elco VECTRON G 05.700 MODULO, VECTRON G 05.1000 MODULO Operating Instructions Manual

Page 1
09/2005 - Art. Nr. 13 019 526A
Operating instructions
For the authorised specialist
Gas burners .........................................2-31
VECTRON G 05.700 MODULO VECTRON G 05.1000 MODULO
Ersatzteilliste Spare parts list Pièces de rechange Wisselstukkenlijst
Elektro- und Hydraulikschema Electric and hydraulic diagrams Schémas électr. et hydraulique Elektr. en hydraulische schema
Art. Nr.
13 018 839
EN
}
Art. Nr.
13 019 525
}
Page 2
2
09/2005 - Art. Nr. 13 019 526A
Contents
Overview
Contents, Declaration of
conformity ............................................2
Important notes .................................. 3
Description of burner, Scope of
delivery, Optional accessories.............4
Technical data, Power graphs ............5
Gas valve selection .............................6
Dimensional drawings and
measurements.....................................7
Gas valve assembly ............................8
Hydraulics diagrams ............................9
Control panel .....................................10
Overview of combustion control unit MPA22
Function description ..........................11
Display and operating unit ................12
Programme structure .......................13
Assembly
Burner head, burner housing ............14
Gas valve assembly ..........................15
Checking/Setting Mixer unit for
natural gas/propane gas....................16
Gas supply, Electrical supply............17
Start-up
Default settings..................................18
Burner head, gas and air pressure switch settings,
gas pressure regulator ......................19
Checks before start-up......................20
Control unit auto-test.........................20
Adjustment mode .........................21-25
Access....................................21
Parameters menu..............21-22
Cold adjustment menu ...........23
Hot adjustment menu........24-25
Operating mode .................................26
Info mode ..........................................27
Voice mode ....................................... 28
Maintenance................................ 28-29
Burner-specific adjustment
settings of the MPA 22 .....................30
Troubleshooting ................................31
Declaration of conformity for
gas burners
We, CEB, of 18, rue des Bûchillons Ville-la-Grand F-74106 ANNEMASSE Cedex declare under our sole responsibility that the products
VECTRON G 05.700 MODULO VECTRON G 05.1000 MODULO
conform to the following standards
EN 60335 EN 50081 EN 50082 EN 676
In accordance with the stipulations of the European Directives
90 / 396 / EEC Gas device guidelines 89 / 336 / EEC EMC directive 73 / 23 / EEC Low voltage
directive
92 / 42 / EEC Working efficiency
directive
these products bear the CE marking
Ville-la-Grand, 01 January 2005 J. HAEP
Overview
Page 3
3
09/2005 - Art. Nr. 13 019 526A
Overview
Important notes
Important instructions
The G 05.700/1000 MODULO burners are designed to burn natural gas or propane gas in category II 2 ELL 3P. The special construction of the burner head with internal recirculation of exhaust gases means that combustion is very low in nitric oxide when burning natural gas. The design and function of the burners meet standard EN676. Assembly, start-up and maintenance must be carried out only by authorised specialists and all applicable guidelines and regulations complied with. Gas pipes and fittings must likewise be installed in compliance with all applicable guidelines and regulations (e.g. DVGW-TRGI 1986/96; TRF 1988; DIN 4756). Only DVGW-tested and -approved sealing materials should be used. Connections should be leak-tested using non-corrosive foam-producing materials or similar. Gas piping should be vented before start-up. Under no circumstances should venting be carried out over the furnace. Repair work to switches, limiters, control and safety units and other individual items of safety equipment must be carried out by the relevant manufacturer or his representatives. The replacement of original parts must be carried out by specialist staff.
Basic regulations
The following standards should be observed in order to ensure safe, environmentally sound and energy-saving operation:
DIN 4705 Calculation of flue dimensions EN 676 Forced-draught gas burners EN 226 Connection to heating systems of vaporising-fuel-oil and forced-draught gas burners VDE 0116 Electrical equipment for furnace systems EN 60335-1 Safety of electrical equipment for domestic use and similar purposes VDE 0722 Electrical Equipment for non-electrically powered heating devices.
Installation location
The burner must not be used in rooms with aggressive vapours (e.g. hair spray, perchlorethelen, carbon tetrachloride), high levels of dust or high air humidity (e.g. washhouses). An air inlet must be present:
up to 50 kW: 150 cm²
for every further kW: +2 cm² Variations may arise as a result of local regulations.
The guarantee does not cover damage resulting from:
·
Inappropriate use
·
Incorrect installation and/or initial start-up on the part of the buyer or any third party, including the fitting of non-original parts.
·
Operation of the system at excessive pressure.
Final delivery and instructions for use
The combustion system manufacturer must supply the operator with operating and maintenance instructions on or before final delivery. These instructions should be displayed in a prominent location at the point of installation of the heating unit, and should include the address and telephone number of the nearest customer service centre.
Notes for the operator
The system should be inspected by a specialist at least once a year. It is advisable to enter into a maintenance contract in order to ensure trouble-free running.
EN
Page 4
4
09/2005 - Art. Nr. 13 019 526A
Overview
Description of burner
Burner description
The G 05.700/1000 MODULO burners are low emission, modulating gas burners with a monoblock type electronic connection. They are suitable for use with all heat generators in accordance with DIN 4702/EN 303 within the respective performance range.
Scope of delivery
The burner is supplied in three packaging units:
·
Burner housing with operating
instructions, flow diagram, spare parts
list, combustion chamber board.
·
Burner head with flange seal and
fixing screws.
·
Gas valve assembly with gas throttle
module, DMV gas valve with built-in
pocket filter or with external filter,
connection parts, screws, seals.
Optional accessories:
Separate air intake box
Air intake silencer
Gas stop valve
Thermal safety cut-out valve
Compensator
Power regulator
Potentiometer
Test burner
Pressure gauge
A1 Combustion control unit A4 Display and operating unit B10 Ionisation bridge F6 Air pressure switch F12 Protective motor relay K1 Motor contactor M1 Burner motor T1 Ignition transformer (concealed) Y10 Servomotor air flap 7 Control panel 8 Blast tube 13 Burner cover 113 Air box
Page 5
5
09/2005 - Art. Nr. 13 019 526A
Overview
Technical Data Power graphs
Power graph When selecting the burner and gas valves, the boiler efficiency must be taken into account.
