Effekta ME 1000, ME 1500, ME 400, ME 500, ME 600 Instruction Manual

...
UPS
Uninterruptible Power Supply
ME 1000/1500
Instruction Manual
Item number: ACX11MES1K000000 USB
ACX11MES1K500000 USB
July 2008
ME series
Page 2 of 31
Contents
1 Presentation 4 2 Warranty conditions 5
2.1 Limitation of liability 6
3 Safety 7
3.1 General safety instructions 7
3.2 Transportation and storage 7
3.3 Setup 7
3.4 Connection 8
3.5 Operation 8
3.6 Handling batteries 9
3.7 Maintenance, servicing and faults 9
4 Introduction 10 5 System description 11 6 Description of equipment – ME series 12
6.1 Display and operator control elements on the front panel 12
6.1.1 Warning, indicator and operating elements: 13
6.1.2 Operator control elements of the UPS 13
6.1.3 Display elements of the UPS 13
6.2 Equipment elements on the rear panel 14
6.3 Audible alarm signals of the UPS 16
7 Storage and unpacking 17
7.1 Storing the UPS 17
7.2 Unpacking the equipment 17
8 Installing and connecting the UPS 18
8.1 Connecting the equipment 18
8.2 Connecting the UPS 18
8.3 Connection sequence 19
9 Operating and controlling the equipment 20
9.1 Operating the UPS equipment 20
9.1.1 Operating modes and signals 20
9.2 Instructions for using the UPS 22
9.2.1 Switching on the UPS 22
9.2.2 Switching off the UPS 22
9.2.3 Communication 22
10 Starting up the UPS equipment 23
ME series
Page 3 of 31
11 Troubleshooting 23 12 Software 25 13 Maintenance and servicing 26
13.1 Measuring the bridging time (support time) 26
13.2 Service log 27
13.3 Service hotline 28
13.4 Maintenance and service contracts 28
14 Technical Data 29
14.1 Equipment specifications 29
14.2 Accessories 30
14.3 List of wearing parts 30
15 Requirements for the declaration of conformity 31
ME series
Page 4 of 31
Denotes information which, if disregarded, poses a risk to health, functionality or safety.
Warning about the handling of batteries.
Warning about dangerous electrical voltage.
Denotes additional information and tips.
Recycling symbol.
Denotes components that are governed by the electronic scrap ordinance.
Denotes components or parts that must be disposed of in a specific manner. Never throw these components into the regular refuse.
1 Presentation
In this instruction manual, the abbreviation UPS stands for Uninterruptible Power Supply. The following pictograms are used in this instruction manual:
Copyright © 2006 All rights reserved. This instruction manual is protected by copyright law. The copyright owner is EFFEKTA Regeltechnik GmbH.
Trademarks: All trademarks used are the property of their respective owners. EFFEKTA
We reserve the right to make technical and visual changes, and we are not liable for typographical
errors.
®
is a registered trademark of EFFEKTA Regeltechnik GmbH.
ME series
Page 5 of 31
2 Warranty conditions
The delivery receipt is considered to be the initial proof of purchase and should be stored carefully. It is required for all warranty claims. If the product is transferred to another user, then the latter is entitled to claim under the warranty for the remainder of the warranty period. The purchase receipt and this declaration should be transferred to the possession of the new owner.
We guarantee that this equipment is in a functional state and corresponds in technical terms to the descriptions in the enclosed documentation.
The warranty period for special equipment corresponds to the minimum period prescribed by legislation.
This warranty is not valid for the following cases:
o Defects due to: damage during transportation, accidents, natural
disasters, misuse, vandalism, inappropriate use, maintenance errors or incorrect repairs by third parties.
o Modifications, unauthorised tampering, incorrect operation, another
device or accessory, incorrect installation, or any modification not approved by us.
o Disregard for the instructions in the supplied documentation. o Incompatibility of the product as a result of technical innovations or
regulations that may come into effect after the purchase.
o Incompatibility or malfunction caused by product components not used
by us.
o Signs associated with the normal ageing process of the product
(wearing parts).
o Defects caused by external appliances.
