.
The maximum DC power supply connected to the instrument must
comply with the parameters outlined in this guide.
When connecting the Dragonfly and Butterfly to an approved 12 ~ 95
VDC auxiliary power supply, connect them through a line that is
separated from hazardous live voltages using reinforced or double
insulation in accordance with approved safety standards.
Before switching on the Dragonfly and Butterfly, verify that all safety
precautions have been observed and that the installation procedures in
this manual have been followed.
Dragonfly/B utterfly Installation Guide Safety Information
MAN-DRBUIG (Ver. 1.1)
1.3 Directives and Standards
The Dragonfly and Butterfly conform to the following industry safety standards:
Safety Standard Item
1-3
In compliance with MIL-STD-704
In compliance with MIL-STD-810
Aircraft, Electric Power Characteristics
Environmental Engineering Considerations and
Laboratory Tests
In compliance with MIL-STD-1275
Characteristics of 28 Volt DC Electrical Systems in
Military Vehicles
In compliance with MIL-STD-461
Requirements for the Control of Electromagnetic
Interference Characteristics of Subsystems and
Equipment
In compliance with MIL-HDBK-217
In compliance with ISO-9001:2000
Reliability Prediction of Electronic Equipment
Quality Management
In compliance with UL508cPower Conversion Equipment
In compliance with UL840
Insulation Coordination, Including Clearance and
Creepage Distances of Electrical Equipment
In compliance with UL60950-1
(formerly UL1950)
Safety of Information Technology Equipment,
Including Electrical Business Equipment
In compliance with EN60204-1Low Voltage Directive, 73/23/EEC
The Dragonfly and Butterfly servo drives have been developed, produced, tested and
documented in accordance with the relevant standards. Elmo Motion Control is not
responsible for any deviation from the configuration and installation described in this
documentation. Furthermore, Elmo is not r esponsib le for t he perform ance of new
measurements or ensuring that regulatory requirements are met.
1.4 CE Mark Conformance
The Dragonfly and Butterfly servo drives are intended for incorporation in a machine or
end product. The actual end product must comply with all safety aspects of the relevant
requirements of the European Safety of Machinery Directive 98/37/EC as amended, and
with those of the most recent versions of standards EN60204-1 and EN292-2 at the least.
According to Annex III of Article 13 of Council Directive 93/68/EEC, amending Council
Directive 73/23/EEC concerning electrical equipment desi gned for use wit hin certai n
voltage limits, the Butterfly and Dragonfly meet the provisions outlined in Council
Directive 73/23/EEC. The party responsible for ensuring that the equipment meets t he
limits required by EMC regulations is the manufacturer of the end product.
Dragonfly/B utterfly Installation Guide Safety Information
MAN-DRBUIG (Ver. 1.1)
1.5 Warranty Information
The products covered in this manual are warranted to be free of defects in material and
workmanship and conform to the specifications stated either within this document or in
the product catalog description. All Elmo drives are warranted for a period of 12 months
from the time of installation, or 18 months from time of shipment, whichever comes first.
No other warranties, expressed or implied — and including a warranty of
merchantability and fitness for a particular purpose — extend beyond this warranty.
1-4
Cymbal Installat ion GuideIntroduction
MAN-CYMIG (Ver. 1.1)
Chapter 2: Introduction
This Installation Guide is intended for design engineers who are in tegrating Elmo Motion
Control Cymbal servo amplifiers into a machine.
2.1 Product Description
The Cymbal series of servo amplifiers is designed to operate in the current mode
controlling permanent-magnet trapezoidal brushless motor and DC brush motor.
The Cymbal exhibits “the highest density of power and intelligence” and can deliver up
to 11.3 kW of continuous power or 13.6 k W of peak power in a most compact and
efficient package.
The Cymbal operates from a DC power source in the range of 12 ~ 195 VDC.
2-1
The Power stage of the Cymbal is fully isolated from other sections of the Cymbal, such
as the control stage and the heatsink. This contributes very significantly to the safety and
the EMI immunity of the Cymbal. In addition it simplifies the requirements of the DC
power supply used to power the DC bus of the Cymbal and allows also the operation
with a non-isolated DC power source.