Power graphs are expressed as burner power relative to furnace pressure. This corresponds to the maximum value in accordance with EN676, measured on the test blast tube.
Calculation of the burner power:
Q
F
= Burner power (kW)
Q
N
= KRated boiler power (kW)
hK = Boiler efficiency (%)
Q
N
QF=
hK
Type description
G 05.700 MODULO G 05.1000 MODULO
Burner power kW
140-700 170-1040
Operating mode
two-stage sliding/modulating
Fuel
Natural gas (LL, E) Hi = 8.83-10.35 kWh/m
3
or propane gas (F) Hi = 25.89 kWh/m
3
Gas valve DMVSE
512-T
DMVSE
520-T
DMVSE
512-T
DMVSE
520-T
DMVSE
525-R
DMVSE
5065-R
Gas connection
Rp 1, 1/2 Rp 2 Rp 1, 1/2 Rp 2 Rp 2 DN 65
Gas flow pressure m bar
20-100
Burner motor 2800 ¹/min
230/400 V, 50 Hz, 1.1 kW 230/400 V, 50 Hz, 1.5 kW
Combustion control unit/flame sensor
MPA 22/ionisation/alternative IRD probe
Power consumption W
1800 2000
Protection level
IP 41
Ambient temperature max. °C
60° C
Ignition transformer
EBI-M; 2 x 7.5 kV
Air flap drive
Servomotor STE 4.5 Q5.51/6-02R; Runtime: aspprox. 40 sec with adjustment travel of 90°
Gas throttle drive
Servomotor STE 4.5
Burner tube-Ø x Insertion depth mm
170 x 215 (KN)/325 (KM)/KL (435)
Air pressure switch
LGW 10 A 2
Burner weight incl. gas valve kg
100 kg
CE Mark
1312 AQ 0924 1312 AQ 0925
Note on type designation
G = Natural gas/Propane gas 05 = Size 700 = Power rating MODULO = Modulating with
electronic connection
KN = Normal burner head length KM = Medium burner head length
KL = Long burner head length
daPa mbar
kW
335
0
20
40
60
80
100
100 300 500 700 900 1100
0
2
4
6
8
10
daPa mbar
kW
530
1040
0
20
40
60
80
100
100 300 500 700 900 1100
0
2
4
6
8
10
G 05.700 MODULO G 05.1000 MODULO
EN
Page 6
6
09/2005 - Art. Nr. 13 019 526A
Overview
Burner
power
(kW)
DMV512-T
Rp1,1/2
DMV520-T
Rp 2
DMV512-T
Rp1,1/2
DMV520-T
Rp 2
DMV512-T
Rp1,1/2
Natural gas E Hi = 10.365 kWh/m
3
Natural gas LL Hi = 8.83 kWh/m
3
Propane gas
Hi=25.89kWh/m³
Gas pressure loss (from gas valve inlet)
550 16 15 17 15 15
600 19 15 21 16 15
650 22 18 24 19 17
700 26 21 28 22 20
Gas valve selection
The gas pressure loss specified in the table is to be added on to the combus
-
tion chamber pressure in mbar.
N.B.:
The calculated gas flow pressure is to be complied with at the gas valve inlet. To calculate the gas flow pressure required at the transfer station, the resistance of the burner supply conduit including valves (ball valve, TAS, addi
­tional filter or counter) must also be taken into account.
Example (for Burner G 05.1000 MODULO):
·
System data:
Gas type: natural gas E
Gas flow pressure: 20 mbar (N.B.: at gas valve inlet)
Required burner power: 700 kW
Combustion chamber pressure with boiler rated load: 2.5 mbar
·
Condition: working point must be within the burner’s permissible field of work.
·
Selected gas valve: DMV 520-T
·
Checking the selection:
Gas pressure loss (from table): 17 mbar
Combustion chamber pressure: 2.5 mbar
Total 19.5 mbar
Hence: Gas flow pressure 20 mbar >19.5 mbarðSelection of DMV520-T correct.
Burner
power
(kW)
DMV512-T
Rp1,1/2
DMV520-T
Rp 2
DMV525-R
Rp 2
DMV5065-R
DN65
DMV520-T
Rp 2
DMV525-R
Rp 2
DMV5065-R
DN65
DMV512-T
Rp1,1/2
Natural gas E Hi = 10.365 kWh/m³ Natural gas LL Hi = 8.83 kWh/m³
Propane gas
Hi=25.89kWh/m³
Gas pressure loss (from gas valve inlet)
550 17 15 15 15 15 15 15 15
600 20 15 15 15 17 15 15 15
650 23 15 15 15 20 17 17 16
700 27 17 15 15 24 20 20 18
750 31 20 18 18 27 23 23 21
800 35 23 20 20 31 26 26 24
850 40 26 23 23 35 29 29 27
900 44 29 25 25 39 33 33 30
950 49 32 28 28 44 37 37 34
1000 55 36 31 31 48 41 41 38
1
G 05.700 MODULO
G 05.1000 MODULO
Page 7
7
09/2005 - Art. Nr. 13 019 526A
Space requirements
There should be a space of no less than 0.60 m on each side of the burner for maintenance purposes.
Gas valve assembly
The valve assembly can be fitted on the left or the right.
Overview
Dimensional drawings and measurements G 05.700/1000 MODULO With DMV SE gas valve
KN
KM
KL
KN
KM
KL
KN
KM
KL
EN
Page 8
8
09/2005 - Art. Nr. 13 019 526A
Overview
Gas valve assembly
Installation position:
Vertical with upwards facing magnet.
Description, technical data
The compact gas valve DMV SE 512,520 is a compact unit with 2 class A solenoid valves, class A servo-pressure regulator, pocket filter and pressure switch. For the DMV SE 525, 5065 types the tube filter is installed externally.
Pressure switch GW A5:
adjustment range 5.....50 mbar
Magnetic valve V1/V2 quick opening/quick closing.
Servo-pressure regulator, can be adjusted via a spindle.
