ELK 960 User Manual

OVERVIEW
The ELK-960 features adjustable delay time of one (1) second to approximately sixty (60) minutes. It can be operated by 12 to 24 volts D.C. and can be triggered by a negative (-) or positive (+) voltage. The operating mode and the relay condition can be set as follows: BEGIN- Relay turns on when triggered and back off when delay time expires. END- Relay turns off when triggered and back on when delay time expires. The delay time can start when the trigger is first applied (B mode) or when the trigger is removed (A mode). The ELK-960 relay can be set to provide a single 1-SHOT output or to REPEAT (pulse on and off). All options are selected using easy to change mini-jumpers.
TERMINAL DESCRIPTIONS
Positive power input. Connect a +12 to +24 Volts
+
D.C. source. Warning: Do not exceed +24 Volts D.C., Damage will occur.
Negative power (ground) input. Connect to a nega-
-
tive or ground terminal of the power source.
TGR Trigger voltage input. Connect a 4.5 to 24VDC trigger
source. Place jumper JP5 (TRIGGER POLARITY) in the "+" position to trigger from a positive voltage or in the "-" position to trigger from a negative. The trigger voltage may be 4.5 to 24VDC, regardless of the main powered input (12Vdc to 24VDC).
N/O Normally Open side of the relay contacts. No con-
nection to COM when the relay is off.
Delay Timer
ELK-960
APPLICATION:
The ELK-960 is an economical and flexible solution for many general-purpose time delay applications. The unit operates on 12 to 24 Volts D.C. and can be selected for positive or negative trigger logic. Setup is easy with thumbwheel adjustment between 1 and 60 seconds, a quick jumper setting converts the time from seconds to minutes. The timer can be configured to activate once for each trigger, or pulse as soon as power is applied.
Delay Timer
ELK-960
Economical Time Delay Relay Module
COM Common or "pole" side of the relay contacts. When
the relay is off, COM is internally connected with the N/C contact. When the relay is on, COM is internally connected with the N/O contact.
N/C Normally Closed side of the relay contacts. This
terminal is internally connected with the COM termi­nal when the relay is off.
NOTE: The ELK-960 automatically triggers (turns on) and runs through a delay cycle when first powered up. To reduce waiting time and speed up installation, set jumper JP1 to SEConds and adjust R3 to 1 before applying power. Once power is applied, change the settings as required.
SETTINGS AND JUMPER DESCRIPTIONS
R3 This knob is used to increase or decrease the delay time
from 1 to 60. Full clockwise is 1, halfway is 30, full counter-clockwise is 60. The arrow is a reference point.
JP1 SEC = Delay time in seconds. Adjustable from 1 ~ 60.
MIN = Delay time in minutes. Adjustable from 1 ~ 60.
JP2 REPEAT = (Adjustable pulse) Relay cycles ON / OFF at
1-SHOT = Relay activates only once per trigger.
JP3 END = Relay turns off when triggered and back on
BEGIN = Relay turns on when triggered and back off
JP4 A = Delay time starts when trigger is removed.
B = Delay time starts when trigger is first applied.
JP5 + = Selects positive polarity for the input trigger.
- = Selects negative polarity for the input trigger.
1
Times are approximate. When adjusted to the highest setting (60 minutes) the actual time delay will be slightly greater.
HINT: For a delay time in minutes, adjust and test with jumper JP1 in the SEConds position. (IE: For a 15 minute delay, adjust and test to 15 seconds) Then move jumper JP1 to MINutes. This quickly provides a reasonable equivalent delay time in minutes.
2
A 50/50 duty cycle means the OFF and ON times will be
equal.
03/04
delay time interval using a 50/50 duty cycle. A trigger input will temporarily stop the cycle.
when delay time expires. when delay time expires.
1
1
FEATURES:
Operating Voltage Range: 12 to 24 Volts D.C.
Adjustable Delay Time.
Positive or Negative Low Current Trigger.
SPDT (Form "C") Relay.
Selectable Initial Relay State: ON / OFF.
