elco VG4.610 DP, VG4.460 DP Operating Instructions Manual

Page 1
03/2013 - Art. Nr. 4200 1032 7200A
VG4.460 DP VG4.610 DP
Operating instructions
For specialist installation engineers
Gas burners ...........................................2-28
en
it, nl ......................................4200 1032 7100
............................................. 4200 1032 6900
Page 2
03/2013 - Art. Nr. 4200 1032 7200A2
Overview
Contents
Declaration of conformity
for gas burners
We, certified company No. AQF030, F-74106 ANNEMASSE Cedex, declare under our sole responsibility that the products
VG4.460 DP VG4.610 DP
conform to the following standards EN 50165 EN 55014 EN 60335-1 EN 60335-2-102 EN 60555-2 EN 60555-3 EN 676 Belgian royal decree dated 08/01/2004
These products bear the CE mark in accordance with the stipulations of the following directives 2009/142/EC Gas appliances
directive 2004/108/EC EMC directive 2006/ 95/EC Low voltage directive 92/ 42/EEC EEC Working
efficiency directive Annemasse, 1st December 2010
M. SPONZA
Overview Contents....................................................................2
Important information................................................2
Burner description..................................................2-3
Operation Operation, safety operation.......................................4
Control and safety unit...........................................5-7
Terminal allocation chart,
connection socket..................................................8-9
MB-VEFgas train.....................................................10
Assembly Burner assembly, gas train assembly................11-12
Checking the combustion components...................13
Electrical/gas connection........................................14
Testing before commissioning ................................14
Commissioning Adjustment data .................................... ... ..............15
Air regulation...........................................................16
Pre-adjustment without flame ............................17-18
Setting the flame.............. ... ...............................19-21
Saving the adjustment values in the display ..........22
Servicing Maintenance .....................................................23-24
Troubleshooting.................................................25-26
Fault diagnosis menu,
Operating statistics menu ..................................27-28
We accept no responsibility for damage arising from:
- inappropriate use.
- incorrect installation and/or repair on the part of the buyer or any third party, including the fitting of non-original parts.
Final delivery and instructions for use
The firing system fitter must supply the operator of the system with operating and maintenance instructions on or before final delivery. These instructions should be displayed in a prominent location at the point of installation of the heat generator, They should include the address and telephone number of the nearest customer service centre.
Notes for the operator
The system should be inspected by a specialist at least once a year. Depending on the type of installation, shorter maintenance intervals may be necessary! It is advisable to take out a maintenance contract to guarantee regular servicing.
Important information
VG4.460 DP and VG4.610 DP burners are designed for the low-pollutant combustion of natural gas and propane gas. The design and function of the burners meet standard EN 676. They are suitable for use with all heat generators complying with standard EN 303 or for use by hot air generators complying with standard DIN 4794 or DIN 30697 within their respective performance range. Any other type of application requires the approval of ELCO. Installation, start-up and maintenance must only be carried out by authorised specialists and all applicable guidelines and regulations must be complied with.
Burner description
VG4.460 DP and VG4.610 DP burners are two-stage fully automatic monoblock devices. The special design of the combustion head enables combustion with low levels of nitrogen oxide and increased output. Class 3 type-approval in accordance with EN676 certifies that the lowest emission values have been achieved and means that the national environmental regulations have been met AT: KFA 1995, FAV 1997 CH: LRV 2005 DE: 1.BImSChV Emissions values may differ, depending on combustion chamber dimensions, combustion chamber load and the firing system (three-pass boilers, boilers with reverse firing). For specifying warranty values, the conditions for the measuring equipment, tolerances and humidity must be observed.
Packaging
The burner is supplied packaged in three boxes on a pallet:
- Burner housing with operating instructions, circuit diagram and spare parts list.
- Burner head with flange seal and securing screws.
- Compact gas train with integrated filter
The following standards should be observed in order to ensure safe, environmentally sound and energy­efficient operation:
EN 226
Connection of fuel oil and forced-draught gas burners to a heat generator
EN 60335-1, -2-102
Specification for safety of household and similar electrical appliances, particular requirements for gas burning appliances
Gas lines
When installing the gas lines and trains, the general directives and guidelines, as well as the following national regulations, must be observed: CH: - G1 instruction text from SSIGE
- EKAS form no. 1942, liquefied gas directive, part 2
- Cantonal aut hority guidelines
(e.g. directives for the pilot valve)
DE: - DVGW-TVR/TRGI
Installation location
The burner must not be used in rooms with aggressive vapours (e.g. hair spray, tetrachloroethylene, carbon tetrachloride), high levels of dust or high air humidity (e.g . laundry rooms). If no connection to an air exhaust system is provided for the air supply, there must be a supply air inlet measuring: DE: up to 50 kW: 150 cm
2
per additional kW: : + 2.0 cm
2
CH: QF [kW] x 6= ...cm2; but at least
150 cm2. Variations may arise as a result of local regulations.
Page 3
03/2013 - Art. Nr. 4200 1032 7200A 3
Overview
Burner description
A1 Control and safety unit A4 Display F6 Air pressure switch K1 Auxiliary motor supply relay M1 Blower motor T1 Igniter Y10 Air flap servomotor 3 Adjusting screw for dimension Y 5 Housing 6 Plate hanging device
(Maintenance)
7 Combustion chamber pressure
take-off pipe 8 Burner tube 10 7-pin connector
10.1 4 pin connector
10.2 3-pin connector (auxiliary motor
supply relay) 18 Cover 19 Release knob 20 Hood securing screw 113 Air intake box
en
Page 4
03/2013 - Art. Nr. 4200 1032 7200A4
Compact train
Operation
Safety function
Description of the function
A pre-ventilation time of 24 seconds begins when first powering up, after a power cut or a lockout, after the gas supply has been cut or after a shutdown for 24 hours.
