Electro Industries EB-MS-15, EB-MS-20, EB-MX-10, EB-MX-15, EB-MX-20 Installation Manual

ELECTRO-BOILER
Midsize
INSTALLATION & OPERATING INSTRUCTIONS
Model EB-M(S or X)-10 EB-M(S or X)-15 EB-M(S or X)-20
APPLICATION: This Electro-Boiler is factory equipped with WarmFlo smart controller.
WarmFlo automatically regulates outlet water temperature based on a desired
output temperature set point.
Primary application is any hydronic water heating system where reduced flow or radiation can cause overheat conditions (example, zones). However, if it is a mixture of large and small zones, the sudden capacity and flow changes may cause some internal timing/over temp conditions. With the mixture of zones the Electro Industries’ zone controller option is highly recommended.
This series is equipped for load management interrupt and can apply to standard baseboard radiation (not recommended for EB-MS Model), dual heat combinations, under floor radiant, wood boiler supplement, etc.
Note: If this installation does not include dual heat standby boiler, the front panel switch must always be in the “normal” position.
ACCESSORIES: Attached BL001 lists various accessory or option items which are not part of
basic Electro-Boiler. See Room Thermostat Placement section for additional information on slab stat.
Note: This product meets the requirements of the ASME Boiler and Pressure Vessel Code.
10/27/2016 BI516
TABLE OF CONTENTS
Description Page
Introduction 1 System or Water Flow 2 Multiple Zones & Radiant Temperatures 2 Zone Controller 2 Room Thermostat Placement 3 Two-Temperature Operation or Feature 3 Multiple Boilers 4 Boiler/Plumbing Kit Placement 5 Installation Requirements 5 Mechanical Installation
Under-Floor Radiant 7 Dual Heat 8
Electrical Hookup 9
Standby Boiler 10 Water Fill Procedure 10 Controller Setup 11 Staging/Modulating Jumper 12 Operational Tips 13 Standby Switchover, SOT Timer 14 Replacement Parts List 15 Troubleshooting/Repair Helps 16 WarmFlo Operational Information 17
Drawings:
Hookup BH511 Basic Mechanical BX505 Plumbing, Series Dual Boilers BX506 Internal Wiring Schematic UAW416 Low Voltage Wiring Diagram UAW849 Boiler Accessories BL001 Warranty XX017
10/27/2016 BI516
INTRODUCTION
With this WarmFlo configuration, the electric heating elements are automatically staged/modulated and controlled to establish a fixed outlet water temperature. This outlet temperature is sensed by the WarmFlo controller and is controlled to achieve and maintain the boiler’s set point temperature.
Even though this WarmFlo configured unit adjusts outlet temperature independent of water flow and prevents high limiting even with marginal water flow, it is still very important that the hydronic system be correctly designed for the building, the total heat loss requirement, and proper hydronics design and installation practices. This boiler is the energy source for the water flow and radiation system. If the water flow and radiation systems are not adequate for the Btu/h heat loss of the building, installing the Electro-Boiler with WarmFlo will not necessarily supply the comfort and heating for the building.
“Cold boiler” notation – do not, under any circumstances, simply jumper R and W and allow the temperature sensing controller to operate this Electro-Boiler as a “hot boiler”. Unless there is at least 2 GPM flow, the staging delays will cause temperature overshoot and could open up the manual reset limits.
In most dual heat installations this Electro-Boiler is plumbed in parallel with an existing oil, gas, or wood boiler. The Electro-Boiler is generally at the gas/oil outlet; but for wood, the Electro-Boiler must be on the inlet sides. The standby boiler cannot be operated as “hot boiler”. This will defeat the Electro-Boiler. Rewire as required, standby boiler is turned on from the brown wires (included with this boiler).
In the case of existing fossil fuel boiler conversions, it is assumed the expansion tank, valving, air bleeder, and circulation pump are in place, in good operating condition, and adequate for the overall system design.
In the case of new installation (floor radiant or baseboard), use standard hydronics water heating practices for the necessary expansion tank, air bleeder, valving, water pump, etc., sized for the total capacity of the system. The Electro-Boiler is turned on with an “R and W” closure from the zone system wiring.
208 Volt application – the elements within the standard product are rated a 240 volts. If operating at 208, there will be approximately 25% reduced capacity. The internal transformer may or may not adequately operate the control system from a 208 source. Voltage measurements between “R” and “C” must be 22VAC or greater when the system is in the complete operational mode. True 3-phase, 208-volt, models are available in the WarmFlo Series, models EB-WX-13-2 and EB-WX-27-2, contact factory.