Output Modes: One-Shot or Repeat.
Lifetime Limited Warranty, call for details.
Packed In Reusable Poly Storage Box.
SPECIFICATIONS:
Time Settings: 1 Sec to ~ 60 Min.
Relay Contact Rating: 7A @ 30 VDC.
2
Operating Voltage: 12 to 24 Volts D.C.
10A @ 125 VAC.
Trigger Voltage: 4.5 - 24 Volts D.C.
Input Trigger Current: 1.2 mA.
Current Draw With Relay On: 40mA.
Size: 3"x2.2"x1" (Fits Std.Snap Track).
Features and Specifications subject to change without notice.
828-397-4200 Voice 828-397-4415 Fax http://www.elkproducts.com
PO Box 100 • Hwy. 70W Hildebran, NC 28637 • USA
Instructions Printed On Inside
email: info@elkproducts.com
SAMPLE APPLICATIONS AND WIRING DIAGRAMS (Set jumpers as shown)
12/24V DOOR
STRIKE
12/24 Volts DC
Power Supply
+
-
-
+
Pushbutton
N/O
DOOR STRIKE HOLD
1
TRIGGER
POLARITY
JP5
TIME 1 - 60
+-
K1
ELK-960
Delay Timer
+
-
TGR
N/O
COM
N/C
LED
TIMER
TRIGGER
MODE
A B
JP1 JP2 JP3
R3
SEC MIN
REPEAT 1-SHOT
END BEGIN
JP4
Used to extend the relea se time of an access control device
or to manually activate a d oor strike release device. The
trigger is activated by a conta c t closu re or a N/O pushbutton
and the door strike re m a in s a ctivated (do or o pen) after the
button is released fo r the d elay tim e s et u p in the ELK-960.
Power Suppl y
SIREN
-
+
12 Volts DC
+
-
CONTACT ON
N/C
DOOR
DOOR PROP AL ARM
3
TRIGGER POLARITY
JP5
TIME 1 - 60
+-
K1
ELK-960
Delay Timer
+
-
TGR
N/O
COM
N/C
LED
TIMER
TRIGGER
MODE
A B
JP1 JP2 JP3
R3
SEC MIN
REPEAT 1-SHOT
END BEGIN
JP4
Delay is starte d when the door is opened. If the door
remains opened after the time delay has expired th e relay
will turn on and remain on until the door is closed. If the door
is closed before the time delay expires the ELK-960 is reset
awaiting another input from the door contact.
CONTROL PANEL
CLOSED
+ ARMED
ZONE
OUTPUT
INPUT
N/C
CONTACT ON
EXIT DOOR
12V AUX
- +
TGR
N/O
COM
N/C
5
SHUNT TIMER
ELK-960
Delay Timer
+
-
LED
EXIT DELAY
TIME 1 - 60
TRIGGER POLARITY
+-
JP5
TRIGGER
K1
MODE A B
JP4
JP1 JP2 JP3
R3
SEC MIN
REPEAT 1-SHOT
END BEGIN
Provides an exit delay to an otherwise instant a larm loop.
The ELK-960 is triggered by the control's Armed output. The
door contact is t hen shunted by the relay contacts . After the
user has exited and t he delay time has expired, the door
contact is restored into the loop.
CONTROL PANEL
12V ALARM
OUTPUT
+
-
12V Bell or Siren
TGR
N/O
COM
N/C
+-
ALARM CUT-OFF
7
ELK-960
Delay Timer
+
-
LED
TRIGGER POLARITY
JP5
TIMER
TIME 1 - 60
+-
K1
TRIGGER
MODE A
B
JP1 JP2 JP3
R3
SEC MIN
REPEAT 1-SHOT
END BEGIN
JP4
Useful for adding a cut-off timer to a control panel that does
not have one. It can also be used to shorten the cut-off timer
for a control with no adjustable timer.
