elco VG2.120 M/TC, VG2.160 M/TC, VG2.210 M/TC, VG 6.1600 M/TC, VG 6.2100 M/TC Original Operating Instructions

Page 1
en
VG2.120 M/TC VG2.160 M/TC VG2.210 M/TC
Original operating instructions
For authorised specialist engineers
Gas burners ...........................................2-31
de, fr.....................................4200 1038 2500
............................................. 4200 1038 2400
09/2014 - Art. Nr. 4200 1038 2700A
Page 2
Overview
Contents
Overview Contents .....................................................................................2
Operation Operation, safety function ..........................................................4
Assembly Burner assembly ......................................................................11
Commissioning Setting data ..............................................................................15
Maintenance Servicing............................................................................. 26-27
Important information
VG2.120/160/210 M/TC burners are designed for the low-pollutant combustion of natural gas and propane gas. The design and function of the burners meet standard EN
676. They are suitable for use with all heat generators complying with standard EN 303 or for use by hot air generators complying with standard DIN 4794 or DIN 30697 within their respective performance range. Any other type of application requires the approval of ELCO. Installation, start-up and maintenance must only be carried out by authorised specialists and all applicable guidelines and regulations must be complied with. This device is not designed for use by individuals (including children) whose physical, sensory, or mental abilities are reduced, or by persons lacking in experience or knowledge, except if they have benefited from supervision or prior instructions concerning the use of the device given by a person responsible for their safety. Children must be supervised to ensure they do not play with the device.
Burner description
VG2.120/160/210 M/TC burners are modulating, fully automatic, monoblock type burners with electronic cam. The special design of the combustion head enables combustion with low levels of nitrogen oxide and increased output. Class 3 type-approval in accordance with EN676 certifies that the lowest emission values have been achieved and means that the national environmental regulations have been met AT: KFA 1995, FAV 1997 CH: LRV 2005 DE: 1.BImSChV Emissions values may differ, depending on furnace dimensions, furnace load and the firing system (three-pass boilers, boilers with reverse firing). For specifying warranty values, the conditions for the measuring equipment, tolerances and humidity must be observed.
Important information .................................................................2
Burner description ......................................................................3
Control and safety unit BT 3xx ...................................................5
Terminal allocation chart ........................................................ 6-7
Control and safety unit BT 3xx gas operation ............................8
BT 3xx menu overview ...............................................................9
MBC-SE gas train.....................................................................10
Gas train...................................................................................12
Checking the combustion components ....................................13
Electrical connection ................................................................14
Testing before commissioning..................................................14
Ionisation current measurement ...............................................14
Air regulation, MBC SE gas train setting ..................................16
Pressure regulator setting ........................................................16
Confirming the "Manual Handshake" data................................17
Menu 1: setting the servomotors ....................................... 18-23
Pre-setting without flame.................................................... 18-19
Setting with flame ............................................................... 20-23
Operating mode........................................................................23
Setting the gas pressure switch/air pressure switch ................24
Displaying the setting data from the manual control display ....25
Menu 3: Fault memory, Entering a telephone number for the maintenance company and the
maintenance contract number............................................ 28-29
Menu 4: operating statistics......................................................30
Setting the brightness and contrast of the display....................31
Packaging
The burner is supplied in three packaging units:
- Burner housing with operating instructions, circuit diagram and spare parts list.
- Burner head with flange seal and securing screws.
- Compact gas train with integrated filter
The following standards should be observed in order to ensure safe, environmentally sound and energy-efficient operation:
EN 226
Connection of fuel oil and gas burners with blast air to the heat generator
EN 60335-1, -2-102
Specification for safety of household and similar electrical appliances, particular requirements for gas burning appliances
Gas lines
When routing the gas lines and fittings, the general installation instructions and guidelines, as well as the following national regulations, must be observed: CH: - G1 instruction text from SSIGE
- EKAS form no. 1942,
liquefied gas directive, part 2
- Cantonal authority guidelines (e.g.
directives for the pilot valve)
DE: - DVGW-TVR/TRGI
Installation location
The burner must not be used in rooms with aggressive vapours (e.g. hair spray, tetrachloroethylene, carbon tetrachloride), high levels of dust or high air humidity (e.g. laundry rooms). There must be a supply air inlet measuring: DE: up to 50 kW: 150 cm
for each additional kW: + 2.0 cm
CH: QF [kW] x 6= ...cm2; but 200 cm2
minimum. Variations may arise as a result of local regulations.
Page
Declaration of conformity
for gas burners
We, certified company under the name "Site A" declare under our sole responsibility that the products VG2.120 M/TC VG2.160 M/TC VG2.210 M/TC
conform to the following standards EN 50165 EN 55014 EN 60335-1 EN 60335-2-102 EN 60555-2 EN 60555-3 EN 676 Belgian royal decree dated 08/01/2004
These products bear the CE mark in accordance with the stipulations of the following directives 2006/ 42/EC Machinery Directive 2004/108/EC EMC Directive 2006/ 95/EC Low
Voltage Directive
92/ 42/EEC Efficiency Directive
Annemasse, June 1st 2012
F. DECIO
We accept no responsibility for damage arising from:
- inappropriate use
- incorrect installation and/or repair on the part of the buyer or any third party, including the fitting of non-original parts.
Final delivery and instructions for use
The firing system fitter must supply the operator of the system with operating and maintenance instructions on or before final delivery. These instructions should be displayed in a prominent location at the point of installation of the heat generator.They should include the address and telephone number of the nearest customer service centre.
Notes for the operator
The system should be inspected by a specialist at least once a year. Depending on the type of installation, shorter maintenance intervals may be necessary! It is advisable to take out a maintenance contract to guarantee regular servicing.
2
2
09/2014 - Art. Nr. 4200 1038 2700A2
Page 3
Overview
en
Burner description
A1 Control and safety unit A4 Display F6 Air pressure switch M1 Blower motor T1 Igniter Y10 Air flap servomotor 3 Adjusting knob for dimension Y 4 Propane diffuser 5 Housing 6 Plate hanging device
(Maintenance) 8 Burner tube 10 7-pin connector
10.1 4 pin connector 16 Gas connecting flange 18 Cover 19 Release knob 20 Hood securing screw 113 Air intake box
09/2014 - Art. Nr. 4200 1038 2700A 3
Page 4
Operation
Compact train
Operation Safety function
Description of functions
When first powering up, after a power cut or a lockout, after the gas supply has been cut or after a shutdown for 24 hours, a gas valve sealing test is performed before the burner is started, with the fan motor in operation. A pre­ventilation time of 24 seconds begins after the sealing test.