The warranty period for parts replaced and/or repaired within the scope of this warranty expires with the original warranty for the product.
Equipment sent in without accessories will be replaced without accessories. Equipment returned will only be accepted if it is returned in the original packaging.
All incidental transportation costs are excluded from the provisions of the warranty.
ME series
Page 6 of 31
EFFEKTA GmbH does not give any express or implied warranties in relation to this equipment and its quality, performance, merchantability or suitability for a specific purpose. In some countries, the exclusion of implied warranties is not permitted by law. In this case, the validity of all express and implied warranties is restricted to the warranty period. When this period expires, all warranties cease to be valid. In some countries, a limitation of the validity period of implied warranties is not permitted by law, in which case the above restriction is not effective.
2.1 Limitation of liability
Compensation claims are excluded unless they are based on deliberate acts or gross negligence of EFFEKTA GmbH or its employees. Liability under the Product Liability Act remains unaffected. Under no circumstances will we be held liable for:
o Claims for losses or damage made by third parties against you. o Loss of or damage to your records or data or the cost of their recovery. o Financial consequential damage (including loss of earnings or savings)
or incidental damage, even in the event that we were informed of the possibility of such damage.
Under no circumstances whatsoever will EFFEKTA GmbH be held responsible for any coincidental, indirect, special, consequential or other damage of any kind (including, without limitation, damage relating to loss of profit, discontinuation of business, loss of business information or any other loss) arising from use of the equipment or in any connection with the equipment, whether based on a contract, compensation, negligence, strict liability, or other claims, even if EFFEKTA GmbH was informed in advance about the possibility of such damage. This exclusion also applies for any liability arising from claims of third parties against the initial purchaser.
In some countries, the exclusion or limitation of coincidental or consequential damage is not legally permitted, in which case the above declaration is not effective.
ME series
Page 7 of 31
Read and observe the user manual and safety instructions in this chapter before taking any further action (transportation, storage, connection, startup etc.).
Since the UPS equipment uses mains voltage and has a suitable energy accumulator (high-capacity batteries) installed either inside or outside the device, the instructions in this chapter are very important for all users and personnel. For this reason, appropriate safety instructions on the topic of batteries and battery packs are also dealt with here.
Work on the UPS equipment may only be performed by authorised technical personnel.
3 Safety
3.1 General safety instructions
3.2 Transportation and storage
The UPS may only be transported to its place of intended use in the original packaging. The same applies for removals or returns.
The equipment must not be transported or stored upside down. Position the equipment securely during transportation, taking its centre of
gravity into account. Due to its weight, UPS equipment with integrated batteries may drop suddenly if its position shifts slightly.
When storing equipment, make sure that it is also securely positioned.
3.3 Setup
The UPS is intended for use in ventilated rooms. During setup or installation, the installation location prescribed by the
manufacturer must be observed. There is a risk of condensation where the UPS is exposed to extreme and
rapid temperature changes. Before taking any further steps, the equipment should be allowed to acclimatise for at least 2 hours.
Never set up or operate the equipment in a damp environment. Keep fluids away from the equipment.
The UPS must not be set up near heat sources.
ME series
Page 8 of 31
Ensure that the vents of the equipment are not blocked and that the circulation of air is not impeded.
3.4 Connection
Only connect the UPS to an earthed shock-proof socket. Under no
circumstances should the equipment be operated without a protective earth conductor.
The house installation socket must be easily accessible and located in the vicinity of the UPS. In the case of a fixed connection, ensure that the shortest possible cable lengths are used.
Only a VDE-tested and CE-labelled mains cable may be used to connect the UPS to the house installation socket. In the case of a fixed connection, a suitable cable must be used.