12 Volts DC
N/O
SWITCH
Power Supply
- +
USING TWO 960'S TO DELAY THEN THEN TOGGLE A RELAY
9
TRIGGER POLARITY
JP5
TIME 1 - 60
+-
K1
TRIGGER
MODE
A B
JP1 JP2 JP3
R3
#1 #2
JP4
ELK-960
Delay Timer
+
-
TGR
N/O
COM
N/C
LED
SEC MIN
REPEAT 1-SHOT
END BEGIN
12/24V
MAGLOCK
12/24 Volts DC
Power Supply
+
-
-
+
Pushbutton
N/O
MAGLOCK RELEASE
2
TRIGGER
POLARITY
JP5
TIME 1 - 60
+-
K1
ELK-960
Delay Timer
+
-
TGR
N/O
COM
N/C
LED
TIMER
TRIGGER
MODE
A B
JP1 JP2 JP3
R3
SEC MIN
REPEAT 1-SHOT
END BEGIN
JP4
Used to extend the rele ase tim e of an access control device or to manually activa te a doo r maglock release device. The
trigger is activated by a c ont act closure or a N/O pushbutton
and the door mag lock remains released (door open) after the
button is released for the delay time set up in the ELK-960.
Motion
Detector
COM
120VAC
Supply
+
N/C
-
12 Volts DC
Power Supply
+
-
22K Ohm
Resistor
Hot
120V
LIGHT
Neutral
AUTOMAT IC LIGHT
4
ELK-960
Delay Timer
TRIGGER POLARITY
TGR N/O COM N/C
+
-
LED
CONTROL
TIME 1 - 60
+-
JP5
TRIGGER
K1
MODE A B
JP4
JP1 JP2 JP3
R3
SEC MIN
REPEAT 1-SHOT
END BEGIN
For turning on an interior or exterior light with a motion
detector. When motion is detected, the ELK-960 is triggered
and the light is turned on. The amount of time the light rem ains
on after the detector resets is adjustable. Delay time will
automatically restart each time the motion detector activates.
CONTROL PANEL
CLOSED
ZONE
INSTANT ACTIVATION OF ZONE
12V AUX
-
N/C
CONTACT
WITH DELAYED RESTORAL
+
22K Ohm
Resistor
ELK-960
6
Delay Timer
TRIGGER POLARITY
JP5
TGR
N/O
COM
N/C
+
-
LED
+-
K1
TIME 1 - 60
TRIGGER
MODE A
B
JP1 JP2 JP3
R3
SEC MIN
REPEAT 1-SHOT
END BEGIN
JP4
When contact o pens, relay is turned on which causes
instant zone violation. Contact reclosure will cancel trigger
applied by resistor. Delay starts when cont act closes.
Relay turns off and zone restores after delay ti me expires.
CONTROL PANEL
12V ALARM
OUTPUT
- +
12V LIGHT or LED
+ -
12V Bell or Siren
-
+
TGR N/O
COM
N/C
+
8
ELK-960
Delay Timer
-
LED
BELL OR LIGHT
FLASHER
TRIGGER POLARITY
JP5
TIME 1 - 60
+-
K1
TRIGGER
MODE A B
JP4
JP1 JP2 JP3
R3
SEC MIN
REPEAT 1-SHOT
END BEGIN
Converts a steady output to pulsing, suitable for fl ashing a light
or pulsing an audible device. Note: Alarm output must be
capable of supplying enough current to drive the bell and light.
TRIGGER
POLARITY
JP5
TIME 1 - 60
+-
K1
TRIGGER
MODE
A B
JP1 JP2 JP3
R3
SEC MIN
REPEAT 1-SHOT
END BEGIN
JP4
120VAC
Supply
Hot
120V
LIGHT
Neutral
ELK-960
Delay Timer
+
-
TGR N/O COM
N/C
LED
Used for delaying a trigger then toggling a relay on/off. ELK-960 #1 starts a time delay when the N/O switch is closed.
When 960 #1's time d e lay expires, 960 #2 is triggered turni ng it's relay on for the time delay setting , then turning the relay
off. (toggle) To sumarize: fire trigger on #1, waits, turns on #2's relay, waits, then turns relay off.