During the pre-ventilation time
- the air pressure is monitored
- a check is made for the presence of any abnormal flame signals.
At the end of the pre-ventilation time
- the ignition is switched on
- the main and safety solenoid valves are opened
- burner start-up
Monitoring
The flame is monitored by an ionisation probe. The probe is fitted with insulation to the gas head and is routed through the turbulator into the flame zone. The probe must not have any electrical contact with earthed parts. The burner switches to malfunction if a short circuit occurs between the probe and the burner earth. During burner operation, an ionised zone is produced in the gas flame through which a rectified current flows from the probe to the burner tip.
The ionisation current must be at least 8 µA.
Safety functions
- If no flame is produced when the burner is started (gas release), the burner is switched off at the end of the safety time which lasts no more than 3 seconds and the gas valve closes.
- If the flame is lost during operation, the gas supply is cut within a second. A new start-up sequence is activated. If the burner starts, the operating cycle starts running. Otherwise a lockout occurs.
- If there is an air failure during pre­ventilation or operation, a lockout occurs.
- If there is a gas failure, the burner either stops or will not start. As soon as sufficient gas pressure is available again, the burner restarts.
During the regulator shutdown
- The control thermostat interrupts the heating request
- The gas valves close
- The flame goes out
- The blower motor stops
- The burner is ready for operation
F4 Gas pressure switch F6 Air pressure switch Y12 Safety solenoid valve Y13 Main solenoid valve 1 Thermal safety valve (to be
installed by the fitter)
103.1 Gas throttle 106 Screen 108 Gas cut-out valve (to be
installed by the fitter)
119pBr Gas pressure measuring point
at the valve outlet
119.1 Gas pressure measuring point upstream of the valves
119.2 Air pressure measuring point
CH note
In accordance with SSIGE instructions, it is compulsory to install a gas safety valve (mark 1) in the pipe.
DE Note
In compliance with the reference layout applicable to boiler rooms, sites with gas furnaces must be fitted with a thermal gas shut-off valve (1).
09/2014 - Art. Nr. 4200 1038 2700A4
Page 5
Operation
en
Control and safety unit BT 3xx
The control and safety unit BT 3xx controls and monitors the forced draught gas burner. The microprocessor­controlled program sequence ensures the maximum consistency of the cycle times involved, regardless of fluctuations in the mains voltage or ambient temperature. The control and safety unit is designed to detect power failures. Depending on the parameter assignment, the unit either switches to malfunction mode or goes into the standby position if the power supply falls below the mains voltage. In the standby position, there is an automatic restart as soon as the set threshold value is exceeded by 105%.
Pressing button
for ...
... 1 second ... the control and safety
... 2 seconds ... the control and safety
… causes ….
unit to unlock.
unit to lock
Manual locking and unlocking
Using the reset button , the control and safety unit can be locked manually (interlocked) or unlocked, provided the unit is connected to the mains power supply. This function must not be confused with automatic locking and fault acknowledgement in case of an error.
Before installing or removing the unit or any operation in the connection area, switch off the supply to the device, check for the absence of voltage and prevent any reactivation. Otherwise there is risk of electric shock. The control and safety unit must not be opened or repaired.
- Moves the cursor upwards
- Moves the cursor downwards
- Increases the marked value
- Moves the cursor to the right
- Reduces the marked value
- Moves the cursor to the left
Modifies/confirms the value shown
- Unlocks the control and safety unit
Red LED (flashes if a fault is present)
09/2014 - Art. Nr. 4200 1038 2700A 5
Page 6
Operation
Air pressure
switch
Ignition
device
Terminal
Connector
Remote
unlocking
Solenoid valves
(1+2)
Heating request
Min. gas pressure
switch
Burner
safety circuit
Boiler safety circuit
Solenoid
valve 3
Flame check
Fault
display
Burner motor
Terminal
L1 power supply
Grounding of
the burner
UV detector
additional
Ionisation
Flame monitor
Connector
1 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 1 2 3 4
1 2 3
1 2 3
1 2 3
Pin
Pin
1 2 3 1 2 3
1 2 3
1 2 3 1 2 3 1 2
1 2
Terminal allocation chart
Pin Terminal Description Connector Pin Terminal Description Connector
1 1 Phase gas solenoid valve 1
2 2 Earth 1 30 Neutral conductor of the fuel-oil
3 3 Neutral conductor 2 31 Earth 1 4 Phase gas solenoid valve 2 3 32 Phase 2 5 Neutral conductor 1 33 Neutral conductor 3 6 Earth 2 34 Earth 1 7 Phase fuel valve 3 (optional) 2 8 Earth 1 36 Neutral conductor 3 9 Neutral conductor 2 37 Earth 1 10 Phase ignition transformer 2 11 Earth 1 39 Neutral conductor 3 12 Neutral conductor 2 40 Earth 1 13 Phase gas pressure switch min. 2 14 Earth 1 42 Neutral conductor 3 15 Phase 2 43 Earth 1 16 Phase burner safety circuit 2 17 Earth 1 45 UV flame monitor (-) 3 18 Phase 2 46 UV flame monitor (+) 1 19 Phase boiler safety circuit 2 20 Phase 2 48 Phase 1 21 Phase air pressure switch 2 22 Phase 4 50 Flame monitor (-) 1 23 Load (-) 2 24 Load (+) 3 25 Phase 1 26 Malfunction reset 2 27 Burner ON 3 28 Phase
X01
+
X02
X03 X04 X05
X06 X07
X08 X09
X10
1 29 Grounding of the burner
pump
3 35 Phase burner motor
3 38 Alarm output
3 41 L1 power supply
3 44 L1 power supply output
1 47 Ionisation probe
3 49 Flame monitor (+)
X26 X25
X24 X23 X22
X21 X20
09/2014 - Art. Nr. 4200 1038 2700A6
Page 7
Operation
Terminal
Display
PC interface
Gas
servomotor
Air
servomotor*
Fuel oil
servomotor*
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Pin
Connector
en
Terminal allocation chart
Pin Terminal Description Connector
11 22 33 44 55 66 17 28 39 410 511 612 113 214 315 416 517 618 119 220 321 422 523 624 125 226 327 428 529 630
Display
PC interface
Servomotor gas
Servomotor air*
Servomotor fuel oil*
X30
X31
X32
X33
X34
* Terminal allocation depends on the design of the burner
09/2014 - Art. Nr. 4200 1038 2700A 7
Page 8
Operation
Boiler safety circuit Gas safety circuit Burner on Minimum gas pressure swi t ch
Air pressure switch
Flame signal
Air flap
Gas flap
Transformer
Gas valve 1 Gas valve 2
Air motor Fault
Control and safety unit BT 3xx gas operation
Legend to the sequence diagram
t1 Awaiting boiler safety circuit
Air pressure switch min. request
t2 Time for pressure build-up in the gas control line (only
when sealing test mode is activated, program sequence for density test can vary, see sequence diagram for density test)
t3 Servomotor running time t4 Closing of gas flap t5 Ventilation time t6 Transformer activation time
Sealing test sequence diagram - no gas pressure at start of sealing test. Sealing test sequence diagram - gas pressure present at start of sealing
Legend to the sequence diagrams
t1 Ventilation time, always 2 seconds t2 Delay time, always 2 seconds t3 Sealing test time, configurable t4 Filling time, configurable
The diagrams on this page have been taken from the operating instructions of the BurnerTronic BT300 BT320 BT340 from Lamtec. Print no. DLT1200-11-aDE-002 Copyright© 2011 LAMTEC
t9 Safety time t10 Operating phase t11 Regulation t12 Time for pressure release in the gas control line t13 Postventilation time t14 Servomotors under base load t15 Post combustion time t16 Flame extinction test t17 Sealing test gas valve 2
test.