The Cymbal incorporates full custom mixed analog/digital ICs and a hybrid power
stage. The basic configuration is a current mode amplifier targeting the OEM market. As
such, no trimmers are used in the basic version. In addition to its compliance with
relevant MIL standards, the Cymbal amplifier also meets UL508c and the relevant CE
regulations.
The Cymbal power stage is implemented on ceramic substrates. This design enables very
high thermal conductivity, high current carrying capacity, improved EMC and good
mechanical strength. The control section is implemented by dedicated custom ICs that
contribute to enhanced performance and reliability.
2.2 Standard Features
• Operates in current mode
• Internal DC-to-DC converter, which allows for operation from a single supply
• Zero dead-band
• Excellent linearity
• One differential input
• Motor current monitor
• Current gain change for low inductance motors
• Remote current gain control
• Status indication and remote control functions by four open collector transistors
• External continuous and peak current-limit adjustments
• Package: plated-aluminum base plate, plastic housing, UL94V0 recognized
• Ultra-lightweight of 700 grams (24.7 oz)
Cymbal Installat ion GuideIntroduction
MAN-CYMIG (Ver. 1.1)
2.3 Fault Protection
Built-in protection against possible fault conditions, including:
• Shorts between the outputs or between each output and the power input/return
• Over-heating
• Under/over voltage
• Failure of internal power supplies
• Latch mode for each protective feature
2.4 How to Use this Guide
Installation is the first step in integrating and operating the Elmo Cymbal servo
amplifiers. After carefully reading the safety instructions in the first chapter, the
following chapters provide you with installation instructions as follows:
Chapter 3, Installation, provides step-by-step instructions for unpacking, mounting and
connecting the Cymbal.
2-2
Chapter 4, Servo Control Operation, explains how to control the operat ion of t he servo
amplifier.
The Appendix, Technical Specifications, lists all the drive ratings and specifications.
Dragonfly/ Bu tter fly Installation G uideInstallation
MAN-DRBUIG (Ver. 1.1)
Chapter 3: Installation
3.1 Before You Begin
3.1.1 Site Requirements
You can guarantee the safe operation of the Dragonfly and Butterfly by ensuring that they are
installed in an appropriate environment.
Feature Value
Ambient operating temperature -40 °C to +70 °C (-40 °F to 160 °F)
Maximum relative humidity 95% non-condensing
Operating area atmosphere No flammable gases or vapors permitted in area
Note: Models for extended environmental conditions are available.
3-1
The Dragonfly and Butterfly dissipate their heat by convection. The maximum
ambient operating temperature of –40 °C to +70 °C (-40 °F to 160 °F) must not
be exceeded.
3.2 Unpacking the Amplifier
To unpack the Dragonfly and Butterfly:
Carefully remove the servo amplifier from the box and the Styrofoam.
1. Check the amplifier to ensure that there is no visible damage to the instrument. If any
damage has occurred, report immediately to the carrier that delivered your amplifier.
2. To ensure that the Dragonfly or Butterfly you have unpacked is the appropriate type for
your requirements, find the part number sticker on the side of the product:
The P/N gives the type designation
as follows:
BUT- X/YYY
Continuous Current
Operating Voltage
(Amps)
Maximum DC
Dragonfly/ Bu tter fly Installation G uideInstallation
MAN-DRBUIG (Ver. 1.1)
3-2
DRA-
Continuous Cu rrent
(Amps)
Maximum DC
Operating Voltage
X/YY
3. Verify that the Dragonfly or Butterfly type is the one that you ordered, and ensure that
the voltage meets your specific requirements.
3.3 Dimensions
3.3.1 Butterfly Dimensions
Figure 3-1: Butterfly Dimensions
Dragonfly/ Bu tter fly Installation G uideInstallation
MAN-DRBUIG (Ver. 1.1)
3.3.2 Dragonfly Dimensions
3-3
Figure 3-2: Dragonfly Dimensions
3.4 Mounting
3.4.1 Butterfly
The Butterfly was designed for mounting on a printed circuit board (PCB). It is connected by
2mm pitch 0.51 mm square pins. When designing the Butterfly into a device, be sure to leave
about 1 cm (0.4") outward from the heatsink to enable free air convection around the Butterfly.
