Eemax EX180T2T, EX180T2T EE, EX180T2T S, EX180T2T ML, EX180T2T FS User Manual

...
Three Phase
In USA
Assembled
L1
L2 L3
Triple Module, Commercial/Industrial Thermostatic 3-Phase Heater
Applications
Where tepid water is needed
Multiple lavatories
Restaurants and other food service requirements
Booster applications
Manufacturing and wash down processes
Commercial and industrial
Performance Features
Hot or cold water feed
Available electrical models are 480V Delta (ED models) or 208V Delta (EX models) no neutral leg required
Fitted with 1/2" compression ttings and electrical entry on the bottom
Built in over temp protection
Flow switch activates heater only on demand (no standby heat loss)
Save water – "Point of use application"
Continuous hot water – no storage capacity to run out
Factory set temperature available. Range ambient to 180°F
Capacity to 5 GPM (T3 only), 4 GPM (T2T)
Thermostatic control. Microprocessor provides stable outlet temperatures
Warranty, ve (5) years limited on leaks, one (1) year parts
Field serviceable replaceable cartridge element
Optional Features
Emergency eye/face wash ANSI Z358.1 (EE)
Factory set ambient to 180°F (FS)
Multi lavs 0.3 turn on. Staged up to 4 lavs 105°F-110°F temp setting, aerators supplied (ML)
Sanitation 180°F (S)
N4, N4X (304SS) enclosures
Product Specications:
Dimensions: 18.25" x 12.25" x 4.5"
Weight: 15 lb
Cover: Powder Coated Steel
Color: White
Element: Triple replaceable Nichrome cartridge elements
insert
Fittings:
1/2" compression ttings at bottom of unit
Min. Dynamic Operating Pressure: 25 PSI
Max. Dynamic Operating Pressure: 150 PSI
U.S. Patent #'s: 4,762,980 and 4,960,976
Special Design Service
Inquiries for units for unique applications are welcome. Call our Technical Service department at 1-800-543-6163.
Electrical conguration and requirements
All Eemax three phase units are custom made to order and as such, are non-returnable and non-refundable. Check your electrical supply, making sure all criteria for operating your Eemax water heater are met.
Eemax 600V, 480V and 208V
Three Phase Units Delta Conguration
Requires: 3 Lives and 1 Ground (earth)
Suggested Specication
Tankless water heater shall be an Eemax "Three Phase" model number _________________________.
Element shall be replaceable cartridge insert. Element shall be iron free, Nickel Chrome material. Heater shall be tted with 1/2" compression ttings. Heater shall be installed upright with water connections on bottom. Hot water storage tanks prohibited. Unit shall be Eemax or approved equal.
NOTE: Refer to rating chart for product information.
Enclosure to be tted with the following features:
_____ EE
_____ FS
_____ ML
_____ S
_____ N4 _____ N4X NEMA 4 stainless steel, corrosion-resistant cabinet
Specications
Tankless Electric Water Heater
*The wetted surface of this product contacted by water contains less than
0.25% lead and meets NSF/ANSI 372
Emergency Eyewash. Meets ANSI tepid water
requirements
Factory Set. Customer specied factory-set not to
exceed temperature ambient to 180°F
Multi lavs 0.3 GPM turn on, staged up to 4 lavs
105°F-110°F temp setting, aerators supplied
Sanitation. Factory preset not to exceed
temperature of 180°F
NEMA 4 steel cabinet with powder coat nish
Information and product specications contained in this document are subject to change without notice. REV 2020-01
Three Phase
20.00
2.21 7.02
8.78
18.19
12.14
CONNECTION
Triple Module, Commercial/Industrial Thermostatic 3-Phase Heater
Specications
Tankless Electric Water Heater
Sux Denitions
EE Meets ANSI Z358.1 emergency
FS ML Multi lavs 0.3 turn on. Staged
S
1.87
1.30 7.02
NEMA 4/4X
2.89
eye/face wash tepid water require­ments
Factory set ambient to 180°F
up to 4 lavs 105°F-110°F temp
setting
Sanitation 180°F
OUTLET
INLET
ELECTRICAL
20.00
INLETOUTLET
18.50
4XØ .500 MOUNTING HOLES
.90
18.50
1.93
RECOMMENDED
MODEL NUMBER kW
VOLTS 208 Three Phase Delta
C
EX180T2T
C
EX180T2T EE
C
EX180T2T S
C
EX180T2T ML
C
EX180T2T FS
C
EX180T3
C
EX180T3 EE
C
EX180T3 S
C
EX180T3 FS
C
EX240T2T
C
EX240T2T EE
C
EX240T2T S
C
EX240T2T ML
C
EX240T2T FS
C
EX240T3
C
EX240T3 EE
C
EX240T3 S
C
EX240T3 FS
VOLTS 480 Three Phase Delta
ED020480T2T
ED020480T2T S
ED020480T2T ML
ED020480T2T FS
ED020480T3
ED020480T3 EE
ED020480T3 S
ED024480T2T
ED024480T2T S
ED024480T2T ML
ED024480T2T FS
ED024480T3
ED024480T3 EE
ED024480T3 S
ED032480T2T
ED032480T2T S
ED032480T2T ML
ED032480T2T FS
ED032480T3
ED032480T3 EE
ED032480T3 S
ED032480T3 FS
†Temperature electronically limited to factory preset not to exceed temperature. "C" indicates evaluation and compliance to either Underwriters Laboratories (UL) or Intertek (ETL) under CAN/CSA-C22.2 No.