In the case of under floor radiant heating, the basic components for the electric energy, heating system typically includes:
1. Electric boiler itself – covered by this manual.
2. Plumbing kit or piping material at the boiler itself – can be ordered as a kit. EB-PK-M – shown on plumbing installation drawing BX505.
3. Circulating pump – typically sized for head pressure and system flow requirement, typical
catalog number 5586/5582.
4. The under floor circulating tubes and manifolds – provided and manufactured by others, not
covered in this manual.
APPROVED TUBING/PIPING
When plumbing this boiler and its peripheral parts to the loop system, all plumbing parts and/or tubing must be sealed to prevent entrance of oxygen.
Use only tubing or polyethylene tubing with oxygen Diffusion Barrier.
10/27/2016 1 BI516
SYSTEM OR WATER FLOW In order to prevent hi-limiting and assure full 20+ years parts life, the piping system/basic
plumbing/circulator pump must be arranged to provide flow greater than minimum GPM shown in Table
1. If zoned system, this applies when the smallest zone is operating. NOTE: Since this is an automatic temperature sensing system, both sensors and the complete control
wiring are required before using or turning on this Electro-Boiler.
TABLE 1 - ELECTRO-BOILER SPECIFICATION 240 volts, 60 Hz, single phase
Model Btu/h Rating Amp Breakers Stages GPM EB-S/MX-10 34,000 10 kW 42A 60 2 2-4 EB-S/MX-15 51,000 15 kW 63A 60, 30 3 2-6 EB-S/MX-20 68,000 20 kW 83A 60, 60 4 2-8
MULTIPLE ZONES AND RADIANT TEMPERATURES Same water temperature all zones – in this case the system can be setup as one pump with the water
circulated through the boiler and directly to a manifold containing the various zone valves. Although this model series has a built-in outlet sensing and controller mechanism for staging the elements, also consider the next section, Zone Controller. If not using zone controller, the end switches of all of the zone valves are paralleled and directly control R and W to turn on the boiler.
Various water temperature requirements – if this is the case, a primary loop with mixing valve for the various zone temperature requirements is necessary. Injection pump techniques can also be used. However, usually injection pump techniques come with a controller which is designed to protect a gas boiler from cool water return. This is simply not needed and a duplication with the temperature sensing controller within this Electro-boiler and the injection pump controller will be of no benefit within the operating system. The zone valve/zone pump control strategy must be wired to provide the boiler “R and W” contact closure and the primary pump is connected to the boiler pump contacts. This assures the primary pump is active and running whenever the boiler is turned on via contact closure on “R and W”. At least one zone must be open before turning on the primary pump/Electro-Boiler. Do not design a system where the Electro-Boiler is supposed to operate as a “hot boiler” based upon its outlet sensor without the primary pump circulating water, minimum 2 GPM is required.
Electro Industries’ Zone Controllers – the Electro Industries’ zone controller priority zone has the ability to communicate with this TS Series boiler and it will automatically switch to a low mass high water temperature (150 or 180) during zone 1, priority switch on, operation. With this feature the TS boiler can automatically take care of two temperature requirements thus eliminating the need for the technique described in the paragraph above.
ZONE CONTROLLER
This Midsize Series boiler controls the electric elements based upon water temperature independent of flow; therefore, in theory, a staging zone controller is not required; however, there are three suggestions or reasons why a zone controller can simplify the installation and enhance overall performance.
1. Zone wiring and troubleshooting convenience – the addition of the zone board allows for easy
terminal block and point to point wiring for each zone thermostat and each zone valve. Also there are LED’s associated with the thermostat action and the zone valve action. This greatly simplifies wiring and future troubleshooting with a neat terminal block wiring arrangement and the onboard LED’s.
2. Prevents over control or false staging up and down when the temperature sensors are
attempting to regulate – since Electro Industries’ zone controllers have staging “smarts”, the addition of the zone controller will provide smoother boiler temperature control. The zone board has
10/27/2016 2 BI516
a dial switch for each zone and the installer selects one of four zone capacity sizes. When dialing in the size closest to the zone Btu/h capacity, the zone controller “smarts” only allows the appropriate boiler stage which can handle that capacity. Also this is additive if more than one zone calls at any one time.
3. Two temperature system with unbalanced zones – if the application includes zone one requiring
high temperature (fin tube, air handler, etc.) and the remaining zones are radiant floor low temperature, this zone controller will automatically raise the output of the high temperature zone. This is a priority arrangement, zone 1 holds off the other zones while the high temperature output is heating. If at the end of the high temperature zone there is a call on any of the low temperature zones (up to three plus slave 4), there will be a pump only function until the outlet temperature drops below the front panel dial setting.
ZONE CIRCULATORS
The EE-5051 switching relay can be used to interface line voltage pumps with the boiler R and W control terminals, see drawing BH008. However, when using zone controller EB-ZEA-1, these are not required.
