elco VGL4.460 DP, VGL4.610 DP Operating Instructions Manual

Page 1
en
Operating instructions
VGL4.460 DP VGL4.610 DP
it, nl.................................. 4200 1055 6301
en..................................... 4200 1055 6801
de, fr, it, nl, en................. 4200 1055 6101
......................................... 4201 1011 2500
For specialist installation engineers
Gas burners
......................................... 4200 1075 5001
09/2016 - Art. Nr. 4200 1055 6801A
Page 2
Overview
Contents
Overview Contents ................................................................................................................................................ 2
Operation Gas operation
Assembly Burner assembly .................................................................................................................................... 18
Commissioning Adjustment data gas operation, Adjustment data fuel oil operation ....................................................... 23
Important information ............................................................................................................................... 3
Burner description ................................................................................................................................. 3-4
Operation, Safety function....................................................................................................... 5
TCG 5xx control unit.............................................................................................................6-8
Terminal allocation chart, 230 Volt connection........................................................................ 9
Fuel oil operation
MB-VEF gas train, Fuel oil pump ........................................................................................................... 17
Gas manifold, Pressure take-off pipes ................................................................................................... 19
Checking the burner head...................................................................................................................... 20
Electrical connection, Selection of fuel................................................................................................... 21
Gas connection, Checks before commissioning ....................................................................................22
Air regulation, Gas valve adjustment, Fuel oil pressure regulation ........................................................ 24
Gas operation
Fuel oil operation
Setting the gas pressure switch, Setting the air pressure switc
Saving the adjustment values in the display ..........................................................................................35
Terminal allocation chart, Low voltage connections.............................................................. 10
Operation, Safety function.....................................................................................................11
TCH 2xx control unit.........................................................................................................12-14
Terminal allocation chart, 230 Volt connection...................................................................... 15
Terminal allocation chart, Low voltage connections.............................................................. 16
Pre-setting without flame..................................................................................................25-26
General advice before starting the burner............................................................................. 26
Setting the flame ..............................................................................................................27-29
Operating mode..................................................................................................................... 29
Pre-setting without flame..................................................................................................30-31
General advice before starting the burner............................................................................. 31
Setting the flame ..............................................................................................................32-34
Operating mode..................................................................................................................... 34
h ........................................................... 35
Servicing Maintenance......................................................................................................................................36-37
Gas operation
Troubleshooting................................................................................................................ 38-39
Fuel oil operation
Troubleshooting..................................................................................................................... 40
Fault diagnosis menu ............................................................................................................................. 41
Operating statistics menu..................................................................................................................41-42
09/2016 - Art. Nr. 4200 1055 6801A2
Page 3
en
Overview
Important information Burner description
Important information
VGL4.460 DP and VGL4.610 DP burners are designed for the low­pollutant combustion of natural gas and extra light fuel oil. The design and function of the burners meet standards EN 676 and EN 267. They are suitable for use with all heat generators complying with standard EN 303 or for use by hot air generators complying with standard DIN 4794 or DIN 30697 within their respective performance range. Any other type of application requires the approval of ELCO. Installation, start-up and maintenance must only be carried out by authorised
Burner description
VGL4.460 DP and VGL4.610 DP burners are two-stage fully automatic monoblock devices. The special design of the combustion head enables combustion with low levels of nitrogen oxide and increased output. Class 3 type-approval in accordance with EN676 (for gas) and with EN267 (for fuel oil) certifies that the lowest emission values have been achieved and means that the national environmental regulations have been met AT: KFA 1995, FAV 1997 CH: LRV 2005 DE: 1.BImSChV Emissions values may differ, depending on combustion chamber dimensions, combustion chamber load and the firing system (three-pass boilers, boilers with reverse firing). For specifying warranty values, the conditions for the measuring equipment, tolerances and humidity must be observed.
Packaging
The burner is supplied packaged in three boxes on a pallet:
- Burner housing with operating instructions, circuit diagram and spare parts list.
- Burner head with flange seal and securing screws.
- Compact gas train with integrated filter
specialists and all applicable guidelines and regulations must be complied with.
The following standards should be observed in order to ensure safe, environmentally sound and energy­efficient operation:
EN 226
Connection of fuel oil and forced­draught gas burners to a heat generator
EN 60335-1, -2-102
Specification for safety of household and similar electrical appliances, particular requirements for gas burning appliances
Gas lines
When installing the gas lines and trains, the general directives and guidelines, as well as the following national regulations, must be observed: CH: - G1 instruction text from SSIGE
- EKAS form no. 1942, liquefied gas directive, part 2
- Cantonal authority guidelines
(e.g. directives for the pilot valve)
DE: - DVGW-TVR/TRGI
Installation location
The burner must not be used in rooms with aggressive vapours (e.g. hair spray, tetrachloroethylene, carbon tetrachloride), high levels of dust or high air humidity (e.g. laundry rooms). If no connection to an air exhaust system is provided for the air supply, there must be a supply air inlet measuring: DE: up to 50 kW: 150 cm
per additional kW: : + 2.0 cm
CH: QF [kW] x 6= ...cm2; but at least
150 cm2. Variations may arise as a result of local regulations.
2
2
We accept no responsibility for damage arising from:
- inappropriate use.
- incorrect installation and/or repair on the part of the buyer or any third party, including the fitting of non-original parts.
Final delivery and instructions for use
The firing system fitter must supply the operator of the system with operating and maintenance instructions on or before final delivery. These instructions should be displayed in a prominent location at the point of installation of the heat generator, They should include the address and telephone number of the nearest customer service centre.
Notes for the operator
The system should be inspected by a specialist at least once a year. Depending on the type of installation, shorter maintenance intervals may be necessary! It is advisable to take out a maintenance contract to guarantee regular servicing.
09/2016 - Art. Nr. 4200 1055 6801A 3
Page 4
Overview
Burner description
A1 Control and safety unit
(Gas operation)
A1.1 Control and safety unit
(Fuel oil operation) A4 Display F6 Air pressure switch K1 Auxiliary motor supply relay M1 Blower motor T1 Igniter V1 Flame detection cell Y1 Fuel oil solenoid valve, 1 Y2 Fuel oil solenoid valve, 2nd stage Y10 Air flap servomotor 3 Adjusting screw for dimension Y 5 Housing 6 Plate hanging device
(Maintenance) 7 Combustion chamber pressure
take-off pipe 8 Burner tube 10 7-pin connector
10.1 4 pin connector
10.2 3-pin connector (auxiliary motor
supply relay) 18 Cover 19 Release knob 20 Hood securing screw 102 Fuel oil pump 113 Air intake box
st
stage
09/2016 - Art. Nr. 4200 1055 6801A4
Page 5
en
Compact train
Operation Gas operation
Operation Safety function
Description of the function
A pre-ventilation time of 24 seconds begins when first powering up, after a power cut or a lockout, after the gas supply has been cut or after a shutdown for 24 hours.
During the pre-ventilation time
- the air pressure is monitored
- a check is made for the presence of any abnormal flame signals.
At the end of the pre-ventilation time
- the ignition is switched on
- the main and safety solenoid valves are opened.
- burner start-up
Monitoring
The flame is monitored by an IRD cell.
Safety functions
- If no flame is produced when the burner is started (gas release), the burner is switched off at the end of the safety time which lasts no more than 3 seconds and the gas valve closes.
- If the flame is lost during operation, the gas supply is cut within a second. A new start-up sequence is activated. If the burner starts, the operating cycle starts running. Otherwise a lockout occurs.
- If there is an air failure during pre­ventilation or operation, a lockout occurs.
- If there is a gas failure, the burner either stops or will not start. As soon as sufficient gas pressure is available again, the burner restarts.
During the regulator shutdown
- The control thermostat interrupts the heat request.
