A complete product line to fi t all your application needs
The Electro-Boiler™ has been heating America’s homes and
businesses since 1980. We take pride in our craftsmanship
and we use only the best materials to ensure a high quality
product. We are commited to you and we are confi dent that
you will be completely satisfi ed with the Electro-Boiler.
Submittal Sheets are available for each model at
www.electromn.com in the Dealer Support section.
Electro
Providing Comfort Through
Efficient Energy Solutions
MINI-BOILER* MECHANICAL
Pressure Relief
Valve (30 PSIG)
Supply Pressure &
Temperature Gauge
Return Pressure &
Temperature Gauge
WarmFlo
Sensor
Return
From
Radiation
Boiler
Indicator
Lights
Air Eliminator
Expansion
Tank
Circulator
Pump
Supply to
Radiation
Manifold or
Other Radiant Heat
Application
*This plumbing arrangement also
applies to the Midsize boiler.
MINI-BOILER ELECTRICAL
BOILER
SOURCE
POWER
L1 L2
PUMP
NEUTRAL
120VAC
PUMP
POWER
L2L1G
LMC
SHOWN WITH
COVER REMOVED
NO INTERNAL
WIRING SHOWN
2
BLUE
BLUE
R W C
T-STAT
CABLE
1
2
STATUS
INDICATOR
LIGHTS
C
W
R
1
SLAB SENSOR
ANY 2-WIRE STAT OR END SWITCH
CONTACT CAN BE USED TO
OPERATE R & W, ELECTRO-STAT
SHOWN AS EXAMPLE ONLY
TRANSFORMER FOR INTERNAL
CIRCUITS ONLY. ZONE VALVES, ETC.
MUST HAVE THEIR OWN 24V
SOURCE
MINIMUM CLEARANCE FROM SUGGESTED MINIMUM
COMBUSTIBLE SURFACES SERVICE CLEARANCE
BACK 0 INCH 0 MM 0 INCH 0 MM
LEFT 1 INCH 25 MM 6 INCHES 152 MM
RIGHT 1 INCH 25 MM 6 INCHES 152 MM
FRONT 1 INCH 25 MM 24 INCHES 610 MM
TOP 1 INCH 25 MM 24 INCHES 610 MM
BOTTOM REQUIRED CLEARANCE - 10 INCHES/254 MM
STANDARD EQUIPMENT
Staging - EB-MS-**
▪ Supply water sensing
▪ Regulates to front panel selected temperature
▪ Staging indicator lights
▪ DC Power Relays
▪ Hi-limits: 1
2nd - manual reset at 205° F
▪ Circulator switching relay - 10-amp maximum
▪ Thermostat or end switch connection (R and W)
▪ Utility load control provisions
▪ 2.2 gl. Steel vessel ASME “H” Stamp (20-year
MINIMUM CLEARANCE FROM SUGGESTED MINIMUM
COMBUSTIBLE SURFACES SERVICE CLEARANCE
BACK 0 INCH 0 MM 0 INCH 0 MM
LEFT 1 INCH 25 MM 12 INCHES 305 MM
RIGHT 1 INCH 25 MM 6 INCHES 152 MM
FRONT 1 INCH 25 MM 24 INCHES 610 MM
TOP 1 INCH 25 MM 24 INCHES 610 MM
BOTTOM REQUIRED CLEARANCE - 18 INCHES/457 MM
TS SERIES
STANDARD EQUIPMENT
Staging - EB-S-**
▪ Supply water sensing
▪ Regulates to front panel selected temperature
▪ Staging indicator lights
▪ DC Power Relays
▪ Hi-limits: 1st - automatic reset at 190° F
2nd - manual reset at 205° F
▪ Circulator switching relay - 10-amp maximum
▪ Thermostat or end switch connection (R and W)
▪ Utility load control provisions
▪ 6.5 gl. Steel vessel ASME “H” Stamp (20-year
MINIMUM CLEARANCE FROM SUGGESTED MINIMUM
COMBUSTIBLE SURFACES SERVICE CLEARANCE
BACK 0 INCH 0 MM 0 INCH 0 MM
LEFT 1 INCH 25 MM 12 INCHES 305 MM
RIGHT 1 INCH 25 MM 6 INCHES 152 MM
FRONT 1 INCH 25 MM 24 INCHES 610 MM
TOP 1 INCH 25 MM 24 INCHES 610 MM
BOTTOM REQUIRED CLEARANCE - 16 INCHES/406 MM
** = S, WA, or WO
STANDARD EQUIPMENT
Staging - EB-CA-**
▪ Supply water sensing
▪ Regulates to front panel selected temperature
▪ Staging indicator lights
▪ Heavy duty contactors
▪ Hi-limits: 1st - automatic reset at 190° F
2nd - manual reset at 205° F
Note: Head Loss based on 110° F return temperature.