We recommend that the Butterfly be soldered directly to the board. Alternatively, the Butterfly
can be attached to socket connectors mounted on the PCB. If the PCB is enclosed in a metal
chassis, we recommend that the Butterfly be screw-mounted to it as well to help with heat
dissipation. The Butterfly has screw-mount holes on each corner of the heatsink for this
purpose.
3.4.2 Dragonfly
The Dragonfly was designed for mounting on a printed circuit board (PCB). It is connected by
2mm pitch 0.51 mm square pins. When designing the Dragonfly into a device, be sure to leave
about 1 cm (0.4") outward from the lower board to enable free air convection around the
Dragonfly. We recommend that the Dragonfly be soldered directly to the board. Alternatively,
the Dragonfly can be attached to socket connectors mounted on the PCB.
Note: Elmo recommends you leave approximately 1 cm (0.4 in) of space on the side opposite
the terminals to allow for free air convection.
Dragonfly/ Bu tter fly Installation G uideInstallation
MAN-DRBUIG (Ver. 1.1)
3-4
3.5 Integrating the Dragonfly and Butterfly on a PCB
The Dragonfly and Butterfly are designed to be mounted on a PCB, either by soldering the
pins directly to the PCB or by using suitable socket connectors. In both cases the following
rules apply:
3.5.1 Traces
1. The size of the traces on the PCB (thickness and width) is determined by the current
carrying capacity required by the application.
The rated continuous current limit (Ic)of the Dragonfly and Butterfly is the current
used for sizing the motor traces (M1, M2, M3 and PE) and power traces (VP+, PR
and PE).
For control, feedbacks and Inputs/ outputs conductors the actual current is very
small but “generous” thickness and width of the conductors will contribute to a
better performance and lower interferences.
2. The traces should be as short as possible to minimize EMI and to minimize the heat
generated by the conductors.
3. The spacing between the high voltage conductors (VP+, PR, M1, M2, M3, VL) must be
at least:
Surface layer: 1.5 mm
Internal layer: 0.10 mm
Complying with the rules above will help satisfy UL safety standards, MIL-STD-275 and the
IPC-D-275 standard for non-coated conductors, operating at voltages lower than 100VDC and
at "unlimited altitudes" (above 10,000 meters – 30,000 feet).
Dragonfly/ Bu tter fly Installation G uideInstallation
MAN-DRBUIG (Ver. 1.1)
3.5.2 Grounds and Returns
The “Returns” of the Dragonfly and Butterfly are structured internally in a star configuration.
The returns in each functional block are listed below:
Functional Block Return Pin
Power PR (Power Return)
Internal Switch Mode P.S. PR (Power Return)
Control section Internal, not accessible
Feedback SUPRET (J2/2)
The returns above are all shorted within the Dragonfly and Butterfly in a topology that results
in optimum performance.
1. When wiring the traces of the above functions, on the Integration Board, the Returns of
each function must be wired separately to its designated terminal on the Dragonfly and
Butterfly. DO NOT USE A COMMON GROUND PLANE. Shorting the commons on the
Integration Board may cause performance degradation (ground loops, etc).
3-5
2. Return Traces: The return traces should be as large as possible, but without shorting
each other, and with minimal cross-overs.
3. Main Power Supply and Motor Traces: The power traces must be kept as far away as
possible from the feedback and control traces.
4. PE Terminal: The PE terminal is connected directly to the Butterfly's heatsink or to the
Dragonfly's two PE strips on its lower board. In the Butterfly, the heatsink serves as an
EMI common plane. The PE terminal should be connected to the system's Protective
Earth. Any other metallic parts (such as the chassis) of the assembly should be connected
to the Protective Earth as well.
5. Under normal operating conditions, the PE trace carries no current. The only time these
traces carry current is under abnormal conditions (such as when the device has become a
potential shock or fire hazard while conducting external EMI interferences directly to
ground). When connected properly the PE trace prevents these hazards from affecting
the drive.