- The gas valves close
- The flame goes out
- The blower motor stops
- The burner is ready for operation
Principle diagram
F4 Gas pressure switch F6 Air pressure switch Y12 Safety solenoid valve Y13 Main solenoid valve 1 Thermal shut-off valve (to be
installed by the installer) 104 Gas pressure regulator 106 Screen 108 Gas cut-out valve (to be installed
by the installer) 119pBrGas pressure measuring point at
the valve outlet
119.1Gas pressure measuring point
upstream of the valves
119.2Air pressure measuring point pF Furnace pressure pG Gas pressure at the head pL Air pressure
CH note
In accordance with SSIGE instructions, it is compulsory to install a gas safety valve (mark 1) in the pipe
DE Note
In compliance with the reference layout applicable to boiler rooms, sites with gas furnaces must be fitted with a thermal gas shut-off valve (1).
09/2016 - Art. Nr. 4200 1055 6801A 5
Page 6
Operation Gas operation
TCG 5xx control unit
The TCG 5xx control and safety unit controls and monitors the forced draught burner. The microprocessor-controlled program sequence ensures maximum stability of time periods, regardless of fluctuations in the power supply voltage or the ambient temperature. The automatic combustion control unit is designed to cope with brownouts. Whenever the supply voltage drops below its rated minimum level (< 185V), the control unit shuts down - even in the absence of a malfunction signal. The control unit switches itself back on again once the voltage has returned to normal levels (> 195V).
Pressing the unlocking button on the unit for
... 1 second ... the control unit to
... 2 seconds ... the control unit to
... 9 seconds ... the statistics to
… causes …
unlock.
lock.
be deleted
Locking and unlocking
The control unit can be locked (switched to malfunction mode) by pressing the unlocking button and unlocked (fault deleted), provided the unit is connected to the mains power supply.
Always switch off the power supply before installing or
removing the control unit. Do not attempt to open or carry out repairs on the control unit.
Moves the cursor upwards.
Moves the cursor downwards.
Increases the marked value.
Reduces the marked value.
Modifies/Confirms the value
shown.
Unlocks the control unit.
Red LED (flashes if a fault is
present).
Screen Description Screen Description
Awaiting the heat request from
the boiler
Air flap is forced open for pre-
ventilation.
Pre-ventilation
Closing the air flap to the ignition
position, pre-ignition
Opening the gas valve and
safety time
Flame is present, awaiting authorisation of regulation
Burner in operation. The lower
cell shows the strength of the
signal and the operating time of
the burner.
09/2016 - Art. Nr. 4200 1055 6801A6
Page 7
en
Operation Gas operation
TCG 5xx control unit
In parallel with its control and safety functions, the TCG5xx control unit allows the following to be set: (see illustration)
- the position of the air flap during ignition
- the position of the air flap at minimum pressure
- the position of the air flap at maximum pressure
• menu for setting the servomotor
• menu for storing the servomotor setting points in the display
The parameters for the control unit are set using the display and 5 keys. Operating values are shown in real time on the display.
Pressing the keys gives access to 9 menus:
• menu for setting industrial applications*
• menu for manual control*
• fault diagnosis menu
• operating statistics menu
• menu for setting/ adjusting the standard configurations*
• Parameter mode menu*
• Menu for adjusting screen contrast and brightness settings
* In these menus, it is
possible to adjust the control unit's standard configurations. These are pre-set in the factory. No modifications may be carried out on-site without prior consultation with ELCO. The access code and the setting setpoints for these menus are available on request.
09/2016 - Art. Nr. 4200 1055 6801A 7
Page 8
Operation Gas operation
TCG 5xx control unit
Operating cycle phases:
1: No voltage 2: Powering up, no heat request 3: Heating request 4: Opening an air flap, arrival in pre-
ventilation position
5: Checking the rest status of the air
pressure switch
6: Pre-ventilation: energizing of the
motor, checking the air pressure 7: Pre-ventilation 8: Air flap closes to the ignition position 9: Switching on the igniter, unauthorised
flame monitoring 10:Opening of the solenoid valve, flame
formation, safety time: max. 3 s. 11:Awaiting regulator release 12:Opening the air flap, until the
maximum output is reached
13:Closing of the air flap until the
minimum regulation position is reached
14:Operation at intermediate regulation
power
15:Operation at minimum regulation
power
16:Regulator shutdown, closure of the
air flap
17:Awaiting a new heating request
09/2016 - Art. Nr. 4200 1055 6801A8
Page 9
en
Operation
Earth
Flame check
Fault display
Air pressure switch
Igniter
Burner motor
Connector
Terminal
Terminal
Connector
Remote unlocking
L1 power supply
Solenoid valve
Control
thermostat
Heating request
Earth
Gas pressure switch
Terminal Description Connector Terminal Description Connector
1 Burner motor live 20 Minimum output thermostat li ve (T1) 2 Earth 21 Heating request signal (option T2) 3 Neutral 22 Flame monitoring signal 4 Solenoid valve live 23 Neutral 5 Neutral 24 Live 6 Earth 25 Air pressure switch signal 7 Solenoid valve live 26 Live 8 Live 27 Live
9 L i ve L1 28 Re mote unlocking si gnal 10 Earth 29 Neutral 11 Ne utral 30 S ignal fault live 12 Earth 31 Live 13 Earth 32 Gas pressure switch signal mini 14 Igniter live 33 Live
15 Earth 34
Gas pressure switch si gnal (if leakage test
present) 16 Neutral 17 Control thermostat live 18 Signal T7 19 Signal T8
8
5
34
T6/7/8
11
2
10
20
6
21
4
19
Gas operation
Terminal allocation chart 230 Volt connection
09/2016 - Art. Nr. 4200 1055 6801A 9
Page 10
Operation
Display-PC interface
Air servomotor
Gas operation
Terminal allocation chart Low voltage connections
Terminal Description Connector Terminal Description Connector
1 not used 2 not used 19 not used 3 not used 20 not used 4 not used 5 not used 22 not used 6 not used 23 not used 7 not used 24 not used 8 not used 25 not used
9 not used 26 not used 10 11 28 12 29 13 30
Display or PC interface
14 31 15 32 16 33 17
30
27 28 29
16
/
17
18 not used
21 not used
27 not used
Air servomotor
14
33 32
15
09/2016 - Art. Nr. 4200 1055 6801A10
Page 11
en
Operation Fuel oil operation
Operation Safety function
Starting the burner
- After heat is requested by the boiler regulator, the automatic combustion control unit starts the program sequence.
- The blower motor starts up, the ignition switches on.
- Pre-ventilation with air flap open (air flap is only closed when the burner is switched off).
- The solenoid valve 6 opens, pressure set by the partial load regulator 5.
- Flame formation.
- Ignition switches off.
Burner operation, regulation between partial load and full load
The burner operates with two nozzles and at one fuel oil pressure for partial load and one for full load. Fuel oil pressure is regulated by a pressure regulator in the pump.
If an increase in load is requested by the boiler regulator, the burner switches from partial load to full load after a delay of at least 13 seconds.
- Air flap 11 is moved to the full load position by the servomotor.
- When the position of the air flap can be adjusted, the solenoid valve for the second nozzles opens.
- The air flap continues to move to the full load position. The full load is in operation.
Safety function
A safety shutdown is triggered:
- if a flame signal is detected during pre­ventilation (unauthorised flame monitoring),
- if no flame is produced within 5 seconds (safety time) of the burner being started (fuel inlet authorisation),
- if no flame is produced after an unsuccessful restart attempt in the event of flame failure during operation.
A safety shutdown is indicated by the malfunction lamp lighting up. Once the cause of the malfunction has been rectified, it is possible to unlock the control unit by pressing the reset button.
Principle diagram
1 two-stage pump. 2 Fuel pressure regulator (partial
load and full load) 4Pump 5 Magnetic valve (partial load) 6 Magnetic valve (full load) 7 Nozzle line 8 Baffle plate 9Flame tube 10 Burner motor 11 Air flap 12 Air flap electric servomotor
09/2016 - Art. Nr. 4200 1055 6801A 11
Page 12
Operation Fuel oil operation
TCH 2xx control unit
The TCH 2xx fuel oil automatic combustion control unit controls and monitors the forced draught burner. The microprocessor-controlled program sequence ensures maximum stability of time periods, regardless of fluctuations in the power supply voltage or the ambient temperature. The automatic combustion control unit is designed to cope with brownouts. Whenever the supply voltage drops below its rated minimum level (< 185V), the control unit shuts down - even in the absence of a malfunction signal. The control unit switches itself back on again once the voltage has returned to normal levels (> 195V).