During the pre-ventilation time
- the air pressure is monitored
- a check is made for the presence of any abnormal flame signals.
At the end of the pre-ventilation time
- the ignition is switched on
- the main and safety solenoid valves are opened.
- burner start-up
Monitoring
The flame is monitored by an ionisation probe. The probe is fitted with insulation to the gas head and is routed through the turbulator into the flame zone. The probe must not have any electrical contact with earthed parts. The burner switches to malfunction if a short circuit occurs between the probe and the burner earth. During burner operation, an ionised zone is produced in the gas flame through which a rectified current flows from the probe to the burner tip. The ionisation current must be at least 8µA.
Safety functions
- If no flame is produced when the burner is started (gas release), the burner is switched off at the end of the safety time which lasts no more than 3 seconds and the gas valve closes.
- If the flame is lost during operation, the gas supply is cut within a second. A new start-up sequence is activated. If the burner starts, the operating cycle starts running. Otherwise a lockout occurs.
- If there is an air failure during pre­ventilation or operation, a lockout occurs.
- If there is a gas failure, the burner either stops or will not start. As soon as sufficient gas pressure is available again, the burner restarts.
During the regulator shutdown
- The control thermostat interrupts the heat request.
- The gas valves close
- The flame goes out
- The blower motor stops
- The burner is ready for operation
CH note
In accordance with SSIGE instructions, it is compulsory to install a gas safety valve (mark 1) in the pipe
DE Note
In compliance with the reference layout applicable to boiler rooms, sites with gas furnaces must be fitted with a thermal gas shut-off valve (1).
F4 Gas pressure switch F6 Air pressure switch Y12 Safety solenoid valve Y13 Main solenoid valve 1 Thermal shut-off valve (to be
installed by the installer) 104 Gas pressure regulator 106 Screen 108 Gas cut-out valve (to be installed
by the installer) 119pBrGas pressure measuring point at
the valve outlet
119.1Gas pressure measuring point
upstream of the valves
119.2Air pressure measuring point pF Furnace pressure pG Gas pressure at the head pL Air pressure
Page 5
03/2013 - Art. Nr. 4200 1032 7200A 5
en
Screen Description Screen Description
Awaiting the heat request from
the boiler
Opening the gas valve and
safety time
Air flap is forced open for pre-
ventilation.
Flame is present, awaiting authorisation of regulation
Pre-ventilation
Burner in operation. The lower
cell shows the strength of the
signal and the operating time of
the burner.
Closing the air flap to the ignition
position, pre-ignition
Operation
TCG 5xx control unit
The TCG 5xx control and safety unit controls and monitors the forced draught burner. The microprocessor-controlled program sequence ensures maximum stability of time periods, regardless of fluctuations in the power supply voltage or the ambient temperature. The automatic combustion control unit is designed to cope with brownouts. Whenever the supply voltage drops below its rated minimum level (< 185V), the control unit shuts down - even in the absence of a malfunction signal. The control unit switches itself back on again once the voltage has returned to normal levels (> 195V).
Pressing the unlocking button on the unit for
… causes …
... 1 second ... the control unit to
unlock.
... 2 seconds ... the control unit to
lock.
... 9 seconds ... the statistics to
be deleted
Locking and unlocking
The control unit can be locked (switched to malfunction mode) by pressing the unlocking button and unlocked (fault deleted), provided the unit is connected to the mains power supply.
Always switch off the power supply before installing or removing the control unit. Do not attempt to open or carry out repairs on the control unit.
Moves the cursor upwards.
Moves the cursor downwards.
Increases the marked value.
Reduces the marked value.
Modifies/Confirms the value
shown.
Unlocks the control unit.
Red LED (flashes if a fault is
present).
Page 6
03/2013 - Art. Nr. 4200 1032 7200A6
• menu for setting the servomotor,
• menu for storing the servomotor setting points in the display
• menu for consulting faults
• menu for statistical data
Fonctionnement
Coffret de sécurité TCG 5xx
In parallel with its control and safety functions, the TCG5xx control unit allows the following to be set: (see illustration)
- the position of the air flap during ignition
- the position of the air flap at minimum pressure
- the position of the air flap at maximum pressure
The parameters for the control unit are set using the display and 5 keys. Operating values are shown in real time on the display.
Pressing the keys gives access to 7 menus: (
The menu on the bottom right is not
activated in VG4.460 DP
and
VG4.610
DP burners
)
• menu for setting/ adjusting the standard configurations*
• menu for setting industrial applications*
• menu for manual control*
* In these menus, it is
possible to adjust the control unit's standard configurations. These are pre-set in the factory. No modifications may be carried out on-site without prior consultation with ELCO. The access code and the setting setpoints for these menus are available on request.