09/2014 - Art. Nr. 4200 1038 2700A8
Page 9
Operation
en
BT 3xx menu overview
In addition to the function of control and safety unit, the control and safety unit BT 3xx also modulates the burner output by controlling the air flap, gas flap, fuel oil quantity regulation and frequency converter (optional) in one electronic circuit. The electronic circuit controls the opening of the gas flap and fuel oil flow regulation proportional to the air flap along a curve based on 10 setting points During start up, the setting points are defined based on the measurement values of the combustion gas analysis. This guarantees optimal combustion
• Menu 1: Setting the
• Menu 2: Display of the
over the burner's entire output modulation range. A separate burner ignition load can be defined with the "Ignition position" setting point . The limit values of the control range are defined by the min. output " " and max. output " " setting points. In addition, other optional functions, such as sealing tests, reventilation or waiting times can be activated. The combustion control unit is operated via a display and operating unit. The parameters for the control and safety unit are set using the display and 5 keys.
servomotors
setting points of the servomotors in the display unit
Operating values are shown in real time on the display. Pressing the keys gives access to 9 menus:
• Menu 6: Setting/ modification of configurations for industrial applications
• Menu 7: Manual mode
• Menu 3: Displaying faults
• Menu 4: Statistical data
• Menu 5: Setting/ modification of standard configurations
• Menu 8: Setting mode
- Menu 8 currently not available
• Menu 9: Setting the brightness and contrast of the display
In these menus, it is possible to adjust the standard configurations of the control unit. These are pre-set in the factory. The nearest customer service department must be contacted before any on­site modifications are made.
09/2014 - Art. Nr. 4200 1038 2700A 9
Page 10
Operation
MBC-SE gas train
The gas train consists of:
- a gas connection flange 1 with O-ring
- a gas throttle 2, controlled by a
servomotor
- a gas connection pipe 3
- an MBC-SE gas valve train with gas
filter 4 (mini filter)
MBC SE gas valve
1 Electrical connection of solenoid
valves (DIN 43650)
2 Electrical connection of gas
pressure switch (DIN 43650) 3 Gas pressure switch 4 Gas inlet flange 5 Mini filter (under cover) 6 Gas pressure adjustment
screw pBr 8 Gas pressure measurement
tap G1/8 (inter-valve pressure) 9 Gas pressure measurement
tap G1/8 (outlet pressure pBr) 10 Gas pressure measurement
tap G1/8 (inlet pressure)
Installation position:
vertical with the coils facing upwards. Where the lines are vertical, the coils must be horizontal.
Description, technical data
The MBC-SE gas compact valve train is a compact unit with 2 Class A solenoid valves, a Class A servo pressure regulator, a mini filter and a pressure switch.
- Pressure switch GW A5: adjustment
range 5.....50 mbar
- Solenoid valve V1/V2 (fast-opening/ fast-closing)
- Adjustable servo pressure regulator
- Max. operating pressure 500 mbar
- Inlet pressure range 15-500 mbar
- Voltage/frequency: 230 V/50-60 Hz
Pressure regulator setting
The outlet pressure is set using adjustment screw 6.
09/2014 - Art. Nr. 4200 1038 2700A10
Page 11
Installation
en
Burner installation
Burner installation
Burner flange 3 is equipped with elongated slots and can be used with a hole Ø of 150 - 184 mm. These dimensions comply with EN 226. The insertion depth of the combustion components can be adjusted to the geometry of the combustion chamber by sliding pipe bracket 2 on the burner's flame tube. The installed depth remains the same during fitting and removal. The burner is secured to the connecting flange, and therefore to the boiler, via pipe bracket 2. This completely seals off the combustion chamber.
Burner tube installation depth and brickwork surround
Unless otherwise specified by the boiler manufacturer, heat generators without a cooled front wall require brickwork or insulation 5 as shown in the illustration opposite. The brickwork must not protrude beyond the leading edge of the flame tube, and should have a maximum conical angle of 60°. Space 6 must be filled with an elastic, non-flammable insulation material.
Installation:
• Secure connecting flange 3 to the boiler using screws 4
• Fit pipe bracket 2 to the burner pipe and secure using screw 1. Tighten screw 1 to a maximum torque of 6 Nm.
• Turn the burner slightly, guide it into the flange and secure using screw 5.
Removal:
• Loosen screw 5
• Turn the burner out of the bayonet socket and pull it out of the flange.
For assembly in the position with
the volute facing upwards, unclip the display from its support, turn it over 180° and refit it.
Exhaust gas evacuation system
To avoid unpleasant noise emissions, right-angled connectors should not be used on the flue gas side of the boiler.
On boilers with reverse firing, the minimum flame tube insertion depth A should be observed as per the boiler manufacturer's instructions.
Inspection glass cooling
The burner body can be equipped with an R1/8" connection to support a line for cooling the boiler's inspection glass.