Pressing and holding the unlocking button for...
... 1 second ... the control unit to
... 2 seconds ... the control unit to
... 9 seconds ... the statistics to be
… causes …
unlock.
lock.
deleted
Locking and unlocking
The control unit can be locked using the release knob or unlocked as long as the unit is powered on.
Always switch off the power supply
before installing or removing the
control unit. Do not attempt to
open or carry out repairs on the
control unit.
Moves the cursor upwards.
Moves the cursor downwards.
Increases the marked value.
Modifies/Confirms the value shown.
Modifies/Confirms the value shown.
Unlocks the control unit.
Red LED (flashes if a fault is present).
Screen Description Screen Description
Awaiting the heat request from
the boiler
Air flap is forced open for pre-
ventilation.
Pre-ventilation and pre-ignition
Air flap closes to the ignition
position
Oil valve is opened, safety time
Flame is present, awaiting
authorisation of regulation
Burner in operation. The lower
cell shows the strength of the
signal and the operating time of
the burner.
09/2016 - Art. Nr. 4200 1055 6801A12
Page 13
en
Operation Fuel oil operation
TCH 2xx control unit
In parallel with its control and safety functions, the TCH2xx control unit allows the following to be set:
- the position of the air flap during ignition
- the position of the air flap during the 1st stage
- the position of the air flap during opening the stage 2 valve (for switching from 1st to 2nd stage)
- the position of the air flap during the 2nd stage
- the position of the air flap during closing the stage 2 valve (for switching from 2nd to 1st stage).
• menu for setting the servomotor
• menu for storing the servomotor setting points in the display
The parameters for the control unit are set using the display and 5 keys. Operating values are shown in real time on the display.
Pressing the keys gives access to 9 menus:
• menu for setting industrial applications*
• menu for manual control*
• fault diagnosis menu
• operating statistics menu
• menu for setting/ adjusting the standard configurations*
• Parameter mode menu*
• Menu for adjusting screen contrast and brightness settings
* In these menus, it is
possible to adjust the control unit's standard configurations. These are pre-set in the factory. No modifications may be carried out on-site without prior consultation with ELCO. The access code and the setting setpoints for these menus are available on request.
09/2016 - Art. Nr. 4200 1055 6801A 13
Page 14
Operation Fuel oil operation
TCH 2xx control unit
Operating cycle phases:
1: No voltage 2: Powering up, no heat request 3: Heating request 4: Air flap opens to the preventilation
position
5: Pre-ventilation: Switching on the
motor and the igniter
6: Closing the air flap, switching to
the ignition position 7: Unauthorised flame monitoring 8: Starting the burner: opening the
solenoid valve, flame formation,
safety time 9: Awaiting regulator release 10: Opening the air flap, until the
opening position of the 2
nd
stage
valve is reached 11: Operation in 2 12: Closing the air flap, until the
closing of the 2 13: Operation in 1st stage 14: Regulator shutdown, closure of
the air flap to 0° 15: Awaiting a new heating request
nd
stage
nd
stage valve
09/2016 - Art. Nr. 4200 1055 6801A14
Page 15
en
Operation
Earth
Pre-heater
Flame monitor
Fault display
Air pressure switch
Ignition
Burner motor
2nd stage solenoid valve
Connector
Terminal
Terminal
Connector
Remote unlocking
L1 power supply
1st stage solenoid valve
3rd stage solenoid valve
2nd stage thermostat
Heating request
Earth
Fuel pump pump unit
Fuel oil operation
Terminal allocation chart 230 Volt connection
Terminal Description Connector Terminal Description Connector
1 Burner motor live 2 Earth 22 Neutral 3 Neutral 23 Live
st
41 5 Earth 25 Not used 6 Neutral 26 Live 72nd stage solenoid valve live 8 Earth 28 Neutral
9 Neutral 29 Signal fault live 10 3 11 Earth 31 Preheater/release contact 12 Neutral 32 Earth 13 Igniter live 14 Earth 34 Live L1 15 Neutral 35 Earth 16 2 17 Signal T7 37 Earth 18 Signal T8 38 Earth 19 1 20 Heating request signal (option T2) 40 Earth
stage solenoid valve live
rd
stage solenoid valve live
nd
stage thermostat phase (T6)
st
stage thermostat live (T1)
4
1
2
3
5
T6/7/8
19
21 Flame monitoring signal
24 Not used
27 Remote unlocking signal
30 Live
33 Neutral
36 Neutral
39 Pump unit live
41 Neutral
11
10 20 21
25
6
35
09/2016 - Art. Nr. 4200 1055 6801A 15
Page 16
Operation
Display-PC interface
Air flap servomotor
Connector
Terminal
Terminal
Connector
Fuel oil operation
Terminal allocation chart Low voltage connections
Terminal Description Connector Terminal Description Connector
1 Not used
2 Not used 19 Not used
3 Not used 20 Not used
4 Not used
5 Not used 22 Not used
6 Not used 23
7 Not used 24
8 Not used 25
9 Not used 26 10 11 28 12 13
Display-PC interface
14 15 16 17
17
27 28 29
16
18 Not used
21 Not used
Air flap servomotor
27
31
30
15
09/2016 - Art. Nr. 4200 1055 6801A16
Page 17
en
Operation
MB-VEF gas train Fuel oil pump
1 Electrical connection of solenoid
valves (DIN 43650)
2 Electrical connection of the
gas pressure switch (DIN 43650) 3 Gas pressure switch 4 Inlet flange 5 Pressure measuring nipple
R1/8, upstream of filter (option) 6 Filter (under the cover) 7 Connection for furnace pressure
release pipe pF, R1/8 8 Adjusting screw for V ratio 9 Adjusting screw for zero point
offset N 10 Connection for pressure pipe pL,
R1/8 11 Connection for pressure pipe pBr,
R1/8 12 Outlet flange 13 Pressure take-off pipe pBr
The MBVEF compact gas valve assembly is a combination of filter, gas/ air ratio regulator, valves and a pressure switch:
- Screen with 0.8mm mesh
- GWA5 pressure switch
- Servo-pressure control part with adjustable ratio V, correction of the zero point offset N and furnace pressure connection.
- V1 and V2 fast-opening and closing solenoid valves
Technical data
Input pressure 360 mbar max. Ambient temperature -15 to +70°C Voltage 230 V/ 50 Hz Max. Absorbed output 50 VA Protection rating IP 54
The pump is a gear pump. It must be connected as a two-line pump via a bleed filter. For the connection of the fuel oil tank and the bleed filter, it is better to use the single line option. An inta k e fil ter and one oil pressure regulator are integrated in the pump. Pressure gauges for pressure measurements 4 and negative pressure measurements 5 must be connected before the equipment is commissioned.
1 Vacuum connection G 1/4 2 Return connection G 1/4
3.1 Pump tube connection / 1st stage nozzle line G1/8
3.2 Pump tube connection / 2nd stage nozzle line G 1/8
4,7 Pressure gauge connection 5 Vacuum gauge connection 6 Pressure setting Y1 Solenoid valve, 1st stage Y2 Solenoid valve, 2nd stage
09/2016 - Art. Nr. 4200 1055 6801A 17
Page 18
Ø a Ø b c d
190-240 200-270 M10 45°
Assembly
Burner assembly
Preparing the boiler front
• Prepare the burner mounting plate/ boiler door in accordance with the diagram.
• Establish the internal diameter a of 190-240 mm.
• To mount the burner head bracket, drill four M10 holes (drill diameter 200 to 270 mm) as shown in the diagram opposite.
Burner head assembly
• Screw the bolts into the burner fixing plate/boiler door and position the insulation material. For a drill hole of < 270 mm, elongated slots should be cut to the required dimensions.
• Remove the combustion components from the head
• Attach the burner head with 4 nuts (ref. 4). At this point, check that the gas connection flange is correctly positioned (on the left or right).
Fitting the burner body
• Remove the cover (2 screws W).
• Do not damage the cells.