Max. operating overpressure 500 mbar
Inlet pressure range pe 15-500 mbar
Voltage/frequency: 230 V/50-60 Hz
The gas valve assembly consists of:
a gas throttle controlled by a servomotor
a DMV-SE gas valve
a gas filter (pocket filter or external filter)
a thermally triggered safety cut-off valve and a gas ball valve are to be provided by the manufacturer.
DMV SE gas valve
1 Electrical connection of the
solenoid valves (DIN 43650)
2 Electrical connection of the gas
pressure switch (DIN 43650) 3 Gas pressure switch 4 Gas inlet flange 5 Pocket filter (under cover) 6 Gas pressure adjusting screw pBr 8 Gas pressure measuring nipple G1/8 9 Pipe filter
DMV SE 512, 520 with pocket filter
DMV SE 525 with pipe filter
DMV SE 5065 with pipe filter
Page 9
9
09/2005 - Art. Nr. 13 019 526A
Overview
Hydraulics diagram
EN
Page 10
10
09/2005 - Art. Nr. 13 019 526A
Overview
Control panel
Function
A2 Standardised position for
fitting three-point regulator
A4 Display and operating unit
A4.1 Mounting location with clips
for removing the display and operating unit
B10 Flame signal measuring
bridge (concealed)
F10 Fuse
S1/H10 Main switch
0 Off 1On (operating light in switch lights up).
S2 Operating mode selector
switch Auto/Manual N
S3 + Manual increase of
burner power
- Manual reduction of burner power
All control elements are visible externally. A removable transparent cover clipped to the burner cover gives access to the monitoring and control elements for setting and operating the burner. The control panel contains the switching circuit cut-out.
To remove the cover, press in one or both sides gently and pull out at the same time.
To replace the cover, position the two clips at the appropriate openings and push in.
m
N.B.:
The main switch of the control panel only operates the control voltage. Before working in the control area of the burner, disconnect it fully from the mains, incl. burner motor AC connection.
Page 11
11
09/2005 - Art. Nr. 13 019 526A
Overview Combustion control unit MPA22
Function description
In addition to the function of a gas combustion control unit, the MPA 22 combustion control unit also realises power modulation of the burner via the actuation of air flaps and gas throttle in an electronic connection. The electronic connection controls the opening of the gas throttle proportional to the air flap along a curve based on 10 adjustment points. During start up, the adjustment points are defined based on the measurement values of the exhaust gas analysis. This guarantees optimal combustion across the entire performance modulation of the burner. With adjustment point P0, a separate ignition load can be defined for the burner. The thresholds for the normal range are defined with adjustment points “bu” and “bo” (lower operasssting point and upper operating point). In addition, other optional functions, such as leak checks, reventilation or waiting times can be activated. The combustion control unit is operated via a display and operating unit.
1 Additional propane gas valve ¬
2 Safety gas valve Y15
3 Main gas valve Y13
4 Burner motor M1
5 Ignition transformer T1
6 Power 230V-50Hz
7 GW max: Bridge connector
(Safety chain inlet ¬)
8 GW min F4
9 GW VPS ¬
10 Air pressure switch F6
11 Light sensor ¬
12 Flame monitor UV/Ion ¬
13 Pulse counter ¬
14 Gas servomotor Y11
15 Air servomotor Y10
16 Display and operating unit
connection A
17 e-Bus connection ¬
18 Power regulator connection 4P
19 Boiler control panel connection 7P
¬ Option
¬
¬
¬
¬
¬
EN
Page 12
12
09/2005 - Art. Nr. 13 019 526A
·
Access to Info mode (t < 5 s).
·
Access to voice mode (t > 5 s).
·
Return to next highest program level.
· Activating a function.
· Confirming a value.
· Moving the cursor anti-clockwise.
· Increasing the marked value.
· Moving the cursor clockwise.
· Reducing the marked value.
·
Unlocking the combustion control unit.
·
Red light diode flashes in the event of a fault.
Overview Combustion control unit MPA 22
Display and operating unit
Display
Button
Current values and operating statuses are displayed via the display and operating unit. By activating certain keys, it is possible to switch to info mode, operating mode or voice mode in addition to adjustment mode.
Page 13
13
09/2005 - Art. Nr. 13 019 526A
Overview Combustion control unit MPA 22
Program structure
Adjustment mode
Enter access code
Set key data
P9/P1/P0
Start burner via
boiler regulator
for hot
adjustment
Operation at bu
(lower operating
point)
Back to
operating display
eBus address
Reventilation time
Waiting time
Pulses per L/m³
Rest pos. Air flap
Delete error list
Check for leaks
Valve 1 check time
Valve 2 check time
Address regulation
Voice mode
Parameters SettingsCountersErrors
Info mode
Burner start-up
Adjustment of
upper/lower threshold
points
Setting for points P0
to P9
Temperature
controller on
Operating mode
Ready for operation
Temperature controller on
Operation
t>5 s
t<5 s
Start-up
Check air pressure
switch
Pre-ventilation
Safety time
Stabilization time
·
Error 0
·
Error 1
·
Error 2
·
Error 3
·
Error 4
·
Error 5
·
Fuel
·
Value P0
·
Value P1
·
Value P2
·
Value P3
·
Value P4
·
Value P5
·
Value P6
·
Value P7
·
Value P8
·
Value P9
Hot adjustment
Parameter
adjustment
Cold adjustment
Burner burns in
ignition setting
Calculation of
characteristics curve
points P2 .....P8
·
Francais
·
English
·
Deutsch
·
Italiano
·
Nederlands
·
eBus address.
·
Rest pos. Air
·
Check for leaks
·
Reventilation
·
Error list
·
Software
·
Automatic control unit
·
Version
·
Date
·
Product
·
No.
·
Fuel consumption (m)
·
Total operating time (hours)
·
Successful burner starts
EN
Page 14
14
09/2005 - Art. Nr. 13 019 526A
Boiler door preparation
·
Prepare the burner plate/boiler doors as per the drawing.
·
Stipulate interior diameter Ø 195 mm.
·
Four M10 holes (220-260 mm diameter circle) are required, as indicated in the accompanying diagram.
DE
Assembly
Burner head Burner housing
Fitting the burner housing
·
Dismantle the mixing unit before fitting the burner housing.
·
Undo the fixing screw (M10 counter nut and Allen screw) on the side of the unit (opposite the gas connection) and withdraw the mixing unit.