Page 7
03/2013 - Art. Nr. 4200 1032 7200A 7
en
Operation
TCG 5xx control unit
Operating cycle phases:
1: No voltage 2: Powering up, no heat request 3: Heating request 4: Opening an air flap, arrival in pre-
ventilation position
5: Checking the rest status of the air
pressure switch
6: Pre-ventilation: energizing of the
motor, checking the air pressure 7: Pre-ventilation 8: Air flap closes to the ignition position 9: Switching on the igniter, unauthorised
flame monitoring 10:Opening of the solenoid valve, flame
formation, safety time: max. 3 s. 11:Awaiting regulator release 12:Opening the air flap, until the
maximum output is reached
13:Closing of the air flap until the
minimum regulation position is reached
14:Operation at intermediate regulation
power
15:Operation at minimum regulation
power
16:Regulator shutdown, closure of the
air flap
17:Awaiting a new heating request
Page 8
03/2013 - Art. Nr. 4200 1032 7200A8
Operation
Terminal allocation chart 230 Volt connection
Earth
Flame check
Fault display
Air pressure switch
Igniter
Burner motor
Connector
Terminal
Terminal
Connector
Remote unlocking
L1 power supply
Solenoid valve
Control
thermostat
Heating request
Earth
Gas pressure switch
Terminal Description Connector Terminal Description Connector
1 Burner motor live
4
20 Minimum output thermostat live (T1)
19
2 Earth 21 Heating request signal (option T2) 3 Neutral 22 Flame monitoring signal
11
4 Solenoid valve live
2
23 Earth 5 Neutral 24 Live 6 Earth 25 Air pressure switch signal
10
7 Solenoid valve live 26 Live 8 Live 27 Live
20
9 Live L1
6
28 Remote unlocking signal
10 Earth 29 Neutral
21
11 Neutral 30 Signal fault live 12 Earth 31 Live
8
13 Earth 32 Live 14 Igniter live
5
33 Not used
34
15 Earth 34 Not used 16 Neutral 17 Control thermostat live
T6/7/8
18 Signal T7 19 Signal T8
Page 9
03/2013 - Art. Nr. 4200 1032 7200A 9
en
Operation
Terminal allocation chart Low voltage connections
Display-PC interface
Air servomotor
Connector
Terminal
Terminal
Connector
Terminal Description Connector Terminal Description Connector
1 not used
30
18 not used
14
2 not used 19 not used 3 not used 20 not used 4 not used
27 28 29
21 not used 5 not used 22 not used 6 not used 23 not used 7 not used 24 not used
33
8 not used 25 not used 9 not used 26 not used
32
10
Display or PC interface
16
/
17
27 not used
11 28
Air servomotor
15
12 29 13 30 14 31 15 32 16 33 17
Page 10
03/2013 - Art. Nr. 4200 1032 7200A10
Operation
MB-VEF gas train
The MBVEF compact gas valve assembly is a combination of filter, gas/ air ratio regulator, valves and a pressure switch:
- Screen with 0.8mm mesh
- GWA5 pressure switch
- Servo-pressure control part with adjustable ratio V, correction of the zero point offset N and furnace pressure connection.
- V1 and V2 fast-opening and closing solenoid valves
Technical data
Input pressure 360 mbar max. Ambient temperature -15 to +70°C Voltage 230 V/ 50 Hz Max. Absorbed output 50 VA Protection rating IP 54
1 Electrical connection of solenoid
valves (DIN 43650)
2 Electrical connection of the
gas pressure switch (DIN 43650) 3 Gas pressure switch 4 Inlet flange 5 Pressure measuring nipple
R1/8, upstream of filter (option) 6 Filter (under the cover) 7 Connection for furnace pressure
release pipe pF, R1/8 8 Adjusting screw for V ratio 9 Adjusting screw for zero point
offset N 10 Connection for pressure pipe pL,
R1/8 11 Connection for pressure pipe pBr,
R1/8 12 Outlet flange 13 Pressure take-off pipe pBr
Page 11
03/2013 - Art. Nr. 4200 1032 7200A 11
Ø a Ø b c d
190-240 200-270 M10 45°
en
Assembly
Burner assembly
Preparing the boiler front
• Prepare the burner mounting plate/ boiler door in accordance with the diagram.
• Establish the internal diameter a of 190-240 mm.
• To mount the burner head bracket, drill four M10 holes (drill diameter 200 to 270 mm) as shown in the diagram opposite.
Burner head assembly
• Screw the bolts into the burner fixing plate/boiler door and position the insulation material. For a drill hole of < 270 mm, elongated slots should be cut to the required dimensions.
• Remove the combustion components from the head
• Attach the burner head with 4 nuts (ref. 4). At this point, check that the gas connection flange is correctly positioned (on the left or right).
Burner tube installation depth and brickwork surround
Unless otherwise specified by the boiler manufacturer, heat generators without a cooled front wall require brickwork or insulation 5 as shown in the illustration opposite. The brickwork must not protrude beyond the leading edge of the flame tube, and should have a maximum conical angle of 60°. Space 6 must be filled with an elastic, non-flammable insulation material. The furnace pressure take-off pipe pF
must not be clogged.
Exhaust gas evacuation system
To avoid unpleasant noise emissions, right-angled connectors should not be used on the flue gas side of the boiler.
Fitting the burner body
• Remove the cover (2 screws W).
• Unscrew the two screws Z on the burner body completely.
• Bring the burner body into contact after having swivelled it at least 15° to the left.
• Engage the two screws Z on the body into the two lugs provided.
• Tighten the 2 screws.
For assembly in the position with
the volute facing upwards, unclip the display, turn it over 180°, and refit it.
On boilers with reverse firing, minimum flame tube insertion depth A should be observed as per the boiler manufacturer's instructions.
Page 12
03/2013 - Art. Nr. 4200 1032 7200A12
Gas train assembly
• Check the correct position of the O-ring B in the gas connecting flange C.
• Secure the gas train on the burner head so that the gas train coils are in the upper vertical position.