• Unscrew the two screws Z on the burner body completely.
• Bring the burner body into contact after having swivelled it at least 15° to the left.
• Engage the two screws Z on the body into the two lugs provided.
• Tighten the 2 screws.
On boilers with reverse firing, minimum flame tube insertion depth A should be observed as per the boiler manufacturer's instructions.
For assembly in the position with
the volute facing upwards, unclip the display, turn it over 180°, and refit it.
Burner tube installation depth and brickwork surround
Exhaust gas evacuation system
To avoid unpleasant noise emissions, right-angled connectors should not be used on the flue gas side of the boiler.
09/2016 - Art. Nr. 4200 1055 6801A18
Page 19
en
Assembly
Gas manifold Pressure take-off pipes
Gas train assembly
• Check the correct position of the
O-ring B in the gas connecting flange C.
• Secure the gas train on the burner head so that the gas train coils are in the upper vertical position.
• Pay attention to the direction of circulation.
• Connect the power cable to the gas train.
Connecting pressure take-off pipes pF and pL
• Connect the furnace pressure take-off
pL on the burner body and the union pL on the gas train using the flexible
tube pL (blue), shorten the tube depending on the assembly scenario.
• Connect the furnace pressure take-off
pF on the burner body and the union pF on the gas train using the flexible
tube pF (grey), shorten the tube depending on the assembly scenario.
• Manually screw in the unions (max. 5 Nm) and check tightness.
09/2016 - Art. Nr. 4200 1055 6801A 19
Page 20
Assembly
CDE
VGL4.460/610 DP
633
Checking the burner head
Checking the burner head
• Check the adjustment settings of the ignition electrode as per the diagrams.
Fitting the combustion components
• Check that the O-Ring J1 is in the correct position in the gas elbow.
• Insert the combustion components into the head, tighten the mounting screw X using an Allen key, then tighten the lock nut using an open­ended spanner.
• Thread the ignition cables ZK into the grommet S.
• Remove the cover.
09/2016 - Art. Nr. 4200 1055 6801A20
Page 21
en
Assembly
Electrical connection Selection of fuel
All electrical installation and connection work must only be carried out by a suitably qualified electrician.
The applicable guidelines and directives must be observed, as well as the electrical circuit diagram supplied with the burner!
Electrical connection
• Check to ensure that the power supply is as specified (230V, 50 Hz single phase with neutral and earth)
Boiler fuse: 6.3 A
Electrical connection
It must be possible to disconnect the burner from the mains using an omnipolar shutdown device complying with the standards in force. The burner and heat generator (boiler) are connected by a 4-pin connector (no. 2) and a 7-pin connector (no. 1).
The diameter of the cables connected to these connectors must be between 8.3 and 11 mm.
The burner motor has its own separate power supply (no. 3).
Fuse on the motor circuit: 6 A gM
Connecting the gas train
Connect the gas train to the plugs on the burner (black to black, grey to grey).
Selection of fuel
Disconnect the power supply before changing the fuel. The selection of fuel occurs by connecting the cable (no. 4):
- for the gas operation on the unit
TCG5
- for the fuel oil operation on the unit
TCH2
In gas operation, it’s essential to remove the pump coupling (see picture).
This one must be stored in a visible place so it can be repositioned when liquid fuel is to be used.
09/2016 - Art. Nr. 4200 1055 6801A 21
Page 22
Assembly
Gas connection Checks before commissioning
General regulations applying to the gas connection
• The gas train must only be connected to the gas mains by a recognised specialist.
• The cross-section of the gas line should be of a size designed to guarantee that the gas flow pressure does not drop below the specified level.
• A manual shut-off valve (not supplied) must be fitted upstream of the gas train.
• In Germany, a thermally triggered shut-off valve (to be installed by the customer side) must be fitted as
Checks before commissioning
The following must be checked before initial commissioning:
• That the burner is assembled in accordance with the instructions given here.
• That the burner is pre-set in accordance with the values in the adjustment table.
• Setting the combustion components.
• The heat generator must be ready for operation, and the operating regulations for the heat generator must be observed.
• All electrical connections must be correct.
• The heat generator and heating
specified by the draft combustion
ordinance. It is the responsibility of the fitter or his representative to obtain approval for the system at the same time as the burner is commissioned. Only the fitter or his representative can guarantee that the system meets applicable standards and regulations. The fitter should be in possession of the corresponding official permit, and should carry out the corresponding sealing tests and purge the system of air.
system must be filled with water and
the circulating pumps must be in
operation.
• The temperature regulator, pressure
regulator, low water detectors and any
other safety or limiting devices that
might be fitted must be connected and
operational.
• The exhaust gas duct must be
unobstructed and the secondary air
system, if available, must be
operational.
• An adequate supply of fresh air must
be guaranteed.
• The heat request must be available.
• Sufficient gas pressure must be
available.
• The fuel supply lines must be assembled correctly, checked for leaks and bled.
• A standard-compliant measuring point must be available, the exhaust gas duct up to the measuring point must be free of leaks to prevent anomalies in the measurement results.
09/2016 - Art. Nr. 4200 1055 6801A22
Page 23
en
Commissioning
Mi ni. Maxi. Igni tion Mini. Maxi. G20 G25 G20 G25 G20 G25
113 290 0 3,1
0034,5
1,3 / 0 1,5 / -0,1 1,28 / 0,1 1,4 / 0,1 1 / 0,1 1,2 / 0
105 338 0 3, 5 0 0 45
1,3 / -0,35 1,4 / -0,1 1,25 / 0,1 1,4 / 0,1 0,95 / 0,1 1,2 / 0,1 101 383 5 3,8 0 0 90 1,3 / -0,35 1,5 / -0,1 1,31 / 0,1 1,4 / 0,1 0,9 / 0,1 1,2 / 0,2 164 385 15 3,4
15 10 40
1,25 / 0 1,75 / 0 1,25 / 0 1,5 / 0 1 / 0 -
218 460 20 4,3 15 15 50
1,5 / -0,5 2 / -1 1,5 / 0 1,75 / -0,5 1,2 / 0 -
199 512 30 4,8 15 15 90 1,5 / -0,5 2 / -1 1,5 / 0 1,75 / -0,5 1,2 / 0 -
VGL4.610
DP
Ai r f l a p setting
Dimension
Y
( mm)
Burn er
power
kW
Furnace
pressure
pF
(mbar)
Gas valve setti ng
Screw V / Screw N
MB- VEF412 MB- VEF407MB- V E F 4 2 0
VGL4.460
DP
1. stage 2. stage 1. stage 2. stage 1. stage 2. stage 1. stage 2. stage
205 300 25,4 17,3 4,00 2,00 16 16 0 15 20 30 42
210 340 28,7 17, 8 4,00 2,50 16 16 0 15 20 35 56
215 370 31,3 18, 2 4,00 3,00 16,0 16 5 15 20 53 90
190,4 290, 6 16,1 24, 5 4,00 2,00 15 15 0 15 16 25 30
225,5 390, 8 19,0 33, 0 4,50 3,00 15 15 0 15 20 38 50
260,6 521, 1 22,0 43, 9 5,00 5,50 12 12,0 25 15 20 55 90
St age
changeover
Igniti on
Nozzle 60°S
Gph (Danfoss)
kWBurner
Bold : Del iver y s etting; 1kg f uel- oil at 10°C = 11.86kWh
VGL4.460DP
VGL4.610DP
Fuel-oil flow
kg/h
bar
mm
Air flap position
in °
1. stage 2. stage
Adjustment data gas operation Adjustment data fuel oil operation
Burner power
The adjustment values above are guide values and facilitate commissioning. The factory settings are in bold set against a grey background The final settings are essential in ensuring that the burner functions as well as possible
Pump pressure
Setting the burner
When both fuels are available, or failing that, apply the following principle:
1. Set the gaseous fuel to the boiler nominal output
2. then set the liquid fuel. The nominal fuel oil throughput is subject to the nominal air flow defined in the fuel oil setting (choice of nozzles and adjusting the pump pressure).
Dimensi on
Y
Setting the gas pressure switch
• Remove the transparent cover.
