Eemax HA036240, HA027240, HA023240, HA018240 User Manual

EEMAX TROUBLESHOOTING GUIDE
MODELS COVERED: HA018240, HA023240, HA027240,
HA036240
THIS STEP BY STEP TROUBLESHOOTING GUIDE IS DESIGNED FOR THE INSTALLER IF ANY ISSUES ARISE WITH TANKLESS WATER HEATER.
Step by Step Troubleshooting Guide
This Troubleshooting Guide will take you through simple steps to determine any problems or issues with unit. This guide takes you through a sequence of steps that MUST be followed to determine the exact problem.
All Eemax units have a simple design and are very easy to check with the use of a MULTI CLAMP METER able to measure both Voltage and Amperage.
and write down the readings /results on the back pages so when contacting Technical Support you have the information in hand.
Below is an image of a three heating chamber (3 elements) unit. Your unit may have 2 elements or 4 elements. All the steps within the guide are per element, so if you have two element, you make the test twice (once per element), if you have 3 elements, test three times, and 4 elements, test 4 times.
HA018240 and HA024240
2 Heating chambers – 2 Heating elements
HA027240
3 Heating chambers – 3 Heating elements
HA036240
4 Heating Chambers – 4 Heating elements
This Guide is for use by Qualified Electrical Professional
You can contact our Technical Support at 800-543-6163 Mon-Fri 8:00 am5:00 pm. EST. You can visit our web site at
www.eemaxinc.com
or email us at info@eemaxinc.com.
DISCONNECT ALL POWER TO UNIT BEFORE REMOVING
YOU MUST BE ABLE TO MEASURE 208/240 VOLTS ACROSS EACH SET (L1 L1) (L2 L2) (L3 L3)(L4 L4) IF YOU DO NOT THEN IT IS POSSIBLE THE BREAKERS / WIRES ARE CROSSED AND MUST BE CORRECTED.
(EXAMPLE– L1-L1 READS NO VOLTAGE, BUT L1- L2 GIVES YOU VOLTAGE READING)
COVER.
STEP 1
ELECTRICAL CONNECTION
MODEL HA036240 IS SUPPLIED WITH A 8 PRONE TERMINAL BLOCK MARKED (L1 L1) (L2 L2) (L3 L3)( L4 L4). MODEL HA027240 IS SUPPLIED WITH A 6 PRONE TERMINAL BLOCK MARKED (L1 L1) (L2 L2) (L3 L3). MODELS HA018240 AND HA024240 ARE SUPPLED WITH A 4 PRONE TERMINALS BLOCK LABLED (L1 L1) (L2 L2)
EACH ONE OF THE CONNECTION SETS MUST BE CONNECTED TO AN IN­DEPENDENT DOUBLE POLE 40 AMP BREAKER. L1-L1 GOES TO ONE 40 AMP DOUBLE POLE BREAKER, L2-L2 GOES TO ANOTHER 40 AMP DOUBLE POLE BREAKER AND L3-L3 TO ANOTHER 40 AMP DOUBLE POLE BREAKER, AND L4 L4 TO ANOTHER 40 AMP DOUBLE POLE BREAKER NOTE: SPACE SAVING BREAKERS WILL NOT OPERATE PROPERLY
YOU MUST ENSURE THE SET OF WIRES FROM EACH LEG ARE NOT CROSSED
AT THE BREAKERS OTHERWISE THE UNIT WILL NOT FUNCTION AS DESIGNED. IN ORDER TO MAKE SURE THE WIRING IS CONNECTED CORRECTLY PERFORM THE FOLLOWING TEST.
DISCONNECT ALL BREAKERS AT THE SERVICE PANEL. ONCE ALL BREAKERS HAVE BEEN DISCONNECTED MEASURE THE VOLTAGE GOING TO EACH ONE OF THE SETS (L1 L1) (L2 L2) (L3 L3 )
(L4 L4) ALL SHOULD READ 0 VOLTAGE.
NOW– TURN ON 1 BREAKER, IT DOES NOT MATTER WHICH ONE. ONCE ONE BREAKER HAS BEEN TURNED ON, USING YOUR VOLTMETER PLACE ONE PROBE ON L1 AND THE OTHER PROBE ON THE OTHER L1, MEASURE ACROSS (L1-L1) YOU SHOULD GET A READING OF 208- 240V. DO THE SAME FOR (L2-L2) AND (L3-L3) AND (L4 L4).
PERFORM THIS VOLTAGE READING ON ALL LEGS OF TERMINAL BLOCK BOTH AT THE BOTTOM AND TOP OF TERMINAL BLOCK TURNING ON 1 BREAKER AT A TIME.
IF POWER GOING TO THE UNIT IS NOT CORRECT, THE UNIT WILL NOT OPERATE CORRECTLY, SO IT IS IMPORTANT TO PERFORM THIS TEST FIRST, BEFORE PROCEEDING.
THE PROBLEM MIGHT NOT BE AT THE UNIT, BUT AT YOUR ELECTRICAL PANEL, OR BREAKERS.
NOW THAT WE HAVE VERIFIED THAT THE ELECTRICAL CONNECTIONS ARE CORRECT, LETS CONTINUE.