• To do this, drill through cast iron
projection 6 and cut a 1/8" thread.
• Use accessories article no. 12 056 459 for the threaded union and connection hose.
09/2014 - Art. Nr. 4200 1038 2700A 11
Page 12
Installation
Gas train
Gas train installation
• Check the correct position of the O-
ring J1 in the connecting flange.
• Secure the gas train on the burner so that the gas train coils are in the upper vertical position.
• Pay attention to the direction of circulation.
• Route the connection cables C for the gas train through cable gland and connect it to the gas train.
On VG2.160/210 M/TC burners, insert the diaphragm 2 delivered with the gas train mounting parts into the flange of the burner body.
09/2014 - Art. Nr. 4200 1038 2700A12
Page 13
Installation
VG2.120
VG 2.120
VG2.160/210
VG2.120
VG2.160/210
en
Checking the combustion components
Checking the combustion components
• Remove the three screws W from the
cover.
• Remove the cover.
• Loosen lock nut E on the gas pipe
bracket
• Loosen the retaining bolt.
• Remove combustion components.
Setting to propane gas operation VG2.120 burner
• Remove the shutter 3 and the turbulator 4.
• Fit the adaptor 5 (supplied with the housing).
• Fit the turbulator 4 without shutter 3.
Setting to propane gas operation VG2.160/210 burner
• Remove the shutter 3 and the turbulator 4.
• Fit the adaptor 5 (supplied with the housing).
• Fit the turbulator 4 and the shutter 3.
the
Checking the combustion components
• Check the setting of the ionisation probe and the ignition electrode in accordance with the illustrations.
09/2014 - Art. Nr. 4200 1038 2700A 13
Page 14
Installation Electrical connection
Checks before commissioning Ionisation current measurement
General regulations applying to the gas connection
• The gas train must only be connected to the gas mains by a recognised specialist.
• The cross-section of the gas line should be of a size designed to guarantee that the gas flow pressure does not drop below the specified level.
• A manual shut-off valve (not supplied) must be fitted upstream of the gas train.
• In Germany, a thermally triggered shut-off valve (to be installed by the customer side) must be fitted as
specified by the draft combustion
ordinance. It is the responsibility of the fitter or his representative to obtain approval for the system at the same time as the burner is commissioned. Only the fitter or his representative can guarantee that the system meets applicable standards and regulations. The fitter should be in possession of the corresponding official permit, and should carry out the corresponding sealing tests and purge the system of air.
Electrical installation and connection work must only be carried out by a suitably qualified electrician. All applicable regulations and directives must be observed.
N.B. The applicable guidelines and directives must be observed, as well as the electrical circuit diagram supplied with the burner.
Electrical connection
• Check to ensure that the power supply
is as specified (230V, 50 Hz single
phase with neutral and earth). Boiler fuse: 6.3A
Electrical connection
It must be possible to disconnect the burner from the mains using an omnipolar shutdown device complying with the standards in force. A device to protect against short circuits must also be fitted upstream of the burner's electrical power supply.The burner and heat generator (boiler) are connected by a 7-pin connector 1 and a 4-pin connector 2 (not supplied). The diameter of the cables connected to these connectors must be between 8.3 and 11 mm.
Connecting the gas train
Connect the gas train to the plugs on the burner (black to black, grey to grey).
Checks before commissioning
The following must be checked before initial commissioning:
• That the burner is assembled in accordance with the instructions given here.
• That the burner is pre-set in accordance with the values in the adjustment table.
• Setting the combustion components.
• The heat generator must be ready for operation, and the operating regulations for the heat generator must be observed.
• All electrical connections must be correct.
• The heat generator and heating system must be filled with water and the circulating pumps must be in operation.
• The temperature regulator, pressure regulator, low water detectors and any other safety or limiting devices that might be fitted must be connected and operational.
• The exhaust gas duct must be unobstructed and the secondary air system, if available, must be operational.
• An adequate supply of fresh air must be guaranteed.
Ionisation current measurement
To measure the ionisation current, disconnect connector B10 and connect a multimeter with a measuring range of 0-100 µA.
nd
The 2 at least 7 µA. It is also possible to read the ionisation current on the display.
stage ionisation current must be
• The heating request must be available.
• Sufficient gas pressure must be available.
• The fuel supply lines must be assembled correctly, checked for leaks and bled.
• A standard-compliant measuring point must be available, the exhaust gas duct up to the measuring point must be free of leaks to prevent anomalies in the measurement results.
09/2014 - Art. Nr. 4200 1038 2700A14
Page 15
Commissioning
P3(°) P6 (°) P3(°) P6 (°)
40 80 10 0,8 0 0 10 20 30 5 5 10 20 28 13,0 50 100 20 0,9 10 10 20 30 45 15 15 25 38 55 10,0 60 120 30 1,3 15 15 30 40 80 15 15 30 35 65 14,0 40 80 10 0,8 0 0 10 20 30 5 5 10 20 28 17,5 50 100 20 0,9 10 10 20 30 45 15 15 25 38 55 15,0 60 120 30 1,3 15 15 30 40 80 15 15 30 35 65 18,0 40 80 10 0,8 0 0 10 20 30 5 5 10 20 28 7,5 50 100 20 0,9 10 10 20 30 45 15 15 25 38 55 7,5 60 120 30 1,3 15 15 30 40 80 15 15 30 35 65 8,0
40 130 10 1,4 0 0 20 40 60 12 12 26 43 57 10, 0 50 150 15 1,5 5 5 30 55 75 15 15 35 48 70 10, 0 60 160 25 1,7 13 13 30 60 90 17 17 30 44 55 13,0 40 130 10 1,4 0 0 20 40 60 12 12 26 43 57 12, 5 50 150 15 1,5 5 5 30 55 75 15 15 35 48 70 13, 0 60 160 25 1,7 13 13 30 60 90 17 17 30 44 55 16,0 40 130 10 1,4 0 0 20 40 60 3 3 20 36 50 6,5 50 150 15 1,5 5 5 30 55 75 5 5 27 40 65 7,5 60 160 25 1,7 13 13 30 60 90 12 12 25 36 65 8,0
45 140 10 1,4 0 0 20 40 60 13 13 26 50 65 10, 0 50 150 20 1,5 6 6 25 45 65 14 14 32 48 65 10, 0 60 185 35 1,7 10 10 35 65 90 15 15 35 45 75 13,0 45 140 10 1,4 0 0 20 40 60 13 13 26 50 65 12, 5 50 150 20 1,5 6 6 25 45 65 14 14 32 48 65 13, 0 60 185 35 1,7 10 10 35 65 90 15 15 35 45 75 16,5 45 140 10 1,4 0 0 20 40 60 5 5 20 40 65 0,6 50 150 20 1,5 6 6 25 45 65 8 8 27 40 60 0,6 60 185 35 1,7 10 10 35 65 90 10 10 30 42 75 8,0
Burner
Part­load
Dimension
Y mm
gas
Bur ner output
kW
Ga s throttle positi on
Pressure
regulator
PBr
setting
mbar
Full
load
Ignition
load
(°)
Part­load
P0 (°)
Full
load
P9 (°)
Ignition
load
(°)
Part­load
P0 (°)
Full load
P9 (°)
Furnace press ure
mbar
Air flap position
VG2.210
M/TC
G20
G25
G31
VG2.120
M/TC
G20
G25
G31
VG2.160
M/TC
G20
G25
G31
en
Adjustment data
Type of
Only for the VG2.210 burner:
• When operating at low gas pressure, it is necessary to remove the diaphragm 4 from the gas inlet.