• Provisionally set to 15 mbar.
Setting the air pressure switch
• Remove the transparent cover.
• Provisionally set to 1 mbar.
09/2016 - Art. Nr. 4200 1055 6801A 23
Page 24
Commissioning
Air regulation Gas valve adjustment Fuel oil pressure regulation
Air regulation
Combustion air is regulated at two points:
• on the pressure side, using the gap between the turbulator and the burner tube.
• on the vacuum side, by the air flap driven by servomotor Y10.
The regulation of air in the burner head affects not only the air flow but also the mixing zone and the air pressure in the burner tube. Turning screw A
- right: more air
- left: less air
• Adjust dimension Y in accordance with
the settings table.
Air regulation by air flap
Air is regulated on the vacuum side by an air flap. This is driven by servomotor
Y10.
Gas valve adjustment
V Setting the maximum power
N Setting the minimum power
- For more CO2 turn upwards on the scale.
- For less CO scale.
turn downwards on the
2
1 Vacuum connection G 1/4 2 Return connection G 1/4
3.1 Pump tube connection / 1st stage nozzle line G1/8
3.2 Pump tube connection / 2nd stage nozzle line G 1/8
4,7 Pressure gauge connection 5 Vacuum gauge connection 6 Pressure setting Y1 Solenoid valve, 1st stage Y2 Solenoid valve, 2nd stage
Fuel oil pressure regulation
The fuel oil pressure is adjusted using fuel oil pressure regulator 6 for the 1st stage and for the 2nd stage. To check the pressure, connect a R1/8" pressure gauge to connector 4. Turn
- right: to increase the pressure
- left: to reduce the pressure
Checking the vacuum pressure
The vacuum meter for checking negative pressure must be connected to point 5, R1/8". Maximum authorised vacuum: 0.4 bar. At higher vacuum pres­sures, the fuel oil gasifies, which causes scraping noises in the pump and risks damaging it.
09/2016 - Art. Nr. 4200 1055 6801A24
Page 25
en
Commissioning Gas operation
Pre-setting without flame
Setting is carried out in 2 phases:
- pre-adjustment without flame
- setting the flame, to fine tune the settings based on the combustion results
When the burner is switched on, the control unit displays the screen below.
• For the next step, press any button.
The overall view of the menus is displayed, and the air flap positions settings menu is selected.
• Open the settings menu by pressing the key.
Important
At this point, no setting position for the servomotor has been defined, therefore the burner cannot be started under these conditions.
The control unit then opens the settings mode. The screen displays the factory pre­settings for the different positions of the air flap (here for example: for a VGL4.460 DP).
The following positions for the air flap are presented:
- ignition position (when the menu is opened, the curser goes to this position)
- the position of the air flap at minimum pressure
- the position of the air flap at maximum pressure
You must now enter the access code (see the label on the back of the display)
• Increase or decrease the value in increments by repeatedly pressing or
.
• When the first figure has been set, move the cursor to the right by pressing .
• Repeat the operation until you reach the last figure.
• Confirm the access code by pressing
09/2016 - Art. Nr. 4200 1055 6801A 25
Modifying a settings value for the servomotor position:
- To modify the value of a position, move the cursor to the corresponding location with the or key.
- Select the value to be modified using the key, the selected value will flash.
- Increase or decrease the value in increments of 0.1° by repeatedly pressing or . For large modifications, press and hold the or key the value will scroll quickly up or down.
- Confirm the new value using the key. The value stops flashing.
Page 26
Commissioning Gas operation
Pre-setting without flame General advice before starting the burner
End of presetting menu without flame
When all the positions of the servomotor have been determined according to the required settings, it is then possible to move on to the next section for commissioning - "Setting the flame".
To do this, place the cursor in the lower part of the screen on the symbol and confirm by pressing the key.
If it is necessary to quit the menu without saving the pre-settings, position the cursor on the symbol and confirm with the key.
Optimising combustion values
Optimum combustion values can be achieved by adjusting the position of the turbulator (dimension Y) if necessary. Doing this can have an effect on starting characteristics, pulsation and combustion values. Any reduction in dimension Y increases the CO However, starting characteristics become harsher. Compensate for the change in airflow if necessary by adjusting the air flap position.
Precautions: To avoid condensation, observe the minimum required flue gas temperature specified by the boiler manufacturer and comply with the requirements for flue gas ducts.
Risk of deflagration Continuously check CO, CO
and soot emissions when adjusting. Optimise combustion values if CO is present. The CO level must not exceed 50 ppm.
value.
2
2
Function check
Flame monitoring must be checked for safety as part of initial commissioning and also after servicing or if the system has been out of operation for any significant period of time.
- Starting attempt with gas valve closed: once the safety time has elapsed, the control and safety unit should indicate a lack of gas or switch to malfunction mode.
- Starting with the air pressure switch closed: after an 8-second test period, the burner switches to malfunction mode.
- Starting attempt with air pressure switch open: after a 60-second waiting period, the control and safety unit locks.
- Starting attempt with brief opening of the air pressure switch during pre­ventilation: the control and safety unit restarts the pre-ventilation programme (air pressure detected again within 60 seconds) ; otherwise a lockout occurs.
09/2016 - Art. Nr. 4200 1055 6801A26
Page 27
en
Commissioning Gas operation
Setting the flame
- If the boiler heating request is not present, the boiler
remains on standby.
In this case, it is still possible to return to the previous setting menu "Pre-setting without flame". To do this, position the cursor on the symbol and confirm with the key.
- If a boiler heating request is present (T1-T2 contact closed), the burner starts.
The air flap is opened to move to the pre-ventilation position.
Air pressure switch test
The air flap switches to the ignition/pre-ignition position.
The fuel valve opens.
Awaiting flame signal
If no flame is detected at the end of the safety time, the
control unit switches to malfunction mode.
Pre-ventilation
If the flame is detected
Flame stabilisation
The control unit awaits the regulation authorisation.
09/2016 - Art. Nr. 4200 1055 6801A 27
Page 28
Commissioning Gas operation
Setting the flame
Setting the minimum pressure
If the flame has been detected and stabilised, the control unit sets the burner to minimum power as soon as it receives the regulation authorisation.
- Check the combustion values (CO, CO (see page 24).
- Read the flame current value.
- Read the gas flow rate on the gas counter.
Modification of the air flow via the "manual output control"
The "manual output control" function allows the burner output to be modified. To do this, position the cursor on the corresponding line on the display and confirm with the key. It is then possible to adjust the burner output upwards or downwards using the , keys.
The servomotor reacts in real time. This is why the combustion values must be continuously
monitored.
, soot test). If necessary, adjust screw N on the valve
2
Setting the maximum output
Slowly increase the burner to the maximum output using the "manual power control" function. At this point, adjust the gas flow using the regulator V on the gas train. The preset limit values for the minimum output and the maximum output cannot be exceeded. If necessary, exit the "manual output control" function again using the key and modify the limit value for the maximum or minimum output.
Definitive limitation of the maximum output position
Limit the maximum opening of the air flap according to the position determined for the maximum output. In this example, the new position determined for the maximum output is below the value set manually. Using the "manual output control" function, it is now possible to reduce the burner output, but this cannot be set above the new maximum position, which here is 50°.
Definitive limitation of the minimum output position
Using the "manual output control" function, reduce the burner output to the minimum output. If necessary, limit the minimum output position, in the same way as for the maximum output.
Specific function: ignition checking
If the ignition position has been modified, it is possible to carry out a new burner start-up to check the new ignition position, without having to quit the settings menu. To do this, after modifying the ignition position, position the cursor on the symbol, and initiate the new start-up using the key.
09/2016 - Art. Nr. 4200 1055 6801A28
Page 29
en
Commissioning Gas operation
Setting the flame Operating mode
Closing the "Setting the flame" menu
The burner setting is now complete. If necessary, it is possible to again correct each of the settings values. To do this, position the cursor on the value to be modified, using the or key.
Otherwise, at any point, there are 3 possible ways of closing the "Setting the flame" menu, as follows:
- either restart the burner setting procedure, passing through the presetting phase (without entering a password). To do this, position the cursor on the symbol and confirm with the key. All the settings values already saved therefore remain available. This is essential for testing a new ignition position.