If the burner housing hangs below the burner head axis, proceed as follows:
·
Unscrew and remove the two lower nuts on the burner housing and unscrew the two upper nuts as far as possible.
·
Place the burner housing sloping diagonally forwards and fit the two upper bolts into the two slots in the burner head flange.
·
Press the burner housing against the burner head flange and tighten the 4 nuts.
The housing can be mounted above the axis of the burner head if required. In this case, the procedure must be reversed. No other positions for the burner housing are possible.
Fitting the burner head
·
Screw M10 stay bolts into the burner plate/boiler door and add the insulation. If the bolt circle is <260, cut slots to the required size.
·
Fix the burner head with 4 hexagonal nuts M10
Blast tube installation depth
On boilers with reverse firing or on three-pass boilers, the blast tube installation depth must be complied with for correct operation. The following standards are to be reconciled with the boiler manufacturer’s specifications.
Boiler in reverse firing chamber
Dimension A = Boiler front to reverse edge of second pass
Three-pass boiler
80-190 mm Insertion depth
-20 to +90 mm Insertion depth
Øa Øb c d
195 220-260 M10 45°
Page 15
15
09/2005 - Art. Nr. 13 019 526A
Assembly
Gas valve assembly
Assembly Gas valve assembly
·
Press the gas throttle module 5 against the burner head and tighten the 4 nuts. Then secure the gas connection pipe 3 to the gas throttle module. Check that O-Ring 6 and flat gasket 4 are in the correct position.
·
Secure gas valve 2 so that the solenoids of DMV SE are positioned vertically over the gas valve.
·
Fit the supplied gas pressure tube 7 between the gas throttle module and DMV SE.
·
If available, secure external filter 1.
·
Note the direction of the flow.
·
Fit a thermally triggered safety valve and a gas ball valve (provided by manufacturer) before the gas valve.
m
If the position of the gas train is angled, use the enclosed right-angled pressure release pipe with screw connection. If the gas valve is changed, the applicable guidelines and regulations must be observed. All connections should be leak-tested using foam-producing or similar materials.
Caption
1 External filter 2 Gas valve 3 Gas connection pipe 4 Flat gasket between gas
connection pipe and gas throttle
module 5 Gas throttle module 6 O-Ring between gas throttle
module and burner head flange 7 Gas pressure tube
1
2
3
4
65
7
EN
Page 16
16
09/2005 - Art. Nr. 13 019 526A
Assembly
Checking/Setting Mixer unit for natural gas/propane gas
Recommended setting for propane gas
On the gas diffusers labelled C, 2 outwards-facing slots and 1 inwards-facing slot should be left covered by sleeve E.
Secure the turbulator with 5 solid M5x6 screws (diffuser D) and 1 drilled M5x6 screw F (diffuser C).
On the gas diffusers labelled D, 2 outwards-facing slots and 0 inwards-facing slots should be left covered by sleeve E.
1
Checking the mixing unit
·
Check and adjust the setting of the ignition electrodes and the turbulator.
Recommended setting for natural gas
On the gas diffusers labelled A, 5 outwards-facing slots and 1 inwards-facing slot should be left covered by sleeve E.
Secure the turbulator with 6 drilled M5x6 screws F.
On the gas diffusers labelled B, 5 outwards-facing slots and 0 inwards-facing slots should be left covered by sleeve E.
Fitting the mixing unit
·
Release and remove the mixing unit cover by unscrewing the three Allen screws 1.
·
Check the gas connection O-ring.
·
Fit the mixing unit and tighten with screw at side (M10 counter nut and Allen screw).
·
Fit the extension rod with 0-40 scale (loose in accompanying pack) for setting the turbulator.
·
The extension rod must be pushed into the steel sleeve until it makes contact.
·
Feed ignition cable 2 and ionisation cable 3 through the opening and push in the rubber bushing.
·
Screw down the cover, connect the ignition cables 2 and ionisation cable 3.
Page 17
17
09/2005 - Art. Nr. 13 019 526A
Assembly
Gas supply Electrical supply
Electrical supply to the burner
For connection of the burner and regulator, the corresponding circuit diagram is mandatory. The power supply and the electrical connections must comply with the applicable standards.
m
N.B.:
·
Before connecting the burner to the electrical supply, close the gas ball valve.
· Set the main switch of the burner control panel to zero.
Before any intervention on the connector of the gas and air servomo­tors, the display or the e-Bus connec­tion, the burner must be switched off by disconnecting the 7-pin plug.
Burner motor connection
The burner is delivered with a neutral wire and earthing for a mains voltage of 400V-50Hz AC. The connection cable for the burner motor must be run through the cable fittings and wired to the terminal strip as indicated in the electrical diagram. Check the direction of rotation of the fan motor (see arrow on burner casing) via manual activation of the burner protection device.
Gas valve connection
·
Connect the gas valve to the plugs located on the burner (black to black, grey to grey).
·
Insert connector 1 between burner and gas throttle servomotor in accordance with the diagram below.
Burner and regulation connection
Insert the 4-pin and 7-pin plug of the boiler control panel in the correspond
-
ing sockets of the burner.
General regulations for the gas supply
·
Connection of the gas valve assembly to the gas mains must be carried out by a recognised specialist.
·
The cross-section of the gas cable must be such that the prescribed gas flow pressure at the gas valve
inlet is not undershot. Burner start-up automatically implies acceptance of the system. This is the responsibility of the installer or his representative as he alone can guarantee that the system conforms to the current standards and regulations.
The installer must hold a licence issued by the gas authority, must have checked the system for leaks and must have vented it.