ROOM THERMOSTAT PLACEMENT Fin tube radiation, fan coil, etc. – heat only wall t-stat, connected to operate zone valves (see previous
section) or for single zone the t-stat is connected directly to Electro-Boiler R and W. Floor radiant – comfort and proper space heating response is a direct relationship to the thermostat type
and the placement of the thermostat sensing bulb. Typically an under floor heating system can be broken down into three categories.
A. Energy storage, water tubing is under the concrete or within the
sand base – the controlling thermostat must have a remote bulb, and
this remote bulb must sense the concrete slab temperature (slab stat). Coordinated with the concrete pour, install a ¾” PVC, minimum bend radius of 7 inches, and locate at approximately center (vertical) of the concrete slab. The thermostat sensing bulb can later be pushed down this PVC conduit. If the slab is already poured without conduit for slab stat, use electronic remote sensing thermostat.
B. Floor covering, medium to high insulation – use slab stat as described in paragraph A above. C. Quick response, hydronic tubing just under the concrete surface, no flooring material over the
concrete – in this case, heated water can directly radiate into the room, a standard wall mount room
thermostat is adequate. Mount room thermostat on an inside wall similar to most heating systems.
TWO-TEMPERATURE OPERATION OR FEATURE
When using Electro’s zone controller in priority mode, the boiler system can automatically raise the outlet temperature with zone 1 calling. This is setup for default of 150° or pulling a jumper peg the high temperature value is 176°. See appropriate zone controller installation manual for details.
10/27/2016 3 BI516
MULTIPLE BOILERS
This boiler series now includes a method for automatically staging any number of parallel-plumbed boilers. Order plug-in relay EB-C-STG5.
The thermostat is connected only to the first boiler, when all stages are on for more than 5 minutes, this new plug-in relay module turns on the next boiler (R and W), and a second EB-C-STG5 could be used to turn on the third, etc.
Outdoor Reset Option
The EB-MX-** boiler comes equipped with an outdoor sensor (shipped loose). This sensor can be connected to the board to allow for outdoor reset function.
What is Outdoor Reset? Outdoor reset is where the Electro Boiler DT (desired water temperature) shifts up and down based on the outdoor temperature. The water temperature coming out of the boiler will be higher when it’s cold outside and lower when it’s warmer outside. The idea is to have the boiler work with the building heat loss to maintain a more even BTU delivery to the space. This helps with overall system efficiency as well.
NOTE: The EB-MS-** does not include an outdoor sensor. However, one can be ordered if outdoor reset is required.
Outdoor sensor part number: WFS25F
Outdoor Reset Activation
If it is determined that outdoor reset is required for this application, it needs to be activated.
Follow this sequence to activate outdoor reset:
Step 1: Power down the Electro-Boiler Step 2: Connect the outdoor sensor
Red wire to “RED” Black wire to “OT” White wire to “COM”
Step 3: Power up the Electro-Boiler
See: CONTROLLER SETUP for more information on outdoor reset.
10/27/2016 4 BI516
BOILER/PLUMBING KIT PLACEMENT
This model series is wall hung and the vessel must be vertical, drawing BX505. The plumbing kit items are located adjacent to the boiler housing itself as shown on drawing BX501 or
BX505. For future servicing, the unit itself must be installed 20” or more above the floor, the elements are
screwed in from the bottom.
INFORMATION/WATER FLOW CALCULATIONS
Water flow, GPM, can easily be calculated if the temperature rise across the electric boiler can be measured.
The formula below can only be used when the temperature rise is stable and the boiler is not hi-limiting. In other words, verify constant current draw and stable outlet temperatures for at least 15 minutes.
GPM =
Volts x Amps x 3.4
500 x Temp. rise
INSTALLATION REQUIREMENTS
1. All installation work must be performed by trained, qualified contractors or technicians. Electro
Industries, Inc., sponsors installation and service schools to assist the installer. Visit our Website at electromn.com for upcoming service schools.
WARNING
ALL ELECTRICAL WIRING MUST BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE AND LOCAL ELECTRIC CODES, ORDINANCES, AND REGULATIONS.
WARNING
OBSERVE ELECTRIC POLARITY AND WIRING COLORS. FAILURE TO OBSERVE COULD CAUSE ELECTRIC SHOCK AND/OR DAMAGE TO THE EQUIPMENT.
CAUTION
This unit can only be used for its intended design as described in this manual. Any internal wiring changes, modifications to the circuit board, modifications or bypass of any controls, or installation practices not according to the details of this manual will void the product warranty, the CSA/us certification label, and manufacturer product liability. Electro Industries, Inc., cannot be held responsible for field modifications, incorrect installations, and conditions which may bypass or compromise the built-in safety features and controls.