Follow these instructions to ensure safe and proper implementation.
Failure to meet any of the above-mentioned requirements can result in
drive/controller/host failure.
Dragonfly/ Bu tter fly Installation G uideInstallation
MAN-DRBUIG (Ver. 1.1)
3.6 Pin Functions
The Dragonfly and Butterfly are PCB mounted analog servo drives. Their pinouts are
described below.
3.6.1 Pinouts
3-6
No.
Pins Type
2X11 J1 I/O connector
Port Function Connector Location
2 M3 Motor power output 3
2 M2 Motor power output 2
2 M1 Motor power output 1
2 mm Pitch
0.51 mm SQ
2 PE Protective earth
2 PR Power input return
2 VP+ Positive power input
1
VL Auxiliary power input
Dragonfly/ Bu tter fly Installation G uideInstallation
MAN-DRBUIG (Ver. 1.1)
3.6.2 Connector J1
3-7
Pin # Short
Form Function
Description
1 EN+ Enable + Positive voltage input of the “Amplifier Enable” function.
To enable operation of the amplifier, the optocoupler
must be energized by applying voltage between this pin
(+) and pin J1/22 (-).
The optocoupler is isolated from the amplifier. See Figure
3-4.
“OFF” voltage: 0 V < Vin < 1 V.
“ON” voltage: 2.5 V < Vin < 10 V, 5 V typically with
current consumption 2.5 mA.
2 AOK Amplifier OK When the amplifier under normal operating conditions,
this output is in the “active low“ state. When a failure
occurs, this output is changed to the “open” state.
The optocoupler is an isolated, open collector NPN type.
See Figure
3-4.
Maximum voltage = 30 V
Maximum current = 8 mA
“On” voltage: V
OUT(On)
< 0.8 V
Refer to Section 4.3.
3 SO1 Status output 1 Specifications same as in pin J1/2.
4 HA Hall A input Logic levels: TTL
Maximum input voltage
: 15 VDC.
5 HB Hall B input Logic levels: TTL
Maximum input voltage
: 15 VDC.
6 HC Hall C input Logic levels: TTL.
Maximum input voltage: 15 VDC.
7 LATCH Latch mode Latch mode input. For more details see the Latch Mode
section in Chapter 4.
8 ECLRET Current limits
return
9 ECLC External
current limit
continuous
10 CM Current
monitor
11 CREF+ Current
command
positive
12 CREF- Current
command
negative
13 CMRET Current
monitor return
Current limit signals return.
External voltage scales down the rated value.
Voltage range: 0 V to 3.75 V (3.75 V = rated Ic)
Refer to Section 4.2.
Analog output with a scale of ± 3.9 V for ± Ip.
Output resistance: 1 kΩ
Positive input of a differential amplifier:
Input operating voltage range: ±3.75 V
Maximum input voltage: ±20 V
Maximum common mode voltage: ±6 V
Differential input impedance: 40 kΩ
Refer to Section 4.1.
Negative input of a differential amplifier.
Same specification as in pin J1/11.
Current monitor (CM) signal return.
Dragonfly/ Bu tter fly Installation G uideInstallation
MAN-DRBUIG (Ver. 1.1)
Pin # Short
Form Function
Description
3-8
14 ECLP External
current limit
peak
External voltage scales down the rated value.
Voltage range: 0 V to 3.75 V (3.75 V = rated Ip)
Refer to Section 4.2.
15 LMRET Latch Mode
Return for Latch Mode signals.
return
16 GAIN Current gain
change
17 HARET Hall supply
Shorting this pin to LMRET pin (J1/15) reduces
the proportional gain of the current loop by 70%.
Return used only for Hall supply.
voltage return
18 HALL+
5V
19 SORET Status output
+5 V Hall
supply voltage
return
+5 V supply voltage for Hall sensors.
Output current: maximum of 13 mA.
Status output common AOK, SO1, SO2, SO3.
Isolated from circuit common. See Figure
3-4.
20 SO2 Status output 2 Status indication output 2.
Same specification as in pin J1/2.
21 SO3 Status output 3 Status indication output 3.
Same specification as in pin J1/2.