EN
Page 18
18
09/2005 - Art. Nr. 13 019 526A
Start-up
Default settings
Burner power Dimension
Y
mm
Air flap opening Gas throttle opening Pressure
adjustment
setting
pVA mbar
Low loadkWRated load
kW
Ignition
load
P0 (°)
Low load
P1 (°)
Rated load
P9 (°)
Ignition
load
P0 (°)
Low load
P1 (°)
Rated load
P9 (°)
140 400
10 0 0 25 23 23 39 15
150 500
20 0 0 29 23 23 43 15
160 600
35 5 5 40 24 24 50 15
170 700
40 5 5 45 24.5 24.5 62 15
Natural gas settings table G 05.700 MODULO
Natural gas settings table G 05.1000 MODULO
Burner power Dimension
Y
mm
Air flap opening Gas throttle opening Pressure
adjustment
setting
pVA mbar
Low loadkWRated load
kW
Ignition
load
P0 (°)
Low load
P1 (°)
Rated load
P9 (°)
Ignition
load
P0 (°)
Low load
P1 (°)
Rated load
P9 (°)
170 600
20 0 0 38 26.5 26.5 56 15
170 700
25 2 2 41 26.5 26.5 65 15
200 800
30 6 6 68 27 27 90 18.5
220 900
35 8 8 68 28 28 90 18.5
250 1000
40 9 9 68 29 2 90 18.5
Propane gas settings table G 05.700 MODULO
Propane gas settings table G 05.1000 MODULO
Burner power Dimension
Y
mm
Air flap opening Gas throttle opening Pressure
regulator
setting
pVA mbar
Low loadkWRated load
kW
Ignition
load
P0 (°)
Low load
P1 (°)
Rated load
P9 (°)
Ignition
load
P0 (°)
Low load
P1 (°)
Rated load
P9 (°)
140 400
10 4 4 20 19 19 30.5 15
150 500
20 4 4 29 19 19 36 15
160 600
30 4 4 36 19 19 41 15
170 700
40 4 4 40 19 19 45 15
Burner power DimensionY
mm
Air flap opening Gas throttle opening Pressure
regulator
setting
pVA mbar
Low loadkWRated load
kW
Ignition
load
P0 (°)
Low load
P1 (°)
Rated load
P9 (°)
Ignition
load
P0 (°)
Low load
P1 (°)
Rated load
P9 (°)
170 600
15 6 6 36 19.5 19.5 42 17.5
170 700
20 6 6 63 19.5 19.5 75 17.5
200 800
25 7 7 63 19.5 19.5 75 17.5
220 900
35 7 7 68 19.5 19.5 75 17.5
250 1000
40 8 8 68 22 22 75 17.5
The above setting data are basic settings. The factory setting data are in boxes with thick black borders. The burner can normally be run using these settings. Check the setting values carefully in each case. System-specific corrections may be necessary.
Page 19
19
09/2005 - Art. Nr. 13 019 526A
Start-up
Burner head position setting, Gas pressure switch and air pressure switch
Burner head position
Dimension Y is set by turning screw V. Set the burner head setting in accordance with the table. The burner head setting can influence the starting performance and burner performance.
Gas pressure switch
·
Remove the transparent cover.
·
Set the setting scale to 5 mbar (natural gas and propane gas).
The gas pressure switch min. is installed between the valves. The gas safety valve Y15 is actuated one second before the safety time. Within this time, the gas pressure switch must release. If there is insufficient gas pressure, the burner starting is interrupted and a waiting time of 2 minutes starts. Start-up is then attempted again. The waiting time can
only be reset by cutting the power supply to the device. Waiting times: 3 x 2 minutes, then 1 hour
Air pressure switch
·
Remove the transparent cover.
·
Provisionally set the air pressure switch to the minimum setting.
Pressure regulator setting
The gas pressure regulator is set to the default setting in the factory (see page
18). Check the gas pressure after the first time the burner is started up (measuring point: gas valve output flange) and if necessary correct the gas pressure pBr using setting screw S. Do not change it again after start-up.
EN
Page 20
20
09/2005 - Art. Nr. 13 019 526A
Start-up
Checks before start-up Control unit auto-test
Air Gas
Burner check
Control unit unprogrammed
Control unit auto-test
Switch the burner on via the main switch. The combustion control unit executes an auto-test. If the control unit has not yet been programmed, the display shows “Control unit unprogrammed”
Auto-test of the control unit and of the air and gas servomotors
This display loads the values contained in the combustion control unit.
The control unit has not yet been programmed.
Loading values
100%
0%
Pre-start-up check
·
Disconnect the burner by unplugging
it from the power supply.
·
Close gas valves.
·
Note the operating regulations of the
heat generator and regulation
producer.
·
Check that the gas type and gas
pressure are appropriate to the
burner.
·
Check the gas conduit for leaks
·
Vent the fuel supply pipes.
·
Check the flame pipe insertion depth in accordance with the boiler manufacturer’s instructions.
·
Check:
if the fresh air supply and the exhaust gas paths correspond to the burner power.
if there is water pressure in heating circuit,
if the circulation pump is running,
if the mixer opens,
if the draught regulator in the chimney opens,
if the power supply is in order,
thermostat settings,
·
Check the direction of rotation of the fan motor (see arrow on burner casing) via manual activation of the burner protection device.
If all the checks were successful, then ensure that:
·
Main switch 0/1 is set to zero
·
Manual/Auto operating type selector switch is at the centre position
·
Gas ball valve is closed
·
Re-energise the burner.
Page 21
21
09/2005 - Art. Nr. 13 019 526A
Start-up
Access to adjustment mode Parameters menu: Programming additional functions
Access to adjustment mode
·
Press and hold the key and after 0.5 seconds, press the key.
·
Enter the numbers for the access code with the or key.
· Confirm each number with .
· For input fields, switch back to the next highest level with .
After entering the correct code, three menus are available for selection.
Parameter: for programming additional functions.Cold adjustment: for pre-adjusting the burner for initial start-up.Hot adjustment: for only partial programming, e.g. after regulator
shutdown during adjustment or with subsequent correction of the adjustment values.
Parameter
The “Parameters” menu item is selected from adjustment mode. This allows various additional functions and function parameters to be configured.
E-Bus address: 03H: standard address (factory setting). This parameter is required for communication with a PC. The following addresses are possible: F3H, 73H, 33H, 13H.
Access to next parameter: continue with key.
This parameter allows you to configure a reventilation time. Adjustment range: 0 seconds (= no reventilation) to 240 seconds
This parameter allows you to configure a waiting time between a regulator shutdown and a burner restart. Adjustment range: 0 minutes (= no waiting time) to 100 minutes
The pulse factor gives the number of pulses that the control unit receives from the gas counter with the flow rate of a cubic metre of natural gas (accessory). Adjustment range: 1 (1 pulse = 1m
3
) to 255 ( 255 pulses = 1m3).