ELECTRIC SUPPLY
ModelVoltsWattsAmpskWPhaseBtu/hCB
EB-C-18-4848018,0002218
EB-C-36-4848036,0004436
EB-C-54-4848054,0006554
EB-C-27-2020827,0007527
EB-C-40-2020840,50011340.5
EB-C-27-2424027,0006527
EB-C-40-2424040,5009840.5
EB-C-3124031,50013131.5
EB-C-3624036,00015036
Flow - 30° F/11° C
3-60
3-60
3-60
3-60
3-60
3-60
3-60
1-60
1-60
61,43430
122,86860
184,30280
92,151100
138,226150
92,15180
138,226125
107,509100 + 80
122,868100 + 100
Head Loss
CLEARANCES
MINIMUM CLEARANCE FROM SUGGESTED MINIMUM
COMBUSTIBLE SURFACES SERVICE CLEARANCE
BACK 0 INCH 0 MM 0 INCH 0 MM
LEFT 1 INCH 25 MM 16 INCHES 406 MM
RIGHT 1 INCH 25 MM 6 INCHES 152 MM
FRONT 1 INCH 25 MM 24 INCHES 610 MM
TOP 1 INCH 25 MM 24 INCHES 610 MM
BOTTOM REQUIRED CLEARANCE - 16 INCHES/406 MM
Flow - 40° F/16° C
Head Loss
ZONE CONTROLLER
This will simplify your wiring and make zoning applications much easier. In addition, enhanced communicating
features have the ability to stage the electric boiler based upon the connected zone capacity.
Standard Features
• Terminal block wiring, visual
wiring layout
• Indicator lights showing zone
operation
• 24-volt, 40VA transformer
120/208/240 connection
• Fuse protection
• Priority option
• Dual temperature operation
• Applies to digital or
standard thermostats
• Dial switch, select each zone
capacity
All Others
EB-ZXA-1 - universal, pumps or valves, non-communicating, for any boiler
EB-ZS-4 - automatic staging system for Brand X boilers or dual EB-R, -L, -E Series
EB-ZC-4 - wiring and convenience interface, isolated boiler end switch
EB-5415A - low cost, 2 or 3 zones, sheds one boiler stage (Mini-Boiler enhancement)
Pumps, Actuators, Valves
EB-ZTA-1 - install within boiler cabinet
EB-ZEA-1 - with enclosure and 40VA transformer
EB-ZEA-2 - add additional 4, enclosure and 40VA
Pumps
EB-Z2P - two pumps with priority and dual temp.
Zone Valves
EB-ZTS-1 - install within boiler cabinet, encl. option
EB-ZTS-2 - add additional 4, enclosure and 40VA
SLAB STAT
Sensing and controlling the system based upon radiant fl oor surface temperature
or the concrete mass has very positive benefi ts. Radiant fl oor air stat in the same
area as a forced air roomstat presents serious control problems. A remote sensing
slab stat for the radiant fl oor removes this issue.
Remote sensing slab stat is required for storage applications.