• Pay attention to the direction of circulation.
• Connect the power cable to the gas train.
Assembly
Gas manifold Pressure take-off pipes
Connecting pressure take-off pipes pF and pL
• Connect the furnace pressure take-off
pL on the burner body and the union pL on the gas train using the flexible
tube pL (blue), shorten the tube depending on the assembly scenario.
• Connect the furnace pressure take-off
pF on the burner body and the union pF on the gas train using the flexible
tube pF (grey), shorten the tube depending on the assembly scenario.
• Manually screw in the unions (max. 5 Nm) and check tightness.
Page 13
03/2013 - Art. Nr. 4200 1032 7200A 13
en
Checking the burner head
• Check the adjustment settings of the ionisation probe and of the ignition electrode as per the diagrams.
Setting to liquid gas operation
• Remove the gas diffuser 5 and the turbulator 2.
• Remove adaptor 3.
• Fit the adaptor 6 (supplied with the housing) on the gas burner head.
• Turn the gas diffuser 5 180° and refit it.
• Refit the turbulator 2 and the 3 spacers
4, using the 3 new screws 1 provided.
Assembly
Checking/adjusting the burner head
Check the radial position of the flame tube
After untightening the three mounting screws S, it is possible to change the position of the flame tube using the lever H. Nitrogen oxide emissions may be affected by the radial position of the flame tube
• To be set at the start to position 1.
Fitting the combustion components
• Check that the O-Ring J1 is in the correct position in the gas elbow.
• Insert the combustion components into the head, tighten the mounting screw X using an Allen key, then tighten the lock nut using an open­ended spanner.
• Thread the ionisation cable IK and the ignition cables ZK into the grommets R and S.
• Remove the cover.
Page 14
03/2013 - Art. Nr. 4200 1032 7200A14
Ionisation current measurement
To measure the ionisation current, disconnect connector B10 and connect a multimeter with a measuring range of 0-100 µA. The ionisation current must be at least 8 µA. It is also possible to read the ionisation current on the display.
All electrical installation and connection work must only be carried out by a suitably qualified electrician.
The applicable guidelines and directives must be observed, as well as the electrical circuit diagram supplied with the burner!
Electrical connection
• Check to ensure that the power supply is as specified (230V, 50 Hz single phase with neutral and earth)
Boiler fuse: 6.3 A
The burner motor has its own separate power supply (no. 3).
Fuse on the motor circuit: 6 A gM
Electrical connection
It must be possible to disconnect the burner from the mains using an omnipolar shutdown device complying with the standards in force. The burner and heat generator (boiler) are connected by a 7-pin connector 1 and a 4-pin connector 2 (not supplied). The diameter of the cables connected to these connectors must be between 8.3 and 11 mm.
Connecting the gas train
Connect the gas train to the plugs on the burner (black to black, grey to grey).
Assembly Gas connection
Electrical connection Checks before commissioning
General regulations applying to the gas connection
• The gas train must only be connected to the gas mains by a recognised specialist.
• The cross-section of the gas line should be of a size designed to guarantee that the gas flow pressure does not drop below the specified level.
• A manual shut-off valve (not supplied) must be fitted upstream of the gas train.
• In Germany, a thermally triggered shut-off valve (to be installed by the customer side) must be fitted as
specified by the draft combustion
ordinance. It is the responsibility of the fitter or his representative to obtain approval for the system at the same time as the burner is commissioned. Only the fitter or his representative can guarantee that the system meets applicable standards and regulations. The fitter should be in possession of the corresponding official permit, and should carry out the corresponding sealing tests and purge the system of air.
Checks before commissioning
The following must be checked before initial commissioning:
• That the burner is assembled in accordance with the instructions given here.
• That the burner is pre-set in accordance with the values in the adjustment table.
• Setting the combustion components.
• The heat generator must be ready for operation, and the operating regulations for the heat generator must be observed.
• All electrical connections must be correct.
• The heat generator and heating
system must be filled with water and the circulating pumps must be in operation.
• The temperature regulator, pressu re regulator, low water detectors and any other safety or limiting devices that might be fitted must be connected and operational.
• The exhaust gas duct must be unobstructed and the secondary air system, if available, must be operational.
• An adequate supply of fresh air must be guaranteed.
• The heat request must be available.
• Sufficient gas pressure must be available.
• The fuel supply lines must be assembled correctly, checked for leaks and bled.
• A standard-compliant measuring point must be available, the exhaust gas duct up to the measuring point must be free of leaks to prevent anomalies in the measurement results.
Page 15
03/2013 - Art. Nr. 4200 1032 7200A 15
en
Commissioning
Adjustment data
The adjustment values above are guide values and facilitate commissioning.
The factory settings are in bold set against a grey background The final settings are essential in ensuring that the burner functions as well as possible
Setting the gas pressure switch
• Remove the transparent cover.
• Provisionally set to 15 mbar.
Setting the air pressure switch
• Remove the transparent cover.
• Provisionally set to 1 mbar.