AMPS
PER PHASE
18 50/phase 8 AWG 0.7 4.0 61° 49° 41° 31°
18 50/phase 8 AWG 0.7 4.0 49° 41° 31°
18 50/phase 8 AWG 0.7 4.0 61° 49° 41° 31°
18 50/phase 8 AWG 0.3 4.0 61° 49° 41° 31°
18 50/phase 8 AWG 0.7 4.0 61° 49° 41° 31°
18 50/phase 8 AWG 2.0 5.0 61° 49° 41° 31° 25°
18 50/phase 8 AWG 2.0 5.0 49° 41° 31° 25°
18 50/phase 8 AWG 2.0 5.0 61° 49° 41° 31° 25°
18 50/phase 8 AWG 2.0 5.0 61° 49° 41°
24 67/phase 4 AWG 0.7 4.0 82° 66° 55° 41°
24 67/phase 4 AWG 0.7 4.0 55° 41°
24 67/phase 4 AWG 0.7 4.0 82° 66° 55° 41°
24 67/phase 4 AWG 0.3 4.0 82° 66° 55° 41°
24 67/phase 4 AWG 0.7 4.0 82° 66° 55° 41°
24 67/phase 4 AWG 2.0 5.0 82° 66° 55° 41° 33°
24 67/phase 4 AWG 2.0 5.0 55° 41° 33°
24 67/phase 4 AWG 2.0 5.0 82° 66° 55° 41° 33°
24 67/phase 4 AWG 2.0 5.0 82° 66° 55° 41° 33°
20 24/phase 10 AWG 0.7 4.0 68° 55° 46° 34°
20 24/phase 10 AWG 0.7 4.0 68° 55° 46° 34°
20 24/phase 10 AWG 0.3 4.0 68° 55° 46° 34°
20 24/phase 10 AWG 0.7 4.0 68° 55° 46° 34°
20 24/phase 10 AWG 2.0 5.0 68° 55° 46° 34° 27°
20 24/phase 10 AWG 1.0 5.0 55° 46° 34° 27°
20 24/phase 10 AWG 2.0 5.0 68° 55° 46° 34° 27°
24 29/phase 10 AWG 0.7 4.0 82° 66° 55° 41°
24 29/phase 10 AWG 0.7 4.0 82° 66° 55° 41°
24 29/phase 10 AWG 0.3 4.0 82° 66° 55° 41°
24 29/phase 10 AWG 0.7 4.0 82° 66° 55° 41°
24 29/phase 10 AWG 2.0 5.0 82° 66° 55° 41° 33°
24 29/phase 10 AWG 1.0 5.0 55° 41° 33°
24 29/phase 10 AWG 2.0 5.0 82° 66° 55° 41° 33°
32 38/phase
32 38/phase 8 AWG 0.7 4.0 109° 87° 73° 55°
32 38/phase 8 AWG 0.3 4.0 109° 87° 73° 55°
32 38/phase 8 AWG 0.7 4.0 109° 87° 73° 55°
32 38/phase 8 AWG 2.0 5.0 109° 87° 73° 55° 44°
32 38/phase 8 AWG 1.0 5.0 55° 44°
32 38/phase 8 AWG 2.0 5.0 109° 87° 73° 55° 44°
32 38/phase 8 AWG 2.0 5.0 109° 87° 73° 55° 44°
WIRE SIZE
(75° C/CU)
8 AWG 0.7 4.0 109° 87° 73° 55°
TURN-ON
(GPM)
MAX FLOW
(GPM)
TEMPERATURE RISE °F
2.0
2.5
3.0
GPM
GPM
64/No. 88. CNL SKUs are Canada specic.
GPM
4.0
GPM
31° 25°
5.0
GPM
Information and product specications contained in this document are subject to change without notice. REV 2020-01
Loading...