Cold adj. Hot adj.
Parameters
?
Code ____
Accessing the adjustment settings
It is only possible to access adjustment mode when the burner is idle (display: “Control unit unprogrammed” or “Ready for operation”.) To do this, set the Manual/Auto operating type selector switch on the burner control panel to the centre position. In addition, the access code must be entered to activate adjustment mode.
N.B.: Only a specialist with sufficient training in and authorisation to deal with MPA 22 may activate adjustment mode via the access code and adjust the burner. The access code is located at the bottom of the information label on the MPA 22.
During the setup process, a timeout of 30 minutes is active, which is reset by pressing a key on the keypad. Upon expiry of the timeout, a safety shutdown is executed. This ensures that a longer operating time is not possible without the setup process being completed. In adjustment mode, all safety functions are activated. A flame failure, air pressure switch failure or an error in the servomotor actuation leads to a malfunction shutdown or safety shutdown.
?
Next
E-Bus address
03H
Next Back
Reventilation time
000s
Next Back
Waiting time (0-100 min)
000 min
?
Pulses per l/m
3
?
EN
Page 22
22
09/2005 - Art. Nr. 13 019 526A
Next Back
Rest pos. Air flap
00.0°
Next Back
Delete error list
Next Back
Check for leak
Y
Next Back
Valve 1 check time
006s
Next Back
Valve 2 check time
006 s
Next Back
Address Regulation
10H
Connection setup
Save parameters
This parameter allows you to adjust the rest position of the air flap. This parameter (in degrees) may be required after reventilation. Default setting 00.0°
With this function, accumulated errors are deleted from the error log (display information: “Empty”). The next new error is written under No. 0 in the error log.
Leak check: Y= Yes/N= No With this function, you can deactivate the valve leak check.
Valve 1 check time: For proper execution of the leak check, at least the 6 seconds set in the factory are required. Adjustment range: 1-240 s
Valve 2 check time: For proper execution of the leak check, at least the 6 seconds set in the factory are required. Adjustment range: 1-240 s
Address regulation (factory setting to 10H) Other addresses are possible: F7H, F0H, 77H, 70H, 37H, 30H, 17H.
After confirming “Next” in the “Address regulation” menu item, the newly adjusted parameters are saved in the control unit. The control unit then switches back to “Ready for operation”.
Start-up
Adjustment mode Parameters menu: programming of additional functions
Control unit unprogrammed
Page 23
23
09/2005 - Art. Nr. 13 019 526A
Start-up
Adjustment mode Cold adjustment menu: Burner pre-adjustment
Cold adjustment (with ball valve closed)
In the “Cold adjustment” menu item, the P9/P1/P0 key data are pre-adjusted in accordance with the setting table (page 18) for the desired burner power. The control unit then calculates the intermediate points P2 to P8 and switches to the “Hot adjustment” menu.
·
Accessing the adjustment mode.
·
Select cold adjustment with or .
·
Confirm with .
Adjust air and gas setting.
·
Position the cursor on air or gas with or .
·
Activate with (cursor flashes).
·
Set new value with or .
·
Confirm with .
Switch between adjustment points P9/P1/P0.
· Position cursor on “Next” or “Back” with or .
· Confirm with .
· If the position “Next” is confirmed for adjustment point P0 with , the
control unit calculates the intermediate points P2 to P8 and then switches to the hot adjustment menu .
Direct access to this menu via adjustment mode/hot adjustment
.
?
Next
Next Back
Low load
P1
Air: .. ` . Gas: ..´ .
Next Back
Ignition load P0
?
?
start adjustment
Burner via boiler
regulator for hot adj
?
Air: .. ` . Gas: ..´ .
Air: .. ` . Gas: ..´ .
Full load P9
EN
Page 24
24
09/2005 - Art. Nr. 13 019 526A
Start-up
Adjustment mode Hot adjustment menu: Adjusting the burner
Hot adjustment (with first start for function check, still with closed ball valve)
Hot adjustment of the burner
In the “Hot adjustment” menu items, the fine adjustments for the air and gas flap are made for the ten adjustment points P0 to P9 using the exhaust gas analysis. Then, the definitive working range of the burner is defined based on the bu (lower operating point) and bo (upper operating point) thresholds.
Note: if normal shutdown takes place during the adjustment procedure, select the “Hot adjustment” menu item immediately after activating adjustment mode. By doing this, you will keep the values of the points that have already been adjusted, while a recalculation is carried out in the “Cold adjustment” menu.
·
For burner start, set the Manual/Auto burner selector switch to manual on the control panel, ensure heat request via boiler regulator.
The burner starts with the following function sequence:
Air flap opens for ventilation. Air: .........................
Blower motor on. ....................................
Check air pressure switch
Pre-ventilation 20 seconds: time remaining is displayed.
Gas throttle moves to ignition position. Gas: .................
Servomotor air flap moves to ignition position. Air: ............
Ignition on .........................................
Because the ball valve is closed, the burner shuts down after the safety time as the gas pressure is too low. The display shows: “Gas pressure too low”.
·
If the function check was successful, the gas valve is opened. After a two-minute waiting time, the burner is automatically restarted and the above-mentioned process is repeated.
Valve energised. ....................................
Safety time 3 seconds. After the safety time, the ignition transformer is
de-energised.
Flame signal present. .................................
During the stabilisation time, the burner remains in ignition setting.
Burner check
Air: - Gas: -
Start-up
Air pressure check
Pre-ventilation: 20 s
Air: - Gas:
Pre-ignition
Air: Gas: -
Safety time
Stabilisation time
Air: Gas: -
Air: - Gas: -
Air: - Gas: -
Air: - Gas: -
Page 25
25
09/2005 - Art. Nr. 13 019 526A
Start-up
Adjustment mode Hot adjustment menu: adjusting the burner
Next
Ignition load P0
Air: .. ` . Gas: ..´ .
Next Back
Low load P1
Next Back
Adjustment point P2
Point P3 .... Point P8
Next Back
Full load P9
Next
Lower load point bu (lower
operating point)
Next
Upper load point bo
(upper
operating point)
Operation
Burner remains in ignition load, adjustment point P0.