Mini. Maxi. Ignition Mini. Maxi. G20 G25 G20 G25 G31 G20 G25 G31
100 200 15 2
5525 - -
1,2 / 0 1,4 / 0 1,2 / 0 1,7 / -0,5 1,7 / 0 1,5 / 0
200 300 20 3 20 20 40 - -
1,2 / 0 1,5 / 0 1,2 / 0 1,7 / 0 2 / 0 1 ,5 / 0 300 4 00 30 4 20 30 90 - - 1,2 / 0 1,5 / 0 1,2 / 0 1,7 / 0 2 / 0 1,5 / 0 186 371 30 3 7 13 15 40 1,5 / -0,3
1,7 / -0,5 1,4 / 0
1,5 / 0 1,5 / -0,5
1,5 / 0 1,7 / 0,5 1 ,5 / 0
224 446 30 4 2 13 20 52
1,5 / -0 ,3 1,7 / -0,5 1,4 / 0 1,5 / 0 1,5 / -0,5 1,5 / 0 1,7 / 0,5 1,5 / 0
260 521 40 4 7
13 21 90 1,5 / -0,3 1,7 / -0,5 1,4 / 0
1,5 / 0 1,5 / -0,5
1,5 / 0 1,7 / 0,5 1 ,5 / 0
Furnace
pressure
pF
(m bar)
MB-VEF420 MB-VEF412
Gas valve setting
Screw V / Screw N
VG 4.460
DP
VG 4.610
DP
A ir flap se tting
MB-VEF40
7
Burner
power
Dimension
Y
(mm)
Page 16
03/2013 - Art. Nr. 4200 1032 7200A16
Commissioning
Air regulation Gas valve adjustment
Air regulation
Combustion air is regulated at two points:
• on the pressure side, using the gap between the turbulator and the burner tube.
• on the vacuum side, by the air flap driven by servomotor Y10.
The regulation of air in the burner head affects not only the air flow but also the mixing zone and the air pressure in the burner tube. Turning screw A
- right: more air
- left: less air
• Adjust dimension Y in accordance with the settings table.
Air regulation by air flap
Air is regulated on the vacuum side by an air flap. This is driven by servomotor
Y10.
Gas valve adjustment
V Setting the maximum power N Setting the minimum power
- For more CO2 turn upwards on the scale.
- For less CO
2
turn downwards on the
scale.
Page 17
03/2013 - Art. Nr. 4200 1032 7200A 17
en
Commissioning
Pre-setting without flame
Setting is carried out in 2 phases:
- pre-adjustment without flame
- setting the flame, to fine tune the settings based on the combustion results
When the burner is switched on, the control unit displays the screen below.
Important
At this point, no setting position for the servomotor has been defined, therefore the burner cannot be started under these conditions.
• For the next step, press any button.
The overall view of the menus is displayed, and the air flap positions settings menu is selected.
• Open the settings menu by pressing the key.
You must now enter the access code (see the label on the back of the display)
• Increase or decrease the value in increments by repeatedly pressing or
.
• When the first figure has been set, move the cursor to the right by pressing .
• Repeat the operation until you reach the last figure.
• Confirm the access code by pressing
The control unit then opens the settings mode. The screen displays the factory pre­settings for the different positions of the air flap (here for example: for a VG4.460 DP).
The following positions for the air flap are presented:
- ignition position (when the menu is opened, the curser goes to this position)
- the position of the air flap at minimum pressure
- the position of the air flap at maximum pressure
Modifying a settings value for the servomotor position:
- To modify the value of a position, move the cursor to the corresponding location with the or key.
- Select the value to be modified using the key, the selected value will flash.
- Increase or decrease the value in increments of 0.1° by repeatedly pressing or . For large modifications, press and hold the or key the value will scroll quickly up or down.
- Confirm the new value using the key. The value stops flashing.
Page 18
03/2013 - Art. Nr. 4200 1032 7200A18
Commissioning
Pre-setting without flame General advice before starting the burner
End of presetting menu without flame
When all the positions of the servomotor have been determined according to the required settings, it is then possible to move on to the next section for commissioning - "Setting the flame".
To do this, place the cursor in the lower part of the screen on the symbol and confirm by pressing the key.
If it is necessary to quit the menu without saving the pre-settings, position the cursor on the symbol and confirm with the key.
Optimising combustion values
Optimum combustion values can be achieved by adjusting the position of the turbulator (dimension Y) if necessary. Doing this can have an effect on starting characteristics, pulsation and combustion values. Any reduction in dimension Y increases the CO
2
value. However, starting characteristics become harsher. Compensate for the change in airflow if necessary by adjusting the air flap position.
Precautions: To avoid condensation, observe the minimum required flue gas temperature specified by the boiler manufacturer and com ply with the requirements for flue gas ducts.
Risk of deflagration Continuously check CO, CO
2
and soot emissions when adjusting. Optimise combustion values if CO is present. The CO level must not exceed 50 ppm.
Function check
Flame monitoring must be checked for safety as part of initial commissioning and also after servicing or if the system has been out of operation for any significant period of time.
- Starting attempt with gas valve closed: once the safety time has elapsed, the control and safety unit should indicate a lack of gas or switch to malfunction mode.
- Starting with the air pressure switch closed: after an 8-second test period, the burner switches to malfunction mode.
- Starting attempt with air pressure switch open: after a 60-second waiting period, the control and safety unit locks.
- Starting attempt with brief opening of the air pressure switch during pre­ventilation: the control and safety unit restarts the pre-ventilation programme (air pressure detected again within 60 seconds) ; otherwise a lockout occurs.
Page 19
03/2013 - Art. Nr. 4200 1032 7200A 19
en
Commissioning
Setting the flame
- If the boiler heating request is not present, the boiler
remains on standby.
In this case, it is still possible to return to the previous setting menu "Pre-setting without flame". To do this, position the cursor on the symbol and confirm with the key.
- If a boiler heating request is present (T1-T2 contact closed), the burner starts.
