elco VG2.120 M/TC, VG2.160 M/TC, VG2.210 M/TC, VG 6.1600 M/TC, VG 6.2100 M/TC Original Operating Instructions

en
VG2.120 M/TC VG2.160 M/TC VG2.210 M/TC
Original operating instructions
For authorised specialist engineers
Gas burners ...........................................2-31
de, fr.....................................4200 1038 2500
............................................. 4200 1038 2400
09/2014 - Art. Nr. 4200 1038 2700A
Overview
Contents
Overview Contents .....................................................................................2
Operation Operation, safety function ..........................................................4
Assembly Burner assembly ......................................................................11
Commissioning Setting data ..............................................................................15
Maintenance Servicing............................................................................. 26-27
Important information
VG2.120/160/210 M/TC burners are designed for the low-pollutant combustion of natural gas and propane gas. The design and function of the burners meet standard EN
676. They are suitable for use with all heat generators complying with standard EN 303 or for use by hot air generators complying with standard DIN 4794 or DIN 30697 within their respective performance range. Any other type of application requires the approval of ELCO. Installation, start-up and maintenance must only be carried out by authorised specialists and all applicable guidelines and regulations must be complied with. This device is not designed for use by individuals (including children) whose physical, sensory, or mental abilities are reduced, or by persons lacking in experience or knowledge, except if they have benefited from supervision or prior instructions concerning the use of the device given by a person responsible for their safety. Children must be supervised to ensure they do not play with the device.
Burner description
VG2.120/160/210 M/TC burners are modulating, fully automatic, monoblock type burners with electronic cam. The special design of the combustion head enables combustion with low levels of nitrogen oxide and increased output. Class 3 type-approval in accordance with EN676 certifies that the lowest emission values have been achieved and means that the national environmental regulations have been met AT: KFA 1995, FAV 1997 CH: LRV 2005 DE: 1.BImSChV Emissions values may differ, depending on furnace dimensions, furnace load and the firing system (three-pass boilers, boilers with reverse firing). For specifying warranty values, the conditions for the measuring equipment, tolerances and humidity must be observed.
Important information .................................................................2
Burner description ......................................................................3
Control and safety unit BT 3xx ...................................................5
Terminal allocation chart ........................................................ 6-7
Control and safety unit BT 3xx gas operation ............................8
BT 3xx menu overview ...............................................................9
MBC-SE gas train.....................................................................10
Gas train...................................................................................12
Checking the combustion components ....................................13
Electrical connection ................................................................14
Testing before commissioning..................................................14
Ionisation current measurement ...............................................14
Air regulation, MBC SE gas train setting ..................................16
Pressure regulator setting ........................................................16
Confirming the "Manual Handshake" data................................17
Menu 1: setting the servomotors ....................................... 18-23
Pre-setting without flame.................................................... 18-19
Setting with flame ............................................................... 20-23
Operating mode........................................................................23
Setting the gas pressure switch/air pressure switch ................24
Displaying the setting data from the manual control display ....25
Menu 3: Fault memory, Entering a telephone number for the maintenance company and the
maintenance contract number............................................ 28-29
Menu 4: operating statistics......................................................30
Setting the brightness and contrast of the display....................31
Packaging
The burner is supplied in three packaging units:
- Burner housing with operating instructions, circuit diagram and spare parts list.
- Burner head with flange seal and securing screws.
- Compact gas train with integrated filter
The following standards should be observed in order to ensure safe, environmentally sound and energy-efficient operation:
EN 226
Connection of fuel oil and gas burners with blast air to the heat generator
EN 60335-1, -2-102
Specification for safety of household and similar electrical appliances, particular requirements for gas burning appliances
Gas lines
When routing the gas lines and fittings, the general installation instructions and guidelines, as well as the following national regulations, must be observed: CH: - G1 instruction text from SSIGE
- EKAS form no. 1942,
liquefied gas directive, part 2
- Cantonal authority guidelines (e.g.
directives for the pilot valve)
DE: - DVGW-TVR/TRGI
Installation location
The burner must not be used in rooms with aggressive vapours (e.g. hair spray, tetrachloroethylene, carbon tetrachloride), high levels of dust or high air humidity (e.g. laundry rooms). There must be a supply air inlet measuring: DE: up to 50 kW: 150 cm
for each additional kW: + 2.0 cm
CH: QF [kW] x 6= ...cm2; but 200 cm2
minimum. Variations may arise as a result of local regulations.