- or: Save the fixed values and end the setting procedure. To do this, position the cursor on the symbol and confirm with the key . The burner is then ready to operate and can now be controlled by the boiler regulation.
- or: Quit the settings menu without reaching the end of the setting procedure. To do this, position the cursor on the symbol and confirm with the key . All the servomotor positions saved up to this point are recovered by calling up the settings menu again.
Operating mode - Display of the operating status, the flame signal and the operating time
After setting of the burner has been completed, it switches to operating mode.
The burner's instantaneous operating status (operation at minimum or maximum power) is shown by the cursor.
The lower cell shows the intensity of the signal. The display range is from 0 µA to 13 µA. A good quality signal is above 8µA. The following limit values are valid:
• When checking an unwanted flame: the signal must be < 0.7µA
• During the safety time: the signal must be > 1.0µA
• During operation: the signal must be > 8µA
The cell at the bottom right displays the current operating time of the burner.
09/2016 - Art. Nr. 4200 1055 6801A 29
Page 30
Commissioning Fuel oil operation
Pre-setting without flame
Setting is carried out in 2 phases:
- pre-adjustment without flame
- setting the flame, to fine tune the settings based on the combustion results
When the burner is switched on, the control unit displays the screen below.
• Press any button and the following screen will appear:
The overall view of the menus is displayed, and the air flap positions settings menu is selected.
• Open the settings menu by pressing the button .
Important
At this point, no setting position for the servomotor has been defined, therefore the burner cannot be started under these conditions.
The control unit then opens the settings mode. The screen displays the factory pre­settings for the different positions of the air flap (here for example: for a VGL 4.460 DP).
The following positions for the air flap are presented:
- ignition position (when the menu is opened, the curser goes to this position)
- position of the air flap during the 1st stage
- position of the air flap when the 2nd stage fuel oil valve is opened
- position of the air flap during the 2nd stage
You must now enter the access code (see the label on the back of the display)
• Increase or decrease the value in increments by rep eat edl y p res sin g o r
.
• When the first figure has been set, move the cursor to the right by pressing .
• Repeat the operation until you reach the last figure.
• Confirm the access code by pressing .
09/2016 - Art. Nr. 4200 1055 6801A30
Modifying a settings value for the servomotor position:
- To modify the value of a position, move the cursor to the corresponding location with the button or .
- Select the value to be modified using the button , the selected value will flash.
- Increase or decrease the value in increments of 0.1° by repeatedly pressing or . For large modifications, press and hold the or button, the value will scroll quickly up or down.
- Confirm the new value using the button . The value stops flashing.
N.B.:
It is possible to set different positions within a large range of values. However, for safety reasons, the control unit enforces a minimum interval of 2° between the different positions (except between the ignition position and the 1st stage).
Page 31
en
Commissioning
Fuel oil operation
Pre-setting without flame General advice before starting the burner
End of settings menu without flame
When all the positions of the servomotor have been determined according to the required settings, it is then possible to move on to the next section for commissioning - "Setting the flame".
To do this, place the cursor in the lower part of the screen on the symbol and confirm by pressing the button .
If it is necessary to quit the menu without saving the pre-settings, position the cursor on the symbol and confirm with the button .
Preparing the burner start-up
Before starting the burner, draw fuel oil in using a hand pump until the filter is completely filled. Then start the burner by switching on the boiler regulator. Open the bleed screw on the oil filter to allow the oil line to bleed fully during the pre-ventilation phase. The negative pressure must not fall below 0.4 bar. Close the bleed screw when the filter is completely filled with fuel oil and fuel oil is flowing out without bubbles.
Optimising combustion values
Optimum combustion values can be achieved by adjusting the position of the baffle plate (dimension Y) if necessary. Doing this can have an effect on starting characteristics, pulsation and combustion values. Any reduction in dimension Y increases the CO However, starting characteristics become harsher. Compensate for the change in airflow if necessary by adjusting the air flap position.
Precautions: To avoid condensation, observe the minimum required flue gas temperature specified by the boiler manufacturer and comply with the requirements for flue gas ducts.
value.
2
Risk of air blast! Continuously check CO, CO soot emissions when adjusting. Optimise combustion values if CO is present. The CO level must not exceed 50 ppm.
Function check
Flame monitoring must be checked for safety as part of initial commissioning and also after servicing or if the system has been out of operation for any significant period of time.
- Start attempt with the flame detection
cell obscured: at the end of the safety time, the control unit must switch to malfunction mode!
- Start-up with the flame detection cell lit
up: the automatic combustion control unit must switch to malfunction mode after 10 seconds of pre-ventilation.
- Normal start; if the burner is in
operation, cover the flame detection cell: the automatic combustion control unit must switch to malfunction mode after a restart and the end of the safety time
and
2
If dimension Y needs to be corrected again when the 2 will be necessary to check the adjustment values for the 1
nd
stage is adjusted, it
st
stage.
09/2016 - Art. Nr. 4200 1055 6801A 31
Page 32
Commissioning Fuel oil operation
Setting the flame
- If the boiler heating request is not present, the
boiler remains on standby.
In this case, it is still possible to return to the previous setting menu "Pre-setting without flame". To do this, position the cursor on the symbol and confirm with the button .
- If a boiler heating request is present (T1-T2 contact closed), the burner starts.
The air flap is opened to move to the pre-ventilation position.
The air flap switches to the ignition position.
The fuel valve opens.
Awaiting flame signal
If no flame is detected at the end of the safety time, the
control unit switches to malfunction mode.
Pre-ventilation and pre­ignition
Flame detected
Flame stabilisation
The control unit awaits the regulation authorisation.
09/2016 - Art. Nr. 4200 1055 6801A32
Page 33
en
Commissioning Fuel oil operation
Setting the flame
Setting the 1st stage
If the flame has been detected and stabilised, the control unit sets the burner to the 1st stage as soon as it receives the regulation authorisation.
- Adjust the fuel oil pressure for the 1st stage depending on the required output, using the
To do this, modify the position of the servomotor in 1st stage. Proceed as described on page Tableau , page 30, in the paragraph "Modifying the value of a servomotor position setting"
- Precautions: when modifying the setting value, the servomotor will move in real time. As a
Specific function: ignition checking If the ignition position has been modified, it is possible to carry out a new burner start-up to check the new ignition position, without having to quit the settings menu. To do this, after modifying the ignition position, position the cursor on the symbol , and initiate the new start-up using the button .
regulator 6 on the pump. Monitor the combustion values continuously as you do so (CO, CO2, soot test). If necessary, adjust the dimension Y and/or adapt the airflow.
consequence, the combustion values must be constantly checked.
Setting the opening position of the 2nd stage fuel oil valve
After the 1st stage is set, it is possible to set the opening value for the 2nd stage fuel oil valve. Proceed as described in the paragraph "Modifying the value of a servomotor position
setting"
- Precautions: in this case the servomotor does not move immediately, but first remains in the 1st stage position (the actual position of the servomotor is always displayed in the lower part of the display). The 2nd stage valve also remains closed. Firstly it is possible to modify the position of the 2nd stage air flap.
Setting the 2nd stage
To set the position of the air flap in the 2nd stage, position the cursor on the corresponding line on the display using the button . If necessary, modify the setting value. Proceed as described in the paragraph "Modifying the value of a servomotor position setting".
- To make the burner actually switch to the 2nd stage, press the button again. The servomotor will then move the air flap to the set position. At the same time, the 2nd stage fuel oil valve will open, as soon as the opening position set for the servomotor is passed. Continuously check the combustion values (CO, CO2, soot test). If necessary, adjust the dimension Y and/or adapt the airflow.
To do this, modify the position of the servomotor in the 2nd stage. Proceed as described on page Tableau , page 30, in the paragraph "Modifying the value of a servomotor position setting"
- Precautions: when modifying the setting value, the servomotor will move in real time. As a consequence, the combustion values must be constantly checked.