22 EN- Enable - Negative voltage input of “Amplifier Enable” function.
Optocoupler is isolated from the amplifier.
For details, see pin J1/1.
Dragonfly/ Bu tter fly Installation G uideInstallation
The same circuit board used for the Ocarina and Castanet is also available for evaluating the
Dragonfly and Butterfly. It comes with standards terminal blocks for power connections and
D-sub plugs/sockets for signals connections. The Evaluation Board is provided with a cable
kit.
Evaluation Board Catalog Number
Evaluation Board User Manual
OCA-EVLBRD-1
MAN-EVLBRD-OCA (available on our web site)
Dragonfly/ Bu tter fly Installation G uideInstallation
MAN-DRBUIG (Ver. 1.1)
3.9 DC Power Supply
The DC power supply can be at any voltage in the range defined in the technical
specifications (the Appendix of this guide). The supply source must comply with the safety
aspects of the relevant requirements, in accordance with the most recent version of the
standard EN60950 or equivalent Low Voltage Directive Standard, all according to the
applicable over-voltage category. If the power source to the power supply is the AC line
(through an isolated transformer), safety margins must be considered in order to avoid
activating the under/over voltage protection due to line variations and/or voltage drop
under load.
In addition to the above, the transformer must comply with the safety aspects of the relevant
requirements in accordance with the most recent version of the standard EN60742 (Isolating
and Safety Isolating Transformers). The nominal DC bus voltage should be in the following
range:
3-10
1.2 V
< Vdc < 0.9 V
dcmin
dcmax
where:
V
Vdcmax
is the minimum DC bus
dcmin
is the maximum DC bus
The recommended minimum power supply capacitance for a single-phase rectified DC source
connection is as follows:
Amplifier Voltage Range 60 V 100 V
Recommended capacitance ≥ 470 µF ≥470 µF
The transformer power should be calculated such that it will be able to deliver power to the
amplifier (including peak power) without significant voltage drops.
The power supply should be located as close as possible to the amplifier. The maximum
distance is 30 cm (1 foot). While driving high-inertia loads, the power supply must be
equipped with a shunt regulator; otherwise, the amplifier will be disabled whenever the
capacitors are charged above the maximum voltage, during motor break down.
Dragonfly/ Bu tter fly Installation G uideInstallation
Dragonfly/ Bu tter fly Installation G uideInstallation
MAN-DRBUIG (Ver. 1.1)
3.10 Heat Dissipation
3.10.1 Butterfly
The best way to dissipate heat from the Butterfly is to mount it so that its heatsink faces up.
For best results leave approximately 10 mm of space between the Butterfly's heatsink and any
other assembly.
3.10.1.1 Thermal Data
• Heat dissipation capability (θ): Approximately 10 °C/W.
• Thermal time constant: Approximately 240 seconds (thermal time constant means
that the Butterfly will reach 2/3 of its final temperature after 4 minutes).
• Shut-off temperature: 86 °C – 88 °C (measured on the heatsink)
3.10.1.2 Heat Dissipation Data
Heat Dissipation is shown in graphically below:
3-12
10.0
Power Dissipation (Watt
Butterfl
Whistle - 60 Series Power Dissipation
9.0
8.0
7.0
6.0
5.0
Standard 40 °°°°C Ambient Temp.
4.0
3.0
2.0
1.0
0.0
2
1
0
0
.
.
5
7
5
3
.
2
5
3
4
5
.
.
7
5
Peak Current (A)
.
5
2
5
50V
40V
30V
20V
External
Heatsink
Required
Heatsink
not
Required
6
.
7
5
.
.
2
5
5
8
7
6
9
9
.
7
5
)
Dragonfly/ Bu tter fly Installation G uideInstallation
MAN-DRBUIG (Ver. 1.1)
Whistle 100 Series Power Dissipation
Butterfly -100
3-13
6.0
External
5.0
Standard 40 °°°°C Ambient Temp.
Heatsink
Required
4.0
Pow er D i ss ipati o n (W
3.0
2.0
1.0
Heatsink
not
Required
0.0
2
5
0
5
1
0.
1.5
2.