3.5 Operation
Only use VDE-tested and CE-labelled electrical cables to connect the consumer load to the UPS. In the case of a fixed connection to the consumer load, a suitable cable must be used.
The fuse protection for the consumer load must always be installed directly in front of it, and never centrally in front of the UPS.
Do not operate any household appliances and power tools, e.g. fan heaters, vacuum cleaners, drills, hairdryers, toasters etc., via the UPS.
Do not connect any consumer loads to the UPS which could overload the equipment (e.g. laser printers).
The sum of the earth fault currents of all consumer loads connected to the UPS must not exceed 3.5mA.
Keep the connecting cables as short as possible and always lay these correctly. Avoid the dangers of laying connecting cables in locations where they may be tripped over, crushed or torn open etc.
The mains power cable must never be disconnected during the operation of the UPS, otherwise the protective earthing of the UPS and the connected consumer loads will be lost.
The UPS equipment contains an energy accumulator (batteries). This means that the output of the UPS may be live even if it is not connected on the line side.
To switch off the UPS completely, first press the switch on the front of the equipment (ON/OFF), wait until the UPS has switched off, then disconnect the
ME series
Page 9 of 31
Warning – danger of electric shocks and burns. Batteries can cause electric shocks and are capable of producing high short­circuit currents which can also inflict burns.
Unauthorised persons must be kept away from batteries.
Do not place batteries against heat sources and do not throw them into a fire as they might explode!
Do not open or destroy batteries. The electrolyte thereby released is extremely dangerous to persons and to the environment (danger of chemical burns to skin and eyes, toxic).
Defective batteries must be disposed of in an environmentally-friendly manner. Never throw batteries into the regular refuse. The local waste disposal regulations must be observed.
Warning – danger of electric shocks. The UPS remains connected to the battery circuit even after it has been disconnected from the mains power supply and has a dangerous voltage potential. Therefore always disconnect the battery circuit before carrying out servicing or maintenance work and make sure that the equipment is isolated from the supply.
power supply (switch off the mains input externally or disconnect the UPS from the mains, e.g. by unplugging it).
Make sure that no fluids or foreign bodies enter the UPS.
3.6 Handling batteries
3.7 Maintenance, servicing and faults
Work on batteries may only be performed and monitored by personnel with appropriate technical knowledge about the required precautions.
Unauthorised persons must be kept away from batteries. When working on the UPS, the following precautions must be taken:
o Remove wristwatches, rings and other metallic objects o Only use electrically-insulated tools
The UPS must not be dismantled.
ME series
Page 10 of 31
4 Introduction
This manual is intended to provide basic information about single-phase line interactive UPS equipment, namely the functional principle, use of the various functions and the procedure to follow in the event of faults. In addition, this manual contains information on transportation and storage as well as handling and installation of the UPS equipment. The planning guidelines in this manual relate only to the specific requirements for UPS equipment. The national and local regulations for electrical installations must be followed without fail during installation. The contents of the description for this equipment may change as a result of technological developments. Though we have endeavoured to make these contents as accurate and clear as possible, we would be grateful for information on any errors which are noted. We accept no liability for errors in this description or their consequences.
The purpose of UPS (Uninterruptible Power Supply) equipment is to protect sensitive electrical devices such as computers, workstations, electronic points of sale, mission-critical instruments, telecommunications equipment, process controls etc. from faults which may arise as a result of poor power supply quality or even power failures. Sensitive devices such as these require comprehensive protection against electrical faults. These may be external faults (e.g. bad weather, operating faults) or faults caused by adjacent devices (e.g. motors, air conditioning units, processing machines, welding equipment etc.). The power supply faults may be summarised as follows:
o Fast and slow line-voltage spikes and fluctuations o Mains power failure o Fast and slow frequency spikes and fluctuations o Mains heterodyning or transient voltages
The UPS equipment monitors the power supply parameters described above using suitable countermeasures to protect the connected users (e.g. changeover to support operation in the event of temporary over- or under­voltage to protect the end devices).