·
Check gas pressure pBr (for factory setting, see default setting on page 18). In the event of a later change, all adjustment settings must be corrected. Therefore, start fine adjustment of the burner at P9. In each adjustment point, check the combustion values and, if necessary, change the gas throttle setting or air flap setting. To do this:
·
Select air or gas with or .
·
Activate with (cursor flashes).
·
Change value with or .
·
Confirm with .
Access to the next adjustment point by selecting Next and confirm by pressing key .
Important:
The values for each adjustment point are only saved when you access the next adjustment point.
·
Enter the adjustment values in the log (page 30).
·
Move the individual adjustment points to point 9 (full load).
· Check gas flow rate full load, if necessary increase or reduce gas and air.
· If all adjustment points from P0 to P9 are optimised in adjustment point P9,
confirm with “Next” .
The burner moves to the lower operating point (bu).
· Check the low load exhaust gas temperature and gas flow rate, if necessary
adjust the burner power by correcting bu (lower operating point).
· Confirmation “Next”.
The burner moves to the upper operating point (bo).
·
Check the high load exhaust gas temperature and gas flow rate. If necessary adjust the burner power by correcting bo (upper operating point). The adjustment is made by changing the air flap.
·
Confirm with “Next” to complete the adjustment procedure. The burner switches to operating mode.
·
Burner moves to lower operating point and waits for a request for heat.
·
Manual/Auto operating type selector switch to manual: burner power can be changed manually via the +/- switch.
·
Manual/Auto operating type selector switch to Auto: burner adjusts bu/bo within the specified power range in accordance with the requirements of the regulation thermostat.
Adjust air pressure switch
·
When the burner is running at rated load, calculate the blower pressure.
·
Set air pressure switch approx. 15% below calculated value.
Air: .. ` . Gas: ..´ .
Air: .. ` . Gas: ..´ .
Air: .. ` . Gas: ..´ .
Air: .. ` . Gas:
Air: .. ` . Gas:
Air: .. ` . Gas:
EN
EN
Page 26
26
09/2005 - Art. Nr. 13 019 526A
Start-up
Operating mode
Burner check
Air: Gas:
Start-up
Air: Gas:
Air pressure check
Pre-ventilation: 20 s
Pre-ignition
Safety time
Stabilisation time
Operation
Burner ready for operation
Boiler thermostat requests heat.
Burner start flowchart:
The burner starts with the following function sequence:
Air flap opens for ventilation. Air: .........................
Blower motor on. ....................................
Pre-ventilation 20 seconds: time remaining is displayed.
Gas throttle moves to ignition position. Gas: .................
Air flap moves to ignition position. Air: .....................
Ignition on .........................................
Valve energised. ....................................
Safety time 3 seconds
Flame formation. ....................................
After the safety time, the ignition transformer is de-energised.
·
During the stabilisation time, the burner remains in ignition setting.
·
The burner is in operation and adjusts bu (lower operating point) to bo (upper operating point) within the specified performance range (manual/Auto operating type selector switch to Auto). The current setting of the air flap is displayed.
Standby
Air: Gas:
Air: Gas:
Air: Gas:
Air: Gas:
Air: Gas:
Air: Gas:
Page 27
27
09/2005 - Art. Nr. 13 019 526A
Start-up
Info mode Voice mode
·
Press key t < 5s.
·
Select desired menu with or .
·
Confirm selected menu with .
· Scroll with or .
· Return to the next highest level with .
Error Counter
Parameter Setting
?
Establishing connection
?
0% 100%
Info 1
Info 2
?
Info 3
Parameters SettingsCountersErrors
Comment: info mode can be activated
with the button during burner operation and burner idle time. To exit info mode, press the button again.
·
Error 0
·
Error 1
·
Error 2
·
Error 3
·
Error 4
·
Error 5
·
Fuel Gas.
·
Value P0
·
Value P1
·
Value P2
·
Value P3
·
Value P4
·
Value P5
·
Value P6
·
Value P7
·
Value P8
·
Value P9
Voice mode can be activated with the button during burner operation and burner idle time.
·
Press button t > 5s .
·
Select desired language with or .
·
Scroll with or (5 languages possible).
·
Confirm selected language with . This will close voice mode.
FRANCAIS ENGLISH DEUTSCH
DEUTSCH ITALIANO NEDERLANDS
·
eBus address.
·
Rest pos. Air
·
Check for leaks
·
Reventilation
·
Error list
·
Software
·
Automatic control unit
·
Version
·
Date
·
Product
·
No.
·
Fuel consumption (m)
·
Total operating time (hours)
·
Successful
burner starts
EN
Page 28
28
09/2005 - Art. Nr. 13 019 526A
Burner and boiler servicing can only carried out by a trained specialist. The system operator is advised to take out a service contract to guarantee regular servicing.
N.B.:
Before maintenance and cleaning work, completely separate the burner from the mains, including the power supply AC motor, and close the gas ball valve.
A1 Combustion control unit A4 Display and operating unit B10 Ionisation bridge F6 Air pressure switch F12 Protective motor relay K1 Motor contactor M1 Burner motor T1 Ignition transformer (concealed) Y10 Servomotor air flap 7 Control panel 8 Blast tube 13 Burner cover 113 Air box
Maintenance
Checking the exhaust gas temperature
·
Check the exhaust gas temperature.
·
Clean the boiler if the exhaust gas temperature is over 30 K above the start-up value.
Checking the ignition electrodes and the mixing unit.
·
Disconnect the 2 ignition cables from the ignition transformer.
·
Remove the grommet for the two cables from the cover by pressing into the burner head.
·
Unscrew completely the 3 screws securing the cover.
·
Slip the cover off over the cables.
·
Loosen the side screw securing the mixing unit.
·
Pull out the mixing-ignition unit.
·
Check the condition of the turbulator.
·
Check the position of the ignition electrodes and the turbulator.
·
If necessary, remove dust from the parts accessible with the cover removed.
·
Check the presence and condition of the O-ring seal J1 when assembling.
Cleaning the fan
·
Disconnect the motor by unplugging it from the power supply.
·
Unscrew the 7 screws of the motor panel.
·
Remove the panel and motor, taking care not to damage the gas pressure tube of the differential air pressure switch.
·
“Dry” clean the air pressure pipes.
·
Do not use pressurised materials.