3
3.5
4
5
5
4.
Peak Curr ent (A)
85VDC
70VDC
50VDC
3.10.1.3 How to Use the Charts
The charts above are based upon theoretical worst-case conditions. Actual test results show
30% - 50% better power dissipation.
To determine if your application needs a heatsink:
1. Allow maximum heatsink temperature to be 80 °C or less.
2. Determine the ambient operating temperature of the Butterfly.
3. Calculate the allowable temperature increase as follows:
• for an ambient temperature of 40 °C , ∆T= 80 °C – 40 °C = 40 °C
4. Use the chart to find the actual dissipation power of the drive. Follow the voltage
curve to the desired output current and then find the dissipated power.
5. If the dissipated power is below 4 W the Butterfly will need no additional cooling.
Note: The chart above shows that no heatsink is needed when the heatsink temperature is
80°C, ambient temperature is 40 °C and heat dissipated is 4 Watts:
3.10.2 Dragonfly
The best way to dissipate heat from the Dragonfly is to mount it so that its lower board faces
upwards. For best results leave approximately 10 mm of space between the Dragonfly's lower
board and any other assembly.
Dragonfly/B utterfly Installation Guide
MAN-DRBUIG (Ver. 1.1)
4-1
Chapter 4: Servo Control Operation
4.1 Current Command Input
The Dragonfly and Butterfly have a single differential input. The input operating voltage
range is ± 3.75 V, meaning that a 3.75 V signal will result in a fully rated peak current. The
current limit circuits will override this signal if the peak duration exceeds 2.7 seconds and/or
the required current exceeds the values set by the ECLC and ECLP signals. If the input
command voltage exceeds 3.75 V, input scaling must be implemented by adding a pair of
external resistors, according to the following formula:
Rin (kΩ) = (5.33 * Vin) - 20
Be careful not to apply input voltage above the maximum allowed input voltage as this will
cause the input operational amplifier to operate beyond its limits (±20 V) and in extreme
cases, may even damage it.
4.2 External Current Limit - Continuous (ECLC)
The continuous current limit of the Dragonfly and Butterfly amplifiers can be scaled down by
an external voltage or by an external resistor connected from pin J1/9 (ECLC) to pin J1/8
(ECLRET).
4.2.1 External Voltage
V
V
ECLC
IC(new) =
IC(new) =
An external positive voltage (0 to 3.75 V) to terminal J1/9 (ECLC) in reference to terminal J1/8
(ECLRET) will control the continuous current limit from zero to Ic (nom).
The voltage is internally clamped to 3.75 V whenever the external VECLC is greater than
3.75V.
The external voltage source must be able to source/ sink at least ±0.2 mA.
The maximum absolute VECLC allowed to be connected is 5 V.
ECLC
3.75V
3.75V
* Ic(nom)
* Ic(nom)
Dragonfly/B utterfly Installation GuideServo Control Operation
MAN-DRBUIG (Ver. 1.1)
4.2.2 External Resistor
Ic(new)
R
R
R
(Kohm) = 37.4 *
(Kohm) = 37.4 *
(Kohm) = 37.4 *
ECLC
ECLC
ECLC
Connect an external resistor between terminal J1/9 (ECLC) and terminal J1/8 (ECLRET).
The resistor value is given by:
0 < RECLC < 36.4 K (1/8 Watt)
At RECLC greater than 36.4 K, the current limit will be internally clamped to the nominal
value.
IC(nom) is the nominal continuous current limit of the amplifier.
Ic(new)
Ic(nom)
Ic(nom)
- 1
- 1
4-2
4.2.3 External Current Limit - Peak (ECLP)
The peak current limit of the Dragonfly and Butterfly amplifiers can be scaled down by an
external voltage or by an external resistor connected between pin J1/14 (ECLP) and J1/8
(ECLRET).
4.2.4 External Voltage
An external positive voltage (0 to 3.75 V) to terminal J1/14 (ECLP) in reference to terminal
J1/8 (ECLRET) will control the peak current limit from zero to Ip(nom).
V
V
ECLP
Ip(new) =
Ip(new) =
The voltage is internally clamped to 3.75 V whenever the external VECLP is higher than 3.75 V.