The adjustment values above are guide values and facilitate commissioning. The factory settings are in bold set against a grey background. The final settings are essential in ensuring that the burner functions as well as possible.
Setting the gas pressure switch
• Remove the transparent cover.
• Provisionally set to 15 mbar.
Setting the air pressure switch
• Remove the transparent cover.
• Provisionally set to 1 mbar.
09/2014 - Art. Nr. 4200 1038 2700A 15
Page 16
Commissioning Air regulation
MBC-SE gas train setting Pressure regulator setting
Air regulation
Combustion air is regulated at two points:
• on the pressure side, using the gap between the turbulator and the burner tube.
• on the vacuum side, by the air flap driven by servomotor Y10.
The regulation of air in the burner head affects not only the air flow but also the mixing zone and the air pressure in the burner tube. Turning screw A
- to the right for more air
- to the left for less air
• Adjust dimension Y in accordance
with the settings table.
Air regulation by air flap
Air is regulated on the vacuum side by an air flap. This is driven by servomotor
Y10.
MBC-SE gas train setting Pressure regulator setting
The gas pressure regulator is set at 10 mbar in the factory. Check the gas pressure after the first time the burner is started (measuring point at gas train outlet flange) and if necessary, correct gas pressure pBr via adjustment screw S in accordance with the table on page
15. After start up, no further changes
should be made.
09/2014 - Art. Nr. 4200 1038 2700A16
Page 17
Commissioning
en
Confirmation of "Manual Handshake" data
The following sequence for confirming or cancelling the data entry is the same for a number of different changes to the parameters. For this reason, this sequence is not illustrated in detail for each of the parameter settings outlined below. The parameter modifications which require a "Manual Handshake" are highlighted on the following pages. These parameter modifications are assigned the following reference:
Manual Handshake
You are now asked to confirm the modifications that have been made. Accept or cancel the entry
The "Manual Handshake" is explained below using menu 5 as an example. The following parameters have been modified in the example:
- Density test activated after burner cycle
- Post-ventilation time activated (5 seconds)
The following screen appears once the parameter has been set and the data entry confirmed. You are asked to confirm the data within 7 seconds. In this case: "Density test after burner cycle activated". A counter displaying the remaining time appears in the bottom right-hand corner of the screen.
Only confirm the displayed settings if they correspond with your specifications. The entry can be accepted if both values are identical. The entry can be cancelled if there is a deviation in values.
To confirm and save the parameter modification, select symbol and confirm with key .
To cancel the modifications, select symbol and confirm with key . Alternatively, you can wait until the time has expired. No modifications are made.
Note:
You will return to the previous menu if the procedure is cancelled. The previous unmodified settings are displayed.
If you accept these values, a second screen appears. In this case: "Post-ventilation time activated, duration 5 seconds". Once again, the data must be confirmed within 7 seconds.
Only confirm the displayed settings if they correspond with your specifications. The entry can be accepted if both values are identical. The entry can be cancelled if there is a deviation in values.
Confirm the data or stop the procedure as described above.
If all values of the "Manual Handshake" have been confirmed, the data is saved in the BurnerTronic. The modifications have been made and the procedure is completed. You return to the starting screen.
Note:
If several parameters of a menu have been changed simultaneously (as in the example), the individual modifications must be confirmed separately.
09/2014 - Art. Nr. 4200 1038 2700A 17
Page 18
Commissioning
Menu 1: setting the servomotors Pre-setting without flame
Setting is carried out in 2 phases:
- Pre-setting without flame
- Setting the flame, to fine tune the settings based on the combustion results
Important
At this point, no setting position for the servomotors has been defined, therefore the burner cannot be started
under these conditions. When the burner is switched on, the control and safety unit displays the screen below.
Access codes must be entered for the individual menus at various points in these instructions. Menu areas protected by access codes are solely reserved for authorised, qualified and trained personnel.
The following menu description explains the menu for gas operation (figures), but is also valid for fuel oil operation. Any deviations are noted where relevant.
• For the next step, press key .
The control and safety unit then opens the settings mode. The screen displays the factory pre-settings for the different positions of the fuel and air flap (here: for an electronically modulated gas burner)
The menu displays all the The overview of the menus is displayed, and the air and gas
flap position settings menu is
settings data using three
consecutive screens (air and
gas flap positions), i.e. for: selected.
- Ignition position: (when
• Open the settings menu by
pressing the key.
the menu is opened, the cursor is positioned here)
- Output points P0 to P9
The access code must be entered at this point (Access code 1)
• Increase or decrease the
value in increments by repeatedly pressing or .
• When the first figure has
been set, move the cursor to the right by pressing .
• Repeat the operation until
you reach the last figure.
• Confirm the access code by
pressing key .
Special feature for operation with the frequency converter:
The fan motor is activated when menu 1 is accessed. Activation must be confirmed, the screen is displayed as shown on the left (Manual Handshake). Continuous ventilation is activated for the pre-set time period in menu 1. This is necessary to obtain a feedback value for the frequency converter channel. This setting is deactivated again at the end of menu 1.
09/2014 - Art. Nr. 4200 1038 2700A18
Modifying a value for the servomotor position:
- To modify the value of a position, move the cursor to the corresponding location with the key.
- Select the value to be modified using the key, the selected value will flash.