Specific function: position the opening and closing of the 2nd stage fuel oil valve differently
The control unit has the possibility of setting the opening of the 2nd stage valve, when the 1st stage changes to the 2nd stage, at a different position to that for closing when the 2nd stage drops to the 1st stage.
- To do this, as described before, first set the opening position of the 2nd stage fuel oil valve.
- Lastly position the cursor on the symbol and confirm with the button . The selected symbol will change like this one .
- Using the button , position the cursor on the setting value of the 2nd stage fuel oil valve, and fix the new closure position, as described in the paragraph "Modifying the value of a servomotor position setting".
09/2016 - Art. Nr. 4200 1055 6801A 33
Page 34
Commissioning Fuel oil operation
Setting the flame Operating mode
Closing the "Setting the flame" menu
The burner setting is now complete. If necessary, it is possible to again correct each of the settings values. To do this, position the cursor on the value to be modified, using the button or .
Otherwise, at all times, the following possible ways of closing the "Setting the flame" menu are available:
- Returning to the burner settings with passing through the pre-setting phase (without entering a
- Saving the fixed values and ending the setting procedure. To do this, position the cursor on the
password). To do this, position the cursor on the symbol and confirm with the button . All the settings values already saved therefore remain available.
symbol and confirm with the button . The burner is then ready to operate and can now be controlled by the boiler regulation.
- Quitting the settings menu without reaching the end of the setting procedure. To do this, position the cursor on the symbol and confirm with the button . All the servomotor positions saved up to this point are recovered by calling up the settings menu again.
Operating mode - Display of the operating status, the flame signal and the operating time
After having completed the setting of the burner, it switches to operating mode.
The current operation of the burner (Operation in 1st or 2nd stage) is indicated by the light bar.
The lower cell shows the intensity of the signal. The display range is from 0 µA to 13 µA. A good quality signal is above 3µA. The following limit values are valid:
• When checking an unwanted flame: the signal must be < 0.7µA
• During the safety time: the signal must be > 1.3µA
• During operation: the signal must be > 1.1µA
The cell at the bottom right displays the current operating time of the burner.
09/2016 - Art. Nr. 4200 1055 6801A34
Page 35
en
Commissioning
Setting the gas pressure switch Setting the air pressure switch Saving the adjustment values in the display
Setting the gas pressure switch
• To set the switch-off pressure: remove the cover from the gas pressure switch.
• Install a gas pressure pBr measuring instrument.
• Start the burner. Switching to maximum power.
• Reduce the pressure upstream of the gas train by gradually closing the manual valve, until
- the gas pressure pBr upstream of
the gas train drops
- the stability of the flame is reduced
- the CO level increases
- or the flame signal deteriorates
considerably
Setting the air pressure switch
• Install a pressure measuring device. To do this, install a T union in the air tube.
• Set the burner to its maximum operating power.
• Set the switch-off point to approximately 15% below the switch­off pressure read.
• Turn the dial clockwise until the gas pressure switch shuts down the burner.
• Continue turning the dial clockwise to set the gas pressure switch to 10% above the shutdown value determined above.
Checking the switch-off pressure
• Open the manual shut-off valve
• Start the burner
• Close the manual shut-off valve
The gas failure procedure should start without the control unit locking.
Saving the adjustment values in the display
If the burner setting procedure has been successfully completed, the servomotor positions for all the operating states will be fixed in the control unit. A back-up copy of the values is therefore stored in the display. In order to visualize them, press the button , the screen opposite is displayed. Using the button select the menu "Save adjustment values" and confirm with the button .
For example: The screen opposite appears. The adjustment data have been stored in the display.
At this point, it is possible to exit the menu in one of two ways:
- positioning the cursor on the symbol and confirm with the button.
- using the symbol.
09/2016 - Art. Nr. 4200 1055 6801A 35
Page 36
Servicing
Maintenance
Burner and boiler servicing must only be carried out by a professional heating engineer trained in these operations. The system operator is advised to take out a maintenance contract to guarantee regular servicing. Depending on the type of installation, shorter maintenance intervals may be necessary.
• Before all maintenance and cleaning
work, switch off all electrical power
supplies (7P socket + separate motor power supply).
• Use original spare parts.
Work recommended as part of an nual burner maintenance:
- Burner test run, input measurement in the boiler room
- Clean the combustion components and replace defective parts if necessary
- Clean the fan wheel and the blower
- Clean the gas filter; replace it if necessary
- Visual inspection of the burner's electrical components; eliminate malfunctions if necessary
- Check burner start characteristics
- Leakage test
- Burner safety devices function check (air pressure/gas pressure switches)
- Flame monitor and automatic combustion control unit function check
- Commissioning the burner
- Check the gas flow
- Correct the adjustment values if necessary
- Draw up a measurement report
General checks
- Emergency stop button function check
- Visual inspection of gas lines in the boiler room
Checking the combustion components
• Remove the burner hood.
• Remove the two screws W from the cover.
• Remove the combustion components.
• Check the ignition electrodes and the ignition cables; replace if necessary.
• Clean the turbulator.
• Check adjustments and settings during assembly.
Removing the plate
• To do this, unscrew but do not remove the 2 screws
• Turn the plate (bayonet system), carefully remove it and hang it in the maintenance position (see illustration).
• Clean the housing, fan wheel and recirculation unit, and check that they are not damaged.
• If necessary to clean it, remove the air recycler; to do so, remove the screw Z then unclip it.
• Clean the turbine and check it is not damaged.
X
securing the motor plate.
Fitting the fan wheel
When changing the motor or the fan wheel, refer to the positioning diagram opposite. The internal flange A of the fan wheel must be aligned with plate B. Insert a ruler between the vanes of the fan wheel and bring A and B to the same height. Tighten the cone-point screw on the fan wheel.
09/2016 - Art. Nr. 4200 1055 6801A36
Page 37
en
Servicing
Maintenance
Replacing the flame tube
For this operation, it is necessary to either open the furnace gate or remove the burner.
- Variant 1 - Access via the furnace gate
• Remove the burner head
• Loosen the 3 securing screws S on the flame tube support by 1 to 2 turns. (Allen 3).
• Open the combustion chamber door.
• Take out the flame tube, check it, clean it and, if it is deformed, replace it.
• Proceed in the reverse order for refitting.
• Fill in the space between the furnace gate and the burner tube with fire­resistant material.
• Close the furnace gate.
- Variant 2 - Removing the burner
• Remove the burner head.
• Loosen the electrical connections.
• Loosen the burner housing (2 M8 screws) and remove. Do not damage electrical cables.
• Unscrew the burner head and then proceed as under variant 1.
• Proceed in the reverse order for refitting.
The flame tube may be hot
to release the screws (bayonet).
• Remove the air intake box, clean it and refit it in reverse order.
• Check that the air flap and the servomotor are correctly positioned.
Cleaning the cover
• Do not use abrasive products or products containing chlorine.
• Clean the cover with water and a suitable cleaning product.
• Refit the cover.
Precautions After any operation: check the combustion performance under real operating conditions (doors shut, cover fitted etc.). Record the results in the relevant documents.
Checking the flue gas temperature
• Check the flue gas temperature at
regular intervals.
• Clean the boiler if the flue gas
temperature is more than 30 °C above the value measured at the time of commissioning.
• Use a flue gas temperature gauge to
make the check easier.
Filter replacement
• The filter element of the multiblock must be checked at least once a year and replaced if clogged.
• Loosen the screws of the filter cap on the multiblock.
• Remove the filter element and clean its housing.
• Do not use any pressurised cleaning products.
• Replace the filter element with a new element.
• Screw the cover back into place.
• Reopen the manual shut-off valve.
• Check it is airtight.
• Check the combustion values.
Cleaning the pump filter
The filter is located in the pump housing. It must be cleaned with every maintenance service. To do this:
• Close the fuel oil shut-off valve.
• Place a container under the pump to catch the fuel oil.
• Remove the screws and cover.
• Remove, clean or replace the filter.
• Refit the filter, close the cover again and use a new gasket.
• Tighten securely.
• Open the fuel oil tap again.
• Check pressure and tightness.
Cleaning the air box
First check that the air flap is in the closed position (0°), before removing it (2 screws V).