Page
Declaration of conformity
for gas burners
We, certified company under the name "Site A" declare under our sole responsibility that the products VG2.120 M/TC VG2.160 M/TC VG2.210 M/TC
conform to the following standards EN 50165 EN 55014 EN 60335-1 EN 60335-2-102 EN 60555-2 EN 60555-3 EN 676 Belgian royal decree dated 08/01/2004
These products bear the CE mark in accordance with the stipulations of the following directives 2006/ 42/EC Machinery Directive 2004/108/EC EMC Directive 2006/ 95/EC Low
Voltage Directive
92/ 42/EEC Efficiency Directive
Annemasse, June 1st 2012
F. DECIO
We accept no responsibility for damage arising from:
- inappropriate use
- incorrect installation and/or repair on the part of the buyer or any third party, including the fitting of non-original parts.
Final delivery and instructions for use
The firing system fitter must supply the operator of the system with operating and maintenance instructions on or before final delivery. These instructions should be displayed in a prominent location at the point of installation of the heat generator.They should include the address and telephone number of the nearest customer service centre.
Notes for the operator
The system should be inspected by a specialist at least once a year. Depending on the type of installation, shorter maintenance intervals may be necessary! It is advisable to take out a maintenance contract to guarantee regular servicing.
2
2
09/2014 - Art. Nr. 4200 1038 2700A2
Overview
en
Burner description
A1 Control and safety unit A4 Display F6 Air pressure switch M1 Blower motor T1 Igniter Y10 Air flap servomotor 3 Adjusting knob for dimension Y 4 Propane diffuser 5 Housing 6 Plate hanging device
(Maintenance) 8 Burner tube 10 7-pin connector
10.1 4 pin connector 16 Gas connecting flange 18 Cover 19 Release knob 20 Hood securing screw 113 Air intake box
09/2014 - Art. Nr. 4200 1038 2700A 3
Operation
Compact train
Operation Safety function
Description of functions
When first powering up, after a power cut or a lockout, after the gas supply has been cut or after a shutdown for 24 hours, a gas valve sealing test is performed before the burner is started, with the fan motor in operation. A pre­ventilation time of 24 seconds begins after the sealing test.
During the pre-ventilation time
- the air pressure is monitored
- a check is made for the presence of any abnormal flame signals.
At the end of the pre-ventilation time
- the ignition is switched on
- the main and safety solenoid valves are opened
- burner start-up
Monitoring
The flame is monitored by an ionisation probe. The probe is fitted with insulation to the gas head and is routed through the turbulator into the flame zone. The probe must not have any electrical contact with earthed parts. The burner switches to malfunction if a short circuit occurs between the probe and the burner earth. During burner operation, an ionised zone is produced in the gas flame through which a rectified current flows from the probe to the burner tip.
The ionisation current must be at least 8 µA.
Safety functions
- If no flame is produced when the burner is started (gas release), the burner is switched off at the end of the safety time which lasts no more than 3 seconds and the gas valve closes.
- If the flame is lost during operation, the gas supply is cut within a second. A new start-up sequence is activated. If the burner starts, the operating cycle starts running. Otherwise a lockout occurs.
- If there is an air failure during pre­ventilation or operation, a lockout occurs.
- If there is a gas failure, the burner either stops or will not start. As soon as sufficient gas pressure is available again, the burner restarts.
During the regulator shutdown
- The control thermostat interrupts the heating request
- The gas valves close
- The flame goes out
- The blower motor stops
- The burner is ready for operation
F4 Gas pressure switch F6 Air pressure switch Y12 Safety solenoid valve Y13 Main solenoid valve 1 Thermal safety valve (to be
installed by the fitter)
103.1 Gas throttle 106 Screen 108 Gas cut-out valve (to be
installed by the fitter)
119pBr Gas pressure measuring point
at the valve outlet
119.1 Gas pressure measuring point upstream of the valves
119.2 Air pressure measuring point
CH note
In accordance with SSIGE instructions, it is compulsory to install a gas safety valve (mark 1) in the pipe.
DE Note
In compliance with the reference layout applicable to boiler rooms, sites with gas furnaces must be fitted with a thermal gas shut-off valve (1).