- Increase or decrease the value (in increments of 0.1°) by repeatedly pressing or . For large modifications, press and hold the or key, the value will scroll quickly up or down.
- Confirm the new value using the key. The value stops flashing.
Page 19
Commissioning
en
Menu 1: setting the servomotors Pre-setting without flame
End of settings menu without flame
When all the positions of the servomotors have been determined according to the required settings, it is possible to move on to the next set-up stage, setting with flame.
To do this, place the cursor in the lower part of the screen on the symbol and confirm by pressing the key. Only for operation with the frequency regulator: Manual Handshake
Accept or cancel the entry. Note: continuous ventilation is deactivated when this menu is exited.
If you want to exit the menu without saving the pre-settings, position the cursor on the symbol and confirm with the key. A processing screen now appears for a short time. The "Setting with flame" comes after this (see page 20).
You are now asked to confirm the modifications that have been made.
It is also possible to delete all the settings at this point. To do this, position the cursor on the symbol and confirm with the key.
The screen opposite appears. At this point, it is possible to:
- delete the values; to do so, move the cursor to the symbol and confirm with the key. A processing screen appears for a short time
- Exit the screen without modification using the symbol.
The previous menu is displayed.
General advice before starting the burner
Function check
All safety equipment must be checked to
Risk of deflagration
Continue to monitor the CO, CO2 and O2 and soot content of the exhaust gases during setting. Improve combustion values in the event of CO emissions and soot formation. The CO content should be <10 ppm. The soot content should be <1.
ensure that it is fully functional as part of initial commissioning and also after servicing or if the system has been out of operation for any significant period of time.
The check must be carried out following the guidelines in the section entitled
Checking the safety equipment.
09/2014 - Art. Nr. 4200 1038 2700A 19
Page 20
Commissioning
Menu 1: setting the servomotors Setting with flame
- If the boiler heating request is not present, the
burner remains on standby.
In this case, it is still possible to return to the previous setting menu "Pre-setting without flame". To do so, confirm with the key.
- As soon as there is a boiler heating request (contacts X10-2 and X10-3 closed), the burner starts.
The air flap is opened to move to the pre-ventilation position.
Air pressure switch test
The air flap switches to the ignition/pre-ignition position.
The fuel valve opens.
Awaiting flame signal
If no flame is detected at the end of the safety time, the
control and safety unit switches to malfunction mode.
Gas valve sealing test* (the remaining time is displayed in the menu in the bottom right-hand corner)
Pre-ventilation
* only for burners with integrated sealing test and only for gas operation
Flame detected
Flame stabilisation
The control and safety unit awaits regulation authorisation.
09/2014 - Art. Nr. 4200 1038 2700A20
Page 21
Commissioning
en
Menu 1: setting the servomotors Setting with flame
Setting the ignition position
If a flame has been detected, the control and safety unit sets the burner to the ignition position as soon as it receives the regulation authorisation.
- Set the fuel controller position and the air flap position according to the desired output level. While doing so, constantly check the combustion values (CO, CO2 O2, soot, NOx). If required, adapt the gas and fuel oil pressures at the valve and fuel-oil pump.
- Modify the position of the servomotors in the ignition position (lines with symbol). Proceed as described on page 18, in the paragraph "Modifying the value of a servomotor position setting".
- Warning: when modifying the value, the servomotor will move in real time. As a consequence, the combustion values must be constantly checked.
The burner remains in ignition load.
Setting points P0-P9.
• Check the gas and fuel oil pressure. In the event of subsequent modifications, all setting values must be corrected. For this reason, fine setting of the burner from point P9 must be carried out, if necessary. At each setting point, check the combustion values and if necessary, change the fuel controller position or the air flap position. To do so:
• Select air or fuel with or .
• Activate via (the cursor flashes).
• Change the value via or .
• Confirm with .
The next setting point is accessed using the key.
Note:
The values for each setting point are not saved until the next setting point is accessed. Each point must be defined. It is not possible to skip individual points, as opposed to when setting without flame. Only when all points (P0...P9) have been defined can the limit values for minimum and maximum be set.
Further procedure:
• Enter the setting values in the log.
• Initiate all setting points individually
• Check the burner output at the maximum setting and raise or lower the fuel and air values if necessary.
• Once all setting points P0 to P9 have been optimised, confirm them by navigating to the next screen. To do so, press the key at point 9.
Note: The next screen can only be activated once all points (P0...P9) have been defined
• The burner moves to the lower operating point, symbol .
• Check the exhaust gas temperature, emissions and output at low load, if required, adapt the burner output by correcting .
- To change:
• Activate with (the cursor flashes).
• Change the value via or
• Confirm with
Continue with the key
The burner moves to the upper operating point, symbol .
• Check the exhaust gas temperature, emissions and output at low load, if required, adapt the burner output by correcting .
- To change:
• Activate with (the cursor flashes).
• Change the value via or
• Confirm with
Continue with the key
The setting procedure is completed at this point, the burner switches to operating mode. The burner switches to the lower operating point and waits for a heating request. The burner operates within the preset output range ( - ) according to the settings of the control thermostat.
09/2014 - Art. Nr. 4200 1038 2700A 21
Page 22
Commissioning
Menu 1: setting the servomotors Setting with flame
It is only possible to adjust (limit) the low load and high load if, for each higher power point, all of the channels also have setpoint values which are always higher. If this is not the case, the screen opposite is displayed. As it is not possible to limit the power range configured, the minimum and maximum operating
points (P0....P9) are automatically defined as the limit.
Example: 1 When the working field is set to always increase, it is possible to adjust the low load and high load.
Example: 2 When the working field is set to not always increase, it is not possible to adjust the low load and high load. The highlighted values in the box do not constantly increase.
Take care with dual fuel burners. The limits for low load and high load apply to both gas and fuel oil operation. It is not possible to define the different limits for fuel oil and gas. If, for example, the values are modified during gas mode, these values are also modified automatically for fuel oil mode.
If values have already been defined, the values for the limits of low and high loads previously specified for the other fuel are displayed in the menu point (left image). If the values are modified, they must be confirmed for both fuels.
09/2014 - Art. Nr. 4200 1038 2700A22
Page 23
Commissioning
en
Menu 1: setting the servomotors Setting with flame Operating mode
Closing the "Setting with flame" menu
The burner setting is now complete. It is still possible, however, to correct the individual values. To do this, position the cursor on the value to be modified, using the or key.