·
Take out the 4 screws securing the air guiding piece.
·
Thoroughly clean the air duct and fan.
·
Reassemble.
Page 29
29
09/2005 - Art. Nr. 13 019 526A
Valves
No special maintenance is required for the valves. Valves must not be repaired. Defective valves must be replaced by a qualified professional, who must check the leak, function and combustion values following replacement.
Remove the blast tube.
To carry out this procedure, the combustion chamber door must be opened or the burner removed.
Variant 1 -Access via the combustion chamber doors
·
Remove the mixer control/ignition device.
·
Loosen the 3 fixing screws on the blast tube support by 1 to 2 turns. N.B.: the screws are threaded to the left (Allen 3).
·
Remove the blast tube, check, clean, and where necessary, replace if a deformity is found.
·
Refit the blast tube in the reverse sequence.
·
The space between the blast tube and the door insulation should be fitted with flameproof material.
Variant 2 - Removing the burner
·
Remove the mixer control/ignition device.
· Loosen the electrical connections.
· Remove the gas valve assembly.
· Unscrew the gas connection
(2 M8 nuts).
· Loosen the burner housing (2 M8 screws) and remove.Do not damage electrical cables.
· Unscrew the burner head and then proceed as under variant 1.
· Refit in the reverse sequence.
Precautions After each intervention, check the combustion performance under real operating conditions (doors shut, cover fitted etc.). Note down the results in the corresponding report forms.
Replacing the filter on the gas valve
The filter must be checked once a year and replaced if dirty. Pocket filter:
·
Release the cover fixing screws on the filter.
·
Remove the filter.
·
Insert new filter.
·
Refit the cover with the screws.
Tube filter:
·
Dismantle the gas connection flange at the inlet side.
·
Remove the filter.
·
Insert new filter.
·
Fit a gas connection flange.
·
Open the manual stop valve; check tightness.
Cleaning the hood
·
Clean the cover with water and a cleaning product.
·
Do not use chlorine-based or abrasive cleaning products.
Maintenance
EN
Page 30
30
09/2005 - Art. Nr. 13 019 526A
Burner-specific adjustment settings of the MPA 22
Measurement/Date:
Parameters Dim Range M1/ M2/ M3/ M4/
eBus address
Reventilation time [s] 0-240
Waiting time [min] 0-100
Pulses per L/m³ 1-255
Rest pos. Air flap [°]
Delete error list blank/
Check seals Y/N
Valve check time 1 [s] 0-240
Valve check time 2 [s] 0-240
Address regulation
Software
Product No.
Counters Dim.
Fuel consumption [m³]
Total operating hours [hours]
Successful burner starts
Measurement/Date:
M1/ M2/ M3/ M4/
Measurement Measurement
Air M1 M2 M3 M4 Gas M1 M2 M3 M4
Value P0 [°] [°]
Value P1 [°] [°]
Value P2 [°] [°]
Value P3 [°] [°]
Value P4 [°] [°]
Value P5 [°] [°]
Value P6 [°] [°]
Value P7 [°] [°]
Value P8 [°] [°]
Value P9 [°] [°]
bu/flow rate [°] [m³/h]
bo/flow rate [°] [m³/h]
bu/Value CO2/CO [%] [ppm]
bo/Value CO2/CO [%] [ppm]
System: ..........................................
Burner No.: .....................................
Boiler manufacturer: ...............................
Boiler type: ..............................................
Observer M1: .....................................................
Observer M2: .....................................................
Observer M3: .....................................................
Observer M4: .....................................................
Page 31
31
09/2005 - Art. Nr. 13 019 526A
Service
Troubleshooting
Fault diagnosis and repair
Before carrying out fault diagnosis, check that the basic requirements for correct operation are being fulfilled:
·
Is there any current?
·
Is there any gas pressure?
·
Is the gas stop valve open ?
·
Are all control and safety devices, such as the boiler thermostat, low-water detector, limit switch, etc. adjusted properly?
Error/fault Cause Corrective action
Display without information No mains voltage present
External cut-out defective Display-control unit plug-and-socket connection interrupted Display defective MPA 22 defective
Check Check/replace Check/establish connection
Replace Replace
Display “Safety chain” No feedback on terminal 7 Insert bridge connector or given
Check switch/limiter
Motor does not start Control unit-motor plug-and-socket
connection interrupted
Capacitor defective
Motor defective
Control unit/servomotors feedback not
correct
Establish connection
Check/replace
Check/replace
Control unit/servomotors
Check/replace
Motor only runs briefly Air pressure switch does not activate
Gas pressure switch does not activate Gas filter dirty Magnetic valve V1 does not open No gas available
Check/change adjustment Check/change adjustment Clean/replace gas filter Check/replace compact valve Notify gas supplier Note: in the event of a gas shortage, the waiting time can be reset by de-energising the burner (7-pin plug)
Burner does not start Compact valve defective
Ignition transformer defective Ignition electrode position/Ignition cable MPA 22 control unit defective Ionisation probe/IRD probe
Replace Replace Check/replace Check/replace Check/replace
Crack formation on ionisation probe Too much gas on probe
Circulation insufficient
Fit solid screws (propane gas set)
If a fault occurs on the burner, the red light diode flashes on the display unit. At the same time, the cause of the fault is displayed and a fault code is displayed.
EN
Page 32
32
09/2005 - Art. Nr. 13 019 526A
Adresse Service-Hotline
ELCO Austria GmbH
Aredstr.16-18 2544 Leobersdorf
0810-400010
ELCO Belgium n.v./s.a.
Pontbeeklaan-53 1731 Zellik
02-4631902
ELCOTHERM AG
Sarganserstrasse 100 7324 Vilters
0848 808 808
ELCO GmbH
Dreieichstr.10 64546 Mörfelden-Walldorf
0180-3526180
ELCO France
18 rue des Buchillons 74106 Annemasse
0450877624
ELCO-Rendamax B.V.
Amsterdamsestraatweg 27 1410 AB Naarden
035-6957350
Fabriqué en EU. Made in EU. Hergestellt in der EU. Gefabriceerd in de EU Document non contractuel. Non contractual document. Angaben ohne Gewähr. Niet-contractueel document
AT
BE
CH
FR
DE
NL
Loading...