09/2014 - Art. Nr. 4200 1038 2700A4
Operation
en
Control and safety unit BT 3xx
The control and safety unit BT 3xx controls and monitors the forced draught gas burner. The microprocessor­controlled program sequence ensures the maximum consistency of the cycle times involved, regardless of fluctuations in the mains voltage or ambient temperature. The control and safety unit is designed to detect power failures. Depending on the parameter assignment, the unit either switches to malfunction mode or goes into the standby position if the power supply falls below the mains voltage. In the standby position, there is an automatic restart as soon as the set threshold value is exceeded by 105%.
Pressing button
for ...
... 1 second ... the control and safety
... 2 seconds ... the control and safety
… causes ….
unit to unlock.
unit to lock
Manual locking and unlocking
Using the reset button , the control and safety unit can be locked manually (interlocked) or unlocked, provided the unit is connected to the mains power supply. This function must not be confused with automatic locking and fault acknowledgement in case of an error.
Before installing or removing the unit or any operation in the connection area, switch off the supply to the device, check for the absence of voltage and prevent any reactivation. Otherwise there is risk of electric shock. The control and safety unit must not be opened or repaired.
- Moves the cursor upwards
- Moves the cursor downwards
- Increases the marked value
- Moves the cursor to the right
- Reduces the marked value
- Moves the cursor to the left
Modifies/confirms the value shown
- Unlocks the control and safety unit
Red LED (flashes if a fault is present)
09/2014 - Art. Nr. 4200 1038 2700A 5
Operation
Air pressure
switch
Ignition
device
Terminal
Connector
Remote
unlocking
Solenoid valves
(1+2)
Heating request
Min. gas pressure
switch
Burner
safety circuit
Boiler safety circuit
Solenoid
valve 3
Flame check
Fault
display
Burner motor
Terminal
L1 power supply
Grounding of
the burner
UV detector
additional
Ionisation
Flame monitor
Connector
1 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 1 2 3 4
1 2 3
1 2 3
1 2 3
Pin
Pin
1 2 3 1 2 3
1 2 3
1 2 3 1 2 3 1 2
1 2
Terminal allocation chart
Pin Terminal Description Connector Pin Terminal Description Connector
1 1 Phase gas solenoid valve 1
2 2 Earth 1 30 Neutral conductor of the fuel-oil
3 3 Neutral conductor 2 31 Earth 1 4 Phase gas solenoid valve 2 3 32 Phase 2 5 Neutral conductor 1 33 Neutral conductor 3 6 Earth 2 34 Earth 1 7 Phase fuel valve 3 (optional) 2 8 Earth 1 36 Neutral conductor 3 9 Neutral conductor 2 37 Earth 1 10 Phase ignition transformer 2 11 Earth 1 39 Neutral conductor 3 12 Neutral conductor 2 40 Earth 1 13 Phase gas pressure switch min. 2 14 Earth 1 42 Neutral conductor 3 15 Phase 2 43 Earth 1 16 Phase burner safety circuit 2 17 Earth 1 45 UV flame monitor (-) 3 18 Phase 2 46 UV flame monitor (+) 1 19 Phase boiler safety circuit 2 20 Phase 2 48 Phase 1 21 Phase air pressure switch 2 22 Phase 4 50 Flame monitor (-) 1 23 Load (-) 2 24 Load (+) 3 25 Phase 1 26 Malfunction reset 2 27 Burner ON 3 28 Phase
X01
+
X02
X03 X04 X05
X06 X07
X08 X09
X10
1 29 Grounding of the burner
pump
3 35 Phase burner motor
3 38 Alarm output
3 41 L1 power supply
3 44 L1 power supply output
1 47 Ionisation probe
3 49 Flame monitor (+)
X26 X25
X24 X23 X22
X21 X20
09/2014 - Art. Nr. 4200 1038 2700A6
Operation
Terminal
Display
PC interface
Gas
servomotor
Air
servomotor*
Fuel oil
servomotor*
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Pin
Connector
en
Terminal allocation chart
Pin Terminal Description Connector
11 22 33 44 55 66 17 28 39 410 511 612 113 214 315 416 517 618 119 220 321 422 523 624 125 226 327 428 529 630
Display
PC interface
Servomotor gas
Servomotor air*
Servomotor fuel oil*
X30
X31
X32
X33
X34
* Terminal allocation depends on the design of the burner
09/2014 - Art. Nr. 4200 1038 2700A 7
Operation
Boiler safety circuit Gas safety circuit Burner on Minimum gas pressure swi t ch
Air pressure switch
Flame signal
Air flap
Gas flap
Transformer
Gas valve 1 Gas valve 2
Air motor Fault
Control and safety unit BT 3xx gas operation
Legend to the sequence diagram
t1 Awaiting boiler safety circuit
Air pressure switch min. request
t2 Time for pressure build-up in the gas control line (only
when sealing test mode is activated, program sequence for density test can vary, see sequence diagram for density test)
t3 Servomotor running time t4 Closing of gas flap t5 Ventilation time t6 Transformer activation time
Sealing test sequence diagram - no gas pressure at start of sealing test. Sealing test sequence diagram - gas pressure present at start of sealing
Legend to the sequence diagrams
t1 Ventilation time, always 2 seconds t2 Delay time, always 2 seconds t3 Sealing test time, configurable t4 Filling time, configurable
The diagrams on this page have been taken from the operating instructions of the BurnerTronic BT300 BT320 BT340 from Lamtec. Print no. DLT1200-11-aDE-002 Copyright© 2011 LAMTEC
t9 Safety time t10 Operating phase t11 Regulation t12 Time for pressure release in the gas control line t13 Postventilation time t14 Servomotors under base load t15 Post combustion time t16 Flame extinction test t17 Sealing test gas valve 2
test.