At any time, the following options can always be used to close the "Setting with flame" menu:
- Restart the burner setting procedure, passing through the presetting phase (without entering a password). To do this, position the cursor on the symbol and confirm with the key. All the setting values already saved remain available. This is especially essential for testing a new ignition position.
- Save the specified values and end the setting procedure. To do this, position the cursor on the symbol and confirm with the key. Confirm and close the selected settings with symbol .
Manual Handshake You are now asked to confirm the modifications that have been made. Accept or cancel the entry
- The burner is now ready to operate and can be immediately controlled by the boiler regulation.
- Exit the settings menu without reaching the end of the setting procedure. To do this, position the cursor on the symbol and confirm with the key. All the servomotor positions saved up to this point are recovered by calling up the settings menu again.
Operating mode - Display of the operating status, the flame signal and the operating time
Once setting of the burner has been completed, it switches to operating mode.
The current operation of the burner (operation at min. output, medium output or max. output) is indicated by the cursor.
When ionisation is employed for flame monitoring (gas operation only), the strength of the signal is shown at the bottom of the display. The possible display range is between 0 μA and 30 μA. A good quality signal is one that is above < 9 μA in all load points.
If ionisation is not employed for flame monitoring, either 0% or 100% is displayed. 0% - there is no flame signal 100% - there is a flame signal
If O2/CO regulation is employed, the current O2 value can be read in the bottom right-hand corner of the display.
09/2014 - Art. Nr. 4200 1038 2700A 23
Page 24
Commissioning
Setting the gas pressure switch Setting the air pressure switch
Setting the gas pressure switch
• To set the switch-off pressure: remove the gas pressure switch cover.
• Install a gas pressure pBr measuring instrument.
• Start the burner. Switching to maximum power.
• Reduce the pressure upstream of the gas train by gradually closing the manual valve, until
- the gas pressure pBr upstream of
the gas train drops
- the stability of the flame is reduced
- the CO level increases
- or the flame signal deteriorates
considerably
Setting the air pressure switch
• Install a pressure measuring device. To do this, install a T union in the air tube.
• Set the burner to its maximum operating power.
• Set the switch-off point to approximately 15% below the switch­off pressure read.
• Turn the dial clockwise until the gas pressure switch shuts down the burner.
• Continue turning the dial clockwise to set the gas pressure switch to 10% above the shutdown value determined above.
Checking the switch-off pressure
• Open the manual shut-off valve
• Start the burner
• Close the manual shut-off valve
The gas failure procedure should start without the control unit locking.
09/2014 - Art. Nr. 4200 1038 2700A24
Page 25
Commissioning
en
Displaying the setting data from the manual control display
Displaying the setting data from the manual control display
Once the burner setting procedure has been successfully completed, the servomotor positions for all the operating states are fixed in the control and safety unit. A backup copy of the values is saved in the display. To do this, press the key, the screen opposite is displayed. Using the key select the menu "Displaying the setting data" and confirm with the key.
The screen opposite appears. All setting data is displayed in three consecutive screens. Scroll through by selecting symbols or and confirming with the key. The top right-hand corner of the display shows the fuel to which the current values apply. To switch between the fuel oil and gas parameters, you must navigate to the corresponding symbol and confirm with .
Exit the menu using the symbol.
Note: setting points are automatically stored at the end of the
Caution: the values shown in this menu correspond with the values that were last successfully set with the current
manual control display using menu 1 (menu 1 must have been completed in its entirety). However, these values do not have to correspond with the values saved in the BT300. Any modifications to curve parameters which were carried out after the last start-up or burner setting with the manual control unit using PC software, are not taken into consideration. If the values in the menu deviate from the ones in the BT300, the values can be synchronised with a restart (using the manual control unit - menu 1).
setting procedure for servomotors (menu 1). The setting procedure (menu 1) must be entirely completed in order to save the data. Only once the burner has switched to regulation for the first time are the setting values in the display saved.
09/2014 - Art. Nr. 4200 1038 2700A 25
Page 26
Maintenance
Maintenance
Burner and boiler servicing must only be carried out by a professionally qualified heating engineer. The system operator is advised to take out a maintenance contract to guarantee regular servicing. Depending on the type of installation, shorter maintenance intervals may be necessary.
• Switch off the power supply before all maintenance and cleaning work.
• Use original spare parts.
Work recommended as part of annual burner maintenance:
- Burner test run, input measurement in the boiler room
- Clean the combustion components and replace defective parts if necessary
- Clean the fan wheel and the fan
- Clean the gas filter; replace it if necessary
- Visual inspection of burner electrics, repair if necessary
- Check burner start characteristics
- Sealing test
- Burner safety devices function check (air pressure/gas pressure switches)
Cleaning the fan wheel
• Remove the plate and attach it in the service position (see illustration).
• Remove and clean the fan wheel and replace it if necessary. Refit in the reverse order.
- Flame monitor and automatic combustion control unit function check
- Commissioning the burner
- Check the gas flow
- Correct the adjustment values if necessary
- Draw up a measurement report
General checks
- Emergency stop button function check
- Visual inspection of gas lines in the boiler room
Checking the combustion components
• Remove the burner hood.
• Disconnect the ignition cable on the transformer side.
• Remove the three screws W from the cover.
• Remove the cover.
• Loosen lock nut E on the gas pipe bracket
• Loosen the retaining bolt.
• Remove the combustion components.
• Check the condition of the baffle plate.
• Check the position of the ignition electrode and the ionisation probe.
• When refitting, make sure that the cable is routed correctly and that O­ring J2 is correctly seated.
• Check it is airtight.
Fitting the fan wheel
When changing the motor or the fan wheel, refer to the positioning diagram opposite. The internal flange A of the fan wheel must be aligned with the plate B. Insert a straight edge between the blades of the fan wheel and bring A and B to the same height. Tighten the cone­point screw on the fan wheel.
09/2014 - Art. Nr. 4200 1038 2700A26
Page 27
Maintenance
en
Maintenance
Replacing the flame tube
It is necessary to remove the burner for this work.
• Loosen the clamping screw on the connecting flange.
• Turn the burner out of the bayonet socket, lift it slightly and pull it out of the connecting flange.
• Place the burner on the floor.
• Undo the 4 screws S.
• Pull the flame tube out towards the front.
• Fit and secure the flame tube.
The flame tube may be hot
Filter replacement
• The filter element of the multiblock must be checked at least once a year and replaced if clogged.