The air flap is opened to move to the pre-ventilation position.
Air pressure switch test
Pre-ventilation
The air flap switches to the ignition/pre-ignition position.
The fuel valve opens. Awaiting flame signal
If no flame is detected at the end of the safety time, the
control unit switches to malfunction mode.
If the flame is detected Flame stabilisation The control unit awaits the
regulation authorisation.
Page 20
03/2013 - Art. Nr. 4200 1032 7200A20
Commissioning
Setting the flame
Setting the minimum pressure
If the flame has been detected and stabilised, the control unit sets the burner to minimum power as soon as it receives the regulation authorisation.
- Check the combustion values (CO, CO
2
, soot test). If necessary, adjust screw N on the valve
(see page16).
- Read the ionisation current value.
- Read the gas flow rate on the gas counter.
Modification of the air flow via the "manual output control"
The "manual output control" function allows the burner output to be modified. To do this, position the cursor on the corresponding line on the display and confirm with th e key. It is then possible to adjust the burner output upwards or downwards using the , keys.
The servomotor reacts in real time. This is why the combustion values must be continuously
monitored.
Setting the maximum output
Slowly increase the burner to the maximum output using the "manual power control" function. At this point, adjust the gas flow using the regu l a to r V on the gas train. The preset limit values for the minimum output and the maximum output cannot be exceeded. If necessary, exit the "manual output control" function again using the key and modify the limit value for the maximum or minimum output.
Definitive limitation of the maximum output position
Limit the maximum opening of the air flap according to the position determined for the maximum output. In this example, the new position determined for the maximum output is below the value set manually. Using the "manual output control" function, it is now possible to reduce the burner output, but this cannot be set above the new maximum position, which here is 50°.
Definitive limitation of the minimum output position
Using the "manual output control" function, reduce the burner output to the minimum output. If necessary, limit the minimum output position, in the same way as for the maximum output.
Specific function: ignition checking
If the ignition position has been modified, it is possible to carry out a new burner start-up to check the new ignition position, without having to quit the settings menu. To do this, after modifying the ignition position, position the cursor on the symbol, and initiate the new start-up using the key.
Page 21
03/2013 - Art. Nr. 4200 1032 7200A 21
en
Commissioning
Setting the flame Operating mode
Closing the "Setting the flame" menu
The burner setting is now complete. If necessary, it is possible to again correct each of the settings values. To do this, position the cursor on the value to be modified, using the or key.
Otherwise, at any point, there are 3 possible ways of closing the "Setting the flame" menu, as follows:
- either restart the burner setting procedure, passing through the pr esetting phase (without entering a password). To do this, position the cursor on the symbol and confirm with the key. All the settings values already saved therefore remain available. This is essential for testing a new ignition position.
- or: Save the fixed values and end the setting procedure. To do this, position the cursor on the symbol and confirm with the key . The burner is then ready to operate and can now be controlled by the boiler regulation.
- or: Quit the settings menu without reaching the end of the setting procedure. To do this, position the cursor on the symbol and confirm with the key . All the servomotor positions saved up to this point are recovered by calling up the settings menu again.
Operating mode - Display of the operating status, the flame signal and the operating time
After setting of the burner has been completed, it switches to operating mode. The burner's instantaneous operating status (operation at minimum or ma ximum power) is
shown by the cursor. The lower cell shows the intensity of the signal. The display range is from 0 µA to 13 µA. A good
quality signal is above 8µA. The following limit values are valid:
• When checking an unwanted flame: the signal must be < 0.7µA
• During the safety time: the signal must be > 1.0µA
• During operation: the signal must be > 8µA
The cell at the bottom right displays the current operating time of the burner.
Page 22
03/2013 - Art. Nr. 4200 1032 7200A22
Commissioning Setting the gas pressure switch
Setting the air pressure switch Saving the adjustment values in the display
Setting the gas pressure switch
• To set the switch-off pressure: remove the cover from the gas pressure switch.
• Install a gas pressure pBr measuring instrument.
• Start the burner. Switching to maximum power.
• Reduce the pressure upstream of the gas train by gradually closing the manual valve, until
- the gas pressure pBr upstream of
the gas train drops
- the stability of the flame is reduced
- the CO level increases
- or the flame signal deteriorates
considerably
• Turn the dial clockwise until the gas pressure switch shuts down the burner.
• Continue turning the dial clockwise to set the gas pressure switch to 10% above the shutdown value determined above.
Checking the switch-off pressure
• Open the manual shut-off valve
• Start the burner
• Close the manual shut-off valve
The gas failure procedure should start without the control unit locking.
Setting the air pressure switch
• Install a pressure measuring device. To do this, install a T union in the air tube.
• Set the burner to its maximum operating power.
• Set the switch-off point to approximately 15% below the switch­off pressure read.
Saving the adjustment values in the display
If the burner setting procedure has been successfully completed, the servomotor positions for all the operating states will be fixed in the control unit. A back-up copy of the values is therefore stored in the display. In order to visualize them, press the button , the screen opposite is displayed. Using the button select the menu "Save adjustment values" and confirm with the button .
The screen opposite appears. The adjustment data have been stored in the display.
At this point, it is possible to exit the menu in one of two ways:
- positioning the cursor on the symbol and confirm with the button.
- using the symbol.