• Unscrew the three securing screws T in the base of the housing by a few turns.
• Shift the air intake box 113 to the right
09/2016 - Art. Nr. 4200 1055 6801A 37
Page 38
Servicing
Gas operation
Troubleshooting
Malfunction diagnosis and repair
In the event of a malfunction, first check that the prerequisites for correct operation are fulfilled:
1. Is there any current?
2. Is there gas pressure?
3. Is the gas shut-off valve open?
4. Are all control and safety devices, such as the boiler thermostat, low water detector, limit switches, etc. correctly set?
If the fault is still present, check that each of the burner components is operating. Important safety components must not be repaired; these components must be replaced by parts with the same part
Symbol Observation Cause Corrective action
Burner does not start after thermostatic closure. No malfunction indicated on the control and safety unit.
No heat requested. Thermostats defective or
number.
Only use original spare parts. Switch off the power supply before carrying out maintenance or cleaning.
After any work on the system:
• Under normal operating conditions (doors closed, cover fitted, etc.), check combustion and check the individual lines for leaks.
• Record the results in the relevant documents.
Drop in supply voltage or power failure.
Control unit malfunction.
incorrectly adjusted
Check the cause of the drop in voltage or the power failure.
Replace the control unit.
Adjust the thermostats, replace if necessary.
The burner starts briefly when switched on, then switches off and the red indicator light comes on.
Burner does not start. Air pressure switch: not in rest
Burner does not start.
Gas pressure normal
The control unit has intentionally been manually locked.
position. Incorrect adjustment
Contact welded
Insufficient gas pressure.
Gas pressure switch wrongly set or defective
Unlock the unit.
Readjust the pressure switch. Check the wiring. Replace the pressure switch.
Check the gas lines. Clean the filter. Check the gas pressure switch or replace the compact gas unit.
09/2016 - Art. Nr. 4200 1055 6801A38
Page 39
en
Servicing Gas operation
Troubleshooting
Symbol Observation Cause Corrective action
Burner blower starts up. Burner does not start.
Burner blower starts up. Burner does not start.
The burner starts, the ignition switches on, then failure
Air pressure switch: Contact does not close.
Flaring during pre-ventilation or pre-ignition.
No flame at the end of the safety time.
Gas throughput set incorrectly. Malfunction in flame monitoring system
Incorrect polarisation (live/neutral position) of the power supply on the 7P connector/socket
Readjust the pressure switch. Check the wiring. Replace the pressure switch.
Check the valve. Check flame monitoring.
Adjust the gas flow stage Check the condition and position of the ionisation probe in relation to earth. Check the condition and connections of the ionisation circuit (cables and measurement bridge).
Check that the polarisation of the 7P connector is correct.
No ignition sparks. Electrode(s) short-circuited.
Ignition cable(s) damaged or defective.
Igniter defective. Control and safety unit
Solenoid valves do not open.
The burner switches off during operation.
Servomotor fault Clogging of the air flap
Valves jamming. Air pressure switch: contact opens during start-up or during operation.
Flame failure during operation.
Locking of the air flap Internal fault with the servomotor
Adjust, clean or replace the electrodes.
Connect or replace the cable(s).
Replace the igniter. Replace the control unit. Check the cabling between the control unit and external components.
Replace the compact gas unit.
Replace the valves. Adjust or replace the pressure switch.
Check the ionisation probe circuit Check or replace the control and safety unit.
Replace the servomotor
09/2016 - Art. Nr. 4200 1055 6801A 39
Page 40
Servicing
Fuel oil operation
Troubleshooting
Malfunction diagnosis and repair
In the event of a malfunction, first check that the prerequisites for correct operation are fulfilled:
1. Is there any current?
2. Is there fuel oil in the tank?
3. Are all shut-off valves open?
4. Are all control and safety devices, such as the boiler thermostat, low­water detector, limit switch, etc. correctly set?
If the cause of the malfunction cannot be ruled out by the checks described above, check the functions of the
Important safety components must not be repaired; these components must be replaced by parts with the same part number.
Only use original spare parts. Switch off the power supply before carrying out
maintenance or cleaning. After any operation: check the combustion performance under real operating conditions (doors shut, cover fitted etc.). Record the results in the relevant documents.
various burner components.
Symbol Observation Cause Corrective action
The thermostat no longer starts the burner.
The burner starts up briefly when the power supply is switched on and then stops
No heat requested by thermostats
Defective control unit.
The control unit has intentionally been manually locked.
Check/replace the thermostat.
Replace the control unit.
Unlock the unit.
The burner starts then stops after pre-ventilation
The burner starts and stops after the solenoid valves have opened
Flame failure during operation.
Servomotor fault Clogging of the air flap
Unauthorised flame is detected during the pre­ventilation/pre-ignition period
No flame at the end of the safety time.
The flame goes out during the operating phase
Locking of the air flap Internal fault with the servomotor
Check for the ignition spark/adjust the electrodes/ replace Check/replace the fuel oil solenoid valve Checking/replacing the cell
Check fuel oil level in tank. Top the tank up as required. Open the valves.
Check the fuel oil pressure and the operation of the pump, coupling, filter and solenoid valve.
Check the ignition circuit, the electrodes and their settings. Clean the electrodes. Clean and replace the cell.
Replace the following parts as required: ignition electrodes/ignition cables/ igniter/nozzle/pump/solenoid valve/safety unit.
Replace the servomotor
09/2016 - Art. Nr. 4200 1055 6801A40
Page 41
en
Servicing
Fault diagnosis menu Operating statistics menu
Fault diagnosis menu
To access the fault diagnosis menu, press any key when the burner is ready to operate, when the burner is in operation, or when it is in malfunction mode. It is not possible to access the fault diagnosis menu during the start-up phase. The general menu screen will appear. Using the , , , or key, place the cursor on the fault diagnosis menu symbol, and confirm using the key.
The details of the last fault to appear are indicated by the flashing symbol. The flame intensity, network voltage, air flap position, number of burner start-ups as well as the operating time of the burner at the time it switched to malfunction mode are displayed underneath.
Using the keys and , it is possible to call up the details of the last 5 faults to have appeared (the fault number is displayed in the upper left corner of the display). After the details of the last 5 faults, the telephone number of the after-sales department as well as the maintenance contract number are shown (no values are entered in the factory).
• Quit the menu using the key.
Entering a telephone number for the maintenance company and the maintenance contract number
When the corresponding symbol appears on the display:
• Keep the key held down until the first figure starts to flash (a short press will exit the menu).
• Using the or key, change the figure to the required value (underscore = empty field)
• Using the key, move on to the next figure.
• When the number is complete, save using the key.
Operating statistics menu
To access the operating statistics menu, press any key, when the burner is ready to operate, when the burner is in operation, or when it is in malfunction mode. It is impossible to access the operating statistics diagnosis menu during the start-up phase. The general menu screen will appear. Using the , , , or key, place the cursor on the operating statistics menu symbol, and confirm using the key. The operating statistics menu comprises 7 screens. Navigation between the different screens is done using the keys and .
- Flame detection time for last start-up
- Average flame detection time for the last 5 start-ups
- Total number of burner start-ups
- Total number of faults
- Total number of operating hours
- Total number of operating hours at rated output
09/2016 - Art. Nr. 4200 1055 6801A 41
Page 42
Servicing
Operating statistics menu
- Total number of burner start-ups since the last meter reset
- Total number of faults since the last meter reset
- Total operating time since the last meter reset
- Total number of operating hours at rated output since the last meter reset
- Number of "unwanted flame" faults
- Number of "No flame after safety time" faults
- Number of "Flame loss during operation" faults
- Number of "Air pressure switch stuck" faults
- Number of "Air pressure switch does not close during operation" faults
- Number of "Air pressure switch switching over" faults
- Number of "servomotor" faults
• Quit the menu using the key .
09/2016 - Art. Nr. 4200 1055 6801A42
Page 43
en
09/2016 - Art. Nr. 4200 1055 6801A 43
Page 44
www.elco.net
Made in EU. Non contractual document.
09/2016 - Art. Nr. 4200 1055 6801A44
Loading...