• Loosen the screws of the filter cap on the multiblock.
• Remove the filter element and clean its housing.
• Do not use any pressurised cleaning products.
• Replace the filter element with a new element.
• Screw the cover back into place.
• Reopen the manual shut-off valve.
• Check it is airtight.
• Check the combustion values.
Cleaning the cover
• Do not use abrasive products or products containing chlorine.
• Clean the cover with water and a suitable cleaning product.
• Refit the cover.
Important Combustion values must be checked under normal operating conditions (boiler room door closed, hood fitted, etc.) after any work is carried out inside the unit. Record the results in the relevant documents.
Checking the flue gas temperature
• Check the flue gas temperature at
regular intervals.
• Clean the boiler if the flue gas
temperature is more than 30 °C above the value measured at the time of commissioning.
• Use a flue gas temperature gauge to
make the check easier.
Cleaning the air box
• Remove fastening screws V from the
air box.
• Remove the air box, clean it and refit it in reverse order.
• Check that the air flap and the servomotor are correctly positioned.
09/2014 - Art. Nr. 4200 1038 2700A 27
Page 28
Servicing Menu 3: Fault memory
Entering a telephone number for the maintenance company and the maintenance contract number
Menu - Fault memory
To access the fault memory menu, press any key when the burner is ready for operation or in operation, or when it is in malfunction mode. It is not possible to access the fault memory menu during the start-up phase. The general menu screen will appear. Using the , , , or keys, place the cursor on the fault memory menu symbol, and confirm using the key. The details of the last fault to appear are indicated by the flashing symbol. This includes the fault code, flame intensity, air and fuel controller position and burner operating time up to the lockout point. Using the and keys, it is possible to call up the details of the last 5 faults to have appeared (the fault number is displayed in the upper left corner of the display). After the details of the last 5 faults, the telephone number of the after-sales department as well as the maintenance contract number (no values are entered in the factory) and the menu point "Delete fault memory" are shown.
• Exit the menu using the key.
Entering a telephone number for the maintenance company and the maintenance contract number
When the corresponding symbol appears on the display:
• Press the key, the first digit starts to flash.
• Using the or keys, change the figure to the value required (underscore = empty field).
• Using the key, move on to the next figure.
• When the number is complete, save using the key.
• The last menu point of menu 3 makes it possible to delete the fault memory (see explanation on the next page).
Fault diagnosis help symbols
Note: The fault displays described below only show fault diagrams for gas operation (images); however, they are also valid for fuel oil operation. Any deviations are noted where relevant. The symbol shown in the top right-hand corner of the display indicates the fuel for which the fault has occurred.
Symbol Cause Symbol Cause Symbol Cause
The control and safety unit has been manually locked
Air pressure switch malfunction at burner startup (air pressure switch activated)
- Combustion air still present
- Pressure switch defective (contacts are welded)
- Pressure switch incorrectly set
Air pressure switch malfunction at burner startup (air pressure switch not switching)
- No combustion air
- Pressure switch defective
- Pressure switch incorrectly set
Stray light
Flame extinguishing during operation
Internal fault with the air servomotor
Internal fault with fuel servomotor
Gas pressure switch malfunction
- No gas pressure
- Pressure switch defective
- Pressure switch incorrectly set
Safety valve fault (gas operation only)
- Leak in safety gas valve
- Main gas valve not opening (defective)
- Pressure switch defective (contacts are welded)
No defined curve
Fault in boiler safety circuit during operation
Fault in burner safety circuit during operation
No flame at end of safety time
Main gas valve fault (gas operation only)
- Leak in main gas valve
- Safety valve not opening (defective)
- Insufficient gas pressure
- MIN pressure switch defective
- MIN pressure switch incorrectly set
Unknown fault For details, see the fault code list
09/2014 - Art. Nr. 4200 1038 2700A28
Page 29
Servicing
en
Menu 3: Fault memory Entering a telephone number for the maintenance company and the maintenance contract number
Continued: Fault diagnosis help signals:
Symbol Cause Symbol Cause Symbol Cause
Power supply fault
- min. supply voltage not reached
Boiler safety circuit fault when starting burner
The following message appears in the display for the last menu point:
Using , navigate to and confirm with the key to delete the fault memory.
Burner safety circuit fault when starting burner
Fuel oil pressure switch malfunction
- No fuel oil pressure
- Pressure switch defective
- Pressure switch incorrectly set
- Pump defective
- Fault in fuel oil supply
Air pressure switch malfunction during burner operation (decreased air pressure switch signal)
- No combustion air (fan has failed)
- Pressure switch defective
- Pressure switch incorrectly set
You are now asked to confirm that you want to delete the fault memory.
Navigate to and confirm with the key to delete.
Navigate to and confirm with the key to quit and exit the menu.
09/2014 - Art. Nr. 4200 1038 2700A 29
Page 30
Servicing
Menu 4: Operating statistics
Operating statistics menu
To access the operating statistics menu, press any key when the burner is ready for operation or in operation, or when it is in malfunction mode. It is not possible to access the operating statistics menu during the start-up phase. The general menu screen will appear. Using the , , , or keys, place the cursor on the operating statistics menu symbol, and confirm using the key. The operating statistics menu comprises 3 screens. You can navigate between the different screens using the and keys.
- Flame detection time for last burner start-up
- Average flame detection time for the last 5 burner start-ups
- Total number of burner start-ups
- Number of burner start-ups, gas operation
- Number of burner start-ups, fuel oil operation (if available)
- Total operating time since the last counter reset
- Total number of operating hours in gas operation since the last counter reset
- Total number of operating hours in fuel oil operation since the last counter reset
09/2014 - Art. Nr. 4200 1038 2700A30
Page 31
Servicing
en
Setting the brightness and contrast of the display
This menu offers access to the display contrast and brightness settings.
To access the menu, press any key when the burner is ready for operation or in operation, or when it is in malfunction mode.
• The general menu screen will appear. Position the cursor on the symbol for setting the display and confirm with the key.
• Modify the settings using the and keys for the contrast (in increments of 2), or the and keys for the brightness (in increments of 10).
• Position the cursor on the symbol and confirm the setting with the key.
• All modifications entered are discarded using the symbol. The burner returns to the previous operating mode.
09/2014 - Art. Nr. 4200 1038 2700A 31
Page 32
www.elco.net
Made in EU. Non contractual document.
09/2014 - Art. Nr. 4200 1038 2700A32
Loading...