Page 23
03/2013 - Art. Nr. 4200 1032 7200A 23
en
Work recommended as part of annual burner maintenance:
- Burner test run, input measurement in the boiler room
- Clean the combustion components and replace defective parts if necessary
- Clean the fan wheel and the blower
- Clean the gas filter; replace it if necessary
- Visual inspection of the burner's electrical components; eliminate malfunctions if necessary
- Check burner start characteristics
- Leakage test
- Burner safety devices function check (air pressure/gas pressure switches)
- Flame monitor and automatic combustion control unit function check
- Commissioning the burner
- Check the gas flow
- Correct the adjustment values if necessary
- Draw up a measurement report
General checks
- Emergency stop button function check
- Visual inspection of gas lines in the boiler room
Servicing
Maintenance
Burner and boiler servicing must on ly be carried out by a professional heating engineer trained in these operations. The system operator is advised to take out a maintenance contract to guarantee regular servicing. Depending on the type of installation, shorter maintenance intervals may be necessary.
• Before all maintenance and cleaning work, switch off all electrical power
supplies (7P socket + separate motor power supply).
• Use original spare parts.
Checking the combustion components
• Remove the burner hood.
• Remove the two screws W from the cover.
• Remove the combustion components.
• Check the ignition electrodes and the ignition cables; replace if necessary.
• Clean the turbulator.
• Check adjustments and settings during assembly.
Removing the plate
• To do this, unscrew but do not remove the 2 screws
X
securing the motor plate.
• Turn the plate (bayonet system), carefully remove it and hang it in the maintenance position (see illustration).
• Clean the housing, fan wheel and recirculation unit, and check that they are not damaged.
• If necessary to clean it, remove the air recycler; to do so, remove the screw Z then unclip it.
• Clean the turbine and check it is not damaged.
Fitting the fan wheel
When changing the motor or the fan wheel, refer to the positioning diagram opposite. The internal flange A of the fan wheel must be aligned with plate B. Insert a ruler between the vanes of the fan wheel and bring A and B to the same height. Tighten the cone-point screw on the fan wheel.
Page 24
03/2013 - Art. Nr. 4200 1032 7200A24
Servicing
Maintenance
Replacing the flame tube
For this operation, it is necessary to either open the furnace gate or remove the burner.
- Variant 1 - Access via the furnace gate
• Remove the burner head
• Loosen the 3 securing screws S on the flame tube support by 1 to 2 turns. (Allen 3).
• Open the combustion chamber door.
• Take out the flame tube, check it, clean it and, if it is deformed, replace it.
• Proceed in the reverse order for refitting.
• Fill in the space between the furnace gate and the burner tube with fire­resistant material.
• Close the furnace gate.
- Variant 2 - Removing the burner
• Remove the burner head.
• Loosen the electrical connections.
• Loosen the burner housing (2 M8 screws) and remove. Do not damage electrical cables.
• Unscrew the burner head and then proceed as under variant 1.
• Proceed in the reverse order for refitting.
The flame tube may be hot
Filter replacement
• The filter element of the multiblock must be checked at least once a year and replaced if clogged.
• Loosen the screws of the filter cap on the multiblock.
• Remove the filter element and clean its housing.
• Do not use any pressurised cleaning products.
• Replace the filter element with a new element.
• Screw the cover back into place.
• Reopen the manual shut-off valve.
• Check it is airtight.
• Check the combustion values.
Cleaning the air box
First check that the air flap is in the closed position (0°), before removing it (2 screws V).
• Unscrew the three securing screws T in the base of the housing by a few turns.
• Shift the air intake box 113 to the right to release the screws (bayonet).
• Remove the air intake box, clean it and refit it in reverse order.
• Check that the air flap and the servomotor are correctly positioned.
Cleaning the cover
• Do not use abrasive products or products containing chlorine.
• Clean the cover with water and a suitable cleaning product.
• Refit the cover.
Precautions After any operation: check the combustion performance under real operating conditions (doors shut, cover fitted etc.). Record the results in the relevant documents.
Checking the flue gas temperature
• Check the flue gas temperature at
regular intervals.
• Clean the boiler if the flue gas
temperature is more than 30 °C abov e the value measured at the time of commissioning.
• Use a flue gas temperature gauge to
make the check easier.
Page 25
03/2013 - Art. Nr. 4200 1032 7200A 25
en
Servicing
Troubleshooting
Malfunction diagnosis and repair
In the event of a malfunction, first check that the prerequisites for correct operation are fulfilled:
1. Is there any current?
2. Is there gas pressure?
3. Is the gas shut-off valve open?
4. Are all control and safety devices, such as the boiler thermostat, low water detector, limit switches, etc. correctly set?
If the fault is still present, check that each of the burner components is operating. Important safety components must not be repaired; these components must be replaced by parts with the same part
number.
Only use original spare parts. Switch off the power supply before carrying out maintenance or cleaning.
After any work on the system:
• Under normal operating conditions (doors closed, cover fitted, etc.), check combustion and check the individual lines for leaks.
• Record the results in the relevant documents.
Symbol Observation Cause Corrective action
Burner does not start after thermostatic closure. No malfunction indicated on the control and safety unit.
Drop in supply voltage or power failure.
Control unit malfunction.
Check the cause of the drop in voltage or the power failure.
Replace the control unit.
No heat requested. Thermostats defective or
incorrectly adjusted
Adjust the thermostats, replace if necessary.
The burner starts briefly when switched on, then switches off and the red indicator light comes on.
The control unit has intentionall y been manually locked.
Unlock the unit.
Burner does not start. Air pressure switch: not in rest
position. Incorrect adjustment
Contact welded
Readjust the pressure switch. Check the wiring. Replace the pressure switch.