2. This installation manual and Electro-Boiler products relate only to the addition of the Electro-Boiler
to the hydronics system. The owner/ installer assumes all responsibility and/or liability associated with any needed installation of the gas/oil boiler, pump, plumbing, system design, hydronics systems or backup gas/oil boiler, etc. Any instructions or comments made within this manual (or factory phone assistance) relating to the gas/oil furnace are provided as comments of assistance and “helps” only.
CAUTION
Hazards or unsafe practices could result in property damage, product damage, severe personal injury and/or death.
10/27/2016 5 BI516
3. Remember, safety is the installer’s responsibility and the installer must know this product well
enough to instruct the end user on its safe use.
Safety is a matter of common sense - - a matter of thinking before acting. Professional installers have training and experienced practices for handling electrical, sheet metal, and material handling processes. Use them.
CLEARANCES
MINIMUM CLEARANCE FROM
COMBUSTIBLE SURFACES BACK 0 INCH 0 MM 0 INCH 0 MM LEFT 1 INCH 25 MM 12 INCHES 305 MM RIGHT 1 INCH 25 MM 6 INCHES 152 MM FRONT 1 INCH 25 MM 24 INCHES 610 MM TOP 1 INCH 25 MM 24 INCHES 610 MM BOTTOM REQUIRED CLEARANCE – 18 INCHES/457 MM
SUGGESTED MINIMUM
SERVICE CLEARANCE
10/27/2016 6 BI516
MECHANICAL INSTALLATION – UNDER-FLOOR RADIATION
CAUTION
Electro Industries Inc. requires the use of dielectric isolation between the boiler vessel supply and return piping when the boiler is plumbed using copper or any other dissimilar metal. Damage to the vessel caused by galvanic corrosion voids Electro Industries’ warranty.
Reference drawing BX505
1. With the typical radiant floor system, a dual heat backup boiler is uncommon. If a backup boiler is
required, please reference “Mechanical Installation – Dual Heat” section.
2. Unpack the Electro-Boiler, the safety relief and pipe fittings are packed within a small carton. The
safety relief is plumbed to the ¾” bushing as shown on BX505.
3. The Electro-Boiler must be positioned with the vessel vertical. The water IN/OUT ports must be at
the top. The unit will not function properly with the vessel in a horizontal position. NOTE: Mount at least 20 inches above the floor to allow element removal and service at the
bottom.
4. The plumbing components and plumbing layout shown on drawing BX505 have been very carefully
chosen and should be plumbed as shown. When following this diagram, the water fill procedure becomes very simple and almost guarantees the removal of all air or prevents air locking problems. Experienced hydronic heating installers may be able to eliminate some components but the inclusion of these components guarantees installation and initial operating success.
5. The vessel is factory constructed with an “air trap” chamber at the top of the vessel, connected to the
1” pipe and arrangement shown on BX505.
6. The key mechanical components required include: Expansion Tank – as a closed loop hydronic heating system, a minimal expansion tank is
required. This can be an air diaphragm tank as provided in the plumbing kit or a basic “empty” tank where air is compressed at the tank top.
Inlet Temperature Gauge – recommended to observe the operation of the system. Air Vent – install with the pressure relief valve as shown on drawing. Inline Air separator – this can be installed ahead of the pump with the expansion tank
moved to this point. However, the vessel designed air trap and the piping arrangement leading to the air bleeder.
Pressure Safety Valve – this is required and is furnished as a loose component with the
boiler unit itself. Failure to install the provided, 30 PSI, pressure relief valve as shown void warranty and the CSA product listing. During purging there is a requirement to bleed out the initial air within this 1” pipe leg by manually holding open the relief valve. Add the necessary pipe extension to the relief valve to prevent water damage on this unit or surrounding area.
Gate Valve/Drain Valve – these are for servicing and easy fill purposes. Circulating Pump – depending upon system lift and system loop resistance, the proper
circulating pump is required to guarantee the minimum GPM flow as specified in Specification Table.
Comment: Circulator pump can be in the outlet or inlet. Newer, higher quality pumps seem to work better in the “supply” line, plus pumping away from the expansion tank is preferred.
7. To ensure safe boiler operation adequate system pressure must be maintained. Some expansion tanks
may have an integral regulator and “port” for water source hookup.
8. Depending upon water conditions, determine whether water additives are necessary.
9. Purge and fill water system. Do not allow the electric element to come on until the system is purged
and you have verified proper water circulation. If the pump is needed, jumper the two orange wires in order to operate the pump directly from its own 120 volt source.
10. Purge each loop individually, one at a time.
11. Check for leaks.
10/27/2016 7 BI516
Loading...
+ 19 hidden pages