The external voltage source must be able to source/sink at least ±0.2 mA.
The maximum absolute VECLP allowed to be connected is 5 V.
ECLP
3.75V
3.75V
* Ip(nom)
* Ip(nom)
Dragonfly/B utterfly Installation GuideServo Control Operation
MAN-DRBUIG (Ver. 1.1)
4.2.5 External Resistor
Ip(new)
R
R
R
(Kohm) = 37.4 *
(Kohm) = 37.4 *
(Kohm) = 37.4 *
ECLP
ECLP
ECLP
Connect an external resistor between terminal J1/14 (ECLP) and terminal J1/8 (ECLRET).
The resistor value is given by:
Ip(new)
Ip(nom)
Ip(nom)
- 1
- 1
4-3
0 < R
< 36.4 K (1/8 Watt)
ECLP
At RECLP greater than 36.4K, the current limit will be internally clamped to the nominal
value.
IP(nom) is the nominal peak current limit of the amplifier.
4.2.6 Latch Mode (LM)
By connecting J1/7 to J1/15, the amplifier is latched to disable mode whenever a Short,
Commutation or Over Temperature failure occurs. Disabling the amplifier temporarily by
removing the power from Enable pin J1/1 resets the latch. Be sure to restore the Enable
connection when the reason for the event no longer exists.
4.3 Status Indications
The following table lists the Dragonfly and Butterfly amplifier status indications.
Function
Latch
Option
AOK
SO1
SO2
SO3
1Amplifier OK (AOK) N/A Low Open
Open collector Open collector
collector
2 External disable No Low Low Open collector Low
3 Current limit No Low Open
Open collector Low
collector
4 Short Yes Open
Low Open collector Low
collector
5 Over temperature Yes Open
collector
6 Internal supplies
protection
No Open
collector
7 Under voltage No Open
Open
Low Low
collector
Low Low Open collector
Low Open collector Open collector
collector
8 Over voltage No Open
collector
9 Shunt* No Low Open
Open
collector
Low Open collector
Low Open collector
collector
Dragonfly/B utterfly Installation GuideServo Control Operation
MAN-DRBUIG (Ver. 1.1)
4-4
Function
10 Power up reset No Open
11 Commutation failure Yes Open
Latch
Option
AOK
collector
SO1
Open
SO2
Open collector Open collector
collector
Low Low Low
collector
* This indication can be used as a digital input for activating an external shunt regulator.
Table 4-1: Dragonfly/Butterfly Status Indications
Notes:
Without latch mode:
The status indications are reset when the fault disappears.
With latch mode:
The Short, Over Temperature and Commutation Failure status indications are reset
when the enable signal is temporarily removed from the enable input.
Multiple faults:
Only the reading of the first fault is reliable. Additional faults add on to the status
outputs and the indication is therefore meaningless.
SO3
Dragonfly/B utterfly Installation Guide
MAN-DRBUIG (Ver. 1.1)
A-1
Appendix: Specifications
A.1 General Specifications
A.1.1 Butterfly
Feature Units 15/48 5/60 10/60 15/60 2.5/100 5/100 10/100 15/100
Minimum supply
voltage
Nomin al sup p l y volta g e V D C 42 50 85
Maximum supply
voltage
Maximum continuous
power output
Efficiency at Rated Power
(at nominal conditions)
Maximum output voltage 93% of DC bus voltage at f=32 kHz
DC and trapezoidal
commutation continuous
current limit (Ic)
Peak current limit A 2 x Ic
Weight g (oz) 45 g (1.6 oz)
Dimensions mm (in) 55 x 15 x 46.5 (2.2" x 0.6" x 1.8")
Mounting method PCB mount
VDC 11 11 20
VDC 48 59 95
W 700 280 570 850 230 460 920 1400
% Up to 99%
A 15 5 10 15 2.5 5 10 15
Dragonfly/Butterfly Installation G uide Specifications
MAN-DRBUIG (Ver. 1.1)
A-2
A.1.2 Dragonfly
Feature Units 3/60 2.5/100
Minimum supply vo lt ag e VDC 11 20
Nominal supply vol tag e VD C 50 85
Maximum supply voltag e VDC 59 95
Maximum continuous power
output
Efficiency at rated power % Up to 99%
Maximum output voltage 93% of DC bus voltage at f=32 kHz
DC and trapezoidal commutation
continuous current limit (Ic)
Peak current limit A 2 x Ic
Weight g (oz) 21.5 g (0.76 oz)
Dimensions mm (in) 51 x 12.5 x 42 (2" x 0.49" x 1.65")
Mounting method PCB mount
W
A
190 240
3.3 2.5
A.2 Environmental Specifications
Ambient
Temperature
Range
Temperature
Shock
Non-operating
conditions
-50 °C to +100 °C (-58 °F to 212 °F)
Operating conditions -40 °C to +70 °C (-40 °F to 160 °F)
Non-operating
conditions
-40 °C to +70 °C (-40 °F to 160 °F)
within 3 min.