Burner does not start. Gas pressure normal
Insufficient gas pressure. Gas pressure switch wrongly set or
defective
Check the gas lines. Clean the filter. Check the gas pressure switch or replace the compact gas unit.
Page 26
03/2013 - Art. Nr. 4200 1032 7200A26
Symbol Observation Cause Corrective action
Burner blower starts up. Burner does not start.
Air pressure switch: Contact does not close.
Readjust the pressure switch. Check the wiring. Replace the pressure switch.
Burner blower starts up. Burner does not start.
Flaring during pre-ventilation or pre-ignition.
Check the valve. Check flame monitoring.
The burner starts, the ignition switches on, then failure
No flame at the end of the safety time.
Gas throughput set incorrectly. Malfunction in flame monitoring system
Incorrect polarisation (live/neutral position) of the power supply on the 7P connector/socket
No ignition sparks. Electrode(s) short-circuited.
Ignition cable(s) damaged or defective.
Igniter defective. Control and safety unit
Solenoid valves do not open. Valves jamming.
Adjust the gas flow stage Check the condition and position of the ionisation probe in relation to earth. Check the condition and connections of the ionisation circuit (cables and measurement bridge).
Check that the polarisation of the 7P connector is correct.
Adjust, clean or replace the electrodes.
Connect or replace the cable(s).
Replace the igniter. Replace the control unit. Check the cabling between the control unit and external components.
Replace the compact gas unit.
Replace the valves. The burner switches off during operation.
Air pressure switch: contact opens during start-up or during operation.
Flame failure during operation.
Adjust or replace the pressure
switch.
Check the ionisation probe circuit
Check or replace the control and
safety unit.
Servomotor fault Clogging of the air flap
Locking of the air flap Internal fault with the servomotor
Replace the servomotor
Servicing
Troubleshooting
Page 27
03/2013 - Art. Nr. 4200 1032 7200A 27
en
Servicing
Fault diagnosis menu Operating statistics menu
Fault diagnosis menu
To access the fault diagnosis menu, press any key when the burner is ready to operate, when the burner is in operation, or when it is in malfunction mode. It is not possible to access the fault diagnosis menu during the start-up phase. The general menu screen will appear. Using the , , , or key, place the cursor on the fault diagnosis menu symbol, and confirm using the key.
The details of the last fault to appear are indicated by the flashing symbol. The flame intensity, network voltage, air flap position, number of burner start-ups as well as the operating time of the burner at the time it switched to malfunction mode are displayed underneath.
Using the keys and , it is possible to call up the details of the last 5 faults to have appeared (the fault number is displayed in the upper left corner of the display). After the details of the last 5 faults, the telephone number of the after-sales department as well as the maintenance contract number are shown (no values are entered in the factory).
• Quit the menu using the key.
Entering a telephone number for the maintenance company and the maintenance contract number
When the corresponding symbol appears on the display:
• Keep the key held down until the first figure starts to flash (a short press will exit the menu).
• Using the or key, change the figure to the required value (underscore = empty field)
• Using the key, move on to the next figure.
• When the number is complete, save using the key.
Operating statistics menu
To access the operating statistics menu, press any key, when the burner is ready to operate, when the burner is in operation, or when it is in malfunction mode. It is impossible to access the operating statistics diagnosis menu during the start-up phase. The general menu screen will appear. Using the , , , or key, place the cursor on the operating statistics menu symbol, and confirm using the key. The operating statistics menu comprises 7 screens. Navigation between the different screens is done using the keys and .
- Flame detection time for last start-up
- Average flame detection time for the last 5 start-ups
- Total number of burner start-ups
- Total number of faults
- Total number of operating hours
- Total number of operating hours at rated output
Page 28
03/2013 - Art. Nr. 4200 1032 7200A28
- Total number of burner start-ups since the last meter reset
- Total number of faults since the last meter reset
- Total operating time since the last meter reset
- Total number of operating hours at rated output since the last meter reset
Servicing
Operating statistics menu
- Number of "unwanted flame" faults
- Number of "No flame after safety time" faults
- Number of "Flame loss during operation" faults
- Number of "Air pressure switch stuck" faults
- Number of "Air pressure switch does not close during operation" faults
- Number of "Air pressure switch switching over" faults
- Number of "servomotor" faults
• Quit the menu using the key .
Page 29
03/2013 - Art. Nr. 4200 1032 7200A 29
Page 30
03/2013 - Art. Nr. 4200 1032 7200A30
Page 31
03/2013 - Art. Nr. 4200 1032 7200A 31
Page 32
03/2013 - Art. Nr. 4200 1032 7200A32
Made in EU. Non contractual document..
www.elco.net
Hotline
ELCO Austria GmbH
Aredstr.16-18 2544 Leobersdorf
+43 (0)810-
400010
ELCO Belgium n.v./s.a.
Industrielaan 61 1070 Anderlecht
+32 (0)2-
4631902
ELCOTHERM AG
Sarganserstrasse 100 7324 Vilters
+41 (0)848 808
808
ELCO GmbH
Dreieichstr.10 64546 Mörfelden-Walldorf
+49 (0)180-
3526180
ELCO Italia S.p.A.
Via Roma 64 31023 Resana (TV)
+39 (0)800-
087887
ELCO Burners B.V.
Amsterdamsestraatweg 27 1411 AW Naarden
+31(0)35-
6957350
OOO «Ariston Thermo RUS LLC»
Bolshaya Novodmitrovskaya St.bld.14/1 office 626 127015 Moscow -Russia
+7 495 213
0300#4128
Loading...