09/2014 - Art. Nr. 4200 1038 2700A8
Operation
en
BT 3xx menu overview
In addition to the function of control and safety unit, the control and safety unit BT 3xx also modulates the burner output by controlling the air flap, gas flap, fuel oil quantity regulation and frequency converter (optional) in one electronic circuit. The electronic circuit controls the opening of the gas flap and fuel oil flow regulation proportional to the air flap along a curve based on 10 setting points During start up, the setting points are defined based on the measurement values of the combustion gas analysis. This guarantees optimal combustion
• Menu 1: Setting the
• Menu 2: Display of the
over the burner's entire output modulation range. A separate burner ignition load can be defined with the "Ignition position" setting point . The limit values of the control range are defined by the min. output " " and max. output " " setting points. In addition, other optional functions, such as sealing tests, reventilation or waiting times can be activated. The combustion control unit is operated via a display and operating unit. The parameters for the control and safety unit are set using the display and 5 keys.
servomotors
setting points of the servomotors in the display unit
Operating values are shown in real time on the display. Pressing the keys gives access to 9 menus:
• Menu 6: Setting/ modification of configurations for industrial applications
• Menu 7: Manual mode
• Menu 3: Displaying faults
• Menu 4: Statistical data
• Menu 5: Setting/ modification of standard configurations
• Menu 8: Setting mode
- Menu 8 currently not available
• Menu 9: Setting the brightness and contrast of the display
In these menus, it is possible to adjust the standard configurations of the control unit. These are pre-set in the factory. The nearest customer service department must be contacted before any on­site modifications are made.
09/2014 - Art. Nr. 4200 1038 2700A 9
Operation
MBC-SE gas train
The gas train consists of:
- a gas connection flange 1 with O-ring
- a gas throttle 2, controlled by a
servomotor
- a gas connection pipe 3
- an MBC-SE gas valve train with gas
filter 4 (mini filter)
MBC SE gas valve
1 Electrical connection of solenoid
valves (DIN 43650)
2 Electrical connection of gas
pressure switch (DIN 43650) 3 Gas pressure switch 4 Gas inlet flange 5 Mini filter (under cover) 6 Gas pressure adjustment
screw pBr 8 Gas pressure measurement
tap G1/8 (inter-valve pressure) 9 Gas pressure measurement
tap G1/8 (outlet pressure pBr) 10 Gas pressure measurement
tap G1/8 (inlet pressure)
Installation position:
vertical with the coils facing upwards. Where the lines are vertical, the coils must be horizontal.
Description, technical data
The MBC-SE gas compact valve train is a compact unit with 2 Class A solenoid valves, a Class A servo pressure regulator, a mini filter and a pressure switch.
- Pressure switch GW A5: adjustment
range 5.....50 mbar
- Solenoid valve V1/V2 (fast-opening/ fast-closing)
- Adjustable servo pressure regulator
- Max. operating pressure 500 mbar
- Inlet pressure range 15-500 mbar
- Voltage/frequency: 230 V/50-60 Hz
Pressure regulator setting
The outlet pressure is set using adjustment screw 6.
09/2014 - Art. Nr. 4200 1038 2700A10
Loading...
+ 22 hidden pages