Altitude
Maximum
Humidity
Vibration
Mechanical
Shock
Non-operating
Unlimited
conditions
Operating conditions -400 m to 155,000 m (-1,300 ft to 510,000 ft)
Non-operating
conditions
Up to 95% relative humidity non-condensing
at 35 °C (95 °F)
Up to 95% relative humidity non-condensing
Operating conditions
at 25 °C (77 °F), up to 90% relative humidity
non-condensing at 42 °C (108 °F)
Operating conditions20 Hz –2,000 Hz, 14.6g
Non-operating
±40g; Half sine, 11 msec
conditions
Operating conditions
±20g; Half sine, 11 msec
Dragonfly/Butterfly Installation G uide Specifications
MAN-DRBUIG (Ver. 1.1)
A.3 Standards Compliance
A.3.1 Quality Assurance
Specification Details
ISO 9001:2000 Quality Management
A.3.2 Design
Specification Description
A-3
In compliance with MIL-STD-704
In compliance with MIL-STD-810
Aircraft, Electric Power Characteristics
Environmental Engineering Conside rations and
Laboratory Tests
In compliance with MIL-STD-1275
Characteristics of 28 Volt DC Electrical Systems in
Military Vehicles
In compliance with MIL-STD-461
Requirements for the Control of Electromagnetic
Interference Characteristics of Subsystems and
Equipment
In compliance with MIL-HDBK-217
IPC-D-275
IPC-SM-782
Reliability Prediction of Electronic Equipment
Reliability prediction of electronic equipment
(rating, de-rating, stress, etc.)
Recognized UL508c Power conversion equipment
In compliance with UL840 Insulation coordination, including clearance and
creepage distances of electrical equipment
In compliance with UL60950 Safety of information technology equipment,
including electrical business equipment
In compliance with EN60204-1 Low voltage directive, 73/23/EEC
Dragonfly/Butterfly Installation G uide Specifications
MAN-DRBUIG (Ver. 1.1)
A.3.4 EMC
Specification Details
A-4
In compliance with
Electromagnetic compatibility (EMC)
EN55011 Class A with EN61000-6-2:
Immunity for industrial environment,
according to:
IEC61000-4-2 / criteria B
IEC61000-4-3 / criteria A
IEC61000-4-4 / criteria B
IEC61000-4-5 / criteria B
IEC61000-4-6 / criteria A
IEC61000-4-8 / criteria A
IEC61000-4-11 / criteria B/C
A.3.5 Workmanship
Specification Details
In compliance with IPC-A-610, level 3 Acceptability of electronic assemblies
A.3.6 PCB
Specification Details
In compliance with IPC-A-600, level 3 Acceptability of printed circuit boards
A.3.7 Packing
Specification Details
In compliance with EN100015 Protection of electrostatic sensitive devices
A.3.8 WEEE*
Specification Description
In compliance with 2002/96/ECWaste Electrical and Electronic Equipment
regulations
* Please send out-of-service Elmo drives to the nearest Elmo sales office.
A.3.9 RoHS
Specification Description
In compliance with 2002/95/EC
(effective July 2006)
Restrictions on Application of Hazardous
Substances in Electric and Electronic Equipment
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.