Eemax AP061600, AP071600, AP102600, AP130600, AP150600 User Manual

SafeAdvantage™ (NEMA 4 Incl.)
In USA
Assembled
For Safety Applications – Eye/Face Wash and Drench Showers
Eye/face wash
Emergency drench showers
Where tepid water is needed
Performance Features
90°F max. output temperature
Fully Modulating - Predictive control algorithm and diverse safety features ensures conformity to ANSI Z358.1 tepid water without additional mixing valves (check local codes)
Fast response rate eliminates the requirement for any additional hot water purge system (no drainage required)
T&P not required per UL499 - Check local codes
Thermo-Optical Sensor for infrared element monitoring
Field programmable, updatable rmware, and adjustable turn-on
LCD display and control with built in diagnostics
Standard model includes NEMA 4 cabinet; alternative cabinets are available for upgrade
Optional Features
N4X (304SS) N4X6 (316SS) enclosures
Free standing legs
Freeze protection for harsh climate, up to -30°F
Non-fused or fused electrical disconnect
GFCI
Explosion proof – C1D2 Compliant, local certication required. Class Z purge and pressurization system provided with pressure switch for alarm controls. For classication other than C1D2 please contact the factory to discuss options.
Siren and Beacon – audible and visual alarm (C1D2 rated when paired with Explosion proof package)
Product Specications
Min. Operating Pressure: 35 PSI
Max. Operating Pressure: 150 PSI
Optimum Operating Pressure: 60-90 PSI
U.S. Patent #'s: US20140023354 and US20140178057
Installation Requirements
Properly sized water hammer arrestor
Minimum 35 PSI dynamic pressure at inlet
Sediment lter installed on inlet
Special Design Service
Inquiries for units for unique applications are welcome. Call our Technical Service department at 1-800-543-6163.
Custom orders non-refundable
Suggested Specication
Tankless water heater shall be an Eemax SafeAdvantage model number AP_________________________.
Factory installation in a ______(N4/N4X/N4X6) enclosure.
Enclosure to be tted with the following features:
_____ FP Freeze protection (-30°F) _____ EDS Non-fused disconnect _____ FDS Fused disconnect _____ EP Explosion proof (C1D2 compliant) _____ GFCI True RMS GFCI with digital display and reset _____ SK 24" legs for free standing applications _____ RD Remote display _____ SB Siren and Beacon _____ DC Dry contact _____ ES Emergency stop - push button
Tankless water heater must have water connections on the bottom, and be constructed with NSF61 listed materials. Direct heating element to be non-ferrous, cartridge style, designed for eld replacement. Tankless water heater to utilize a dual PID algorithm, actively managing power application to real-time system demand. Integrated ow meter capable of volumes in excess of 30 GPM drives predictive control algorithm. Water heater must be protected by redundant safeties. Redundant safeties to include thermo mechanical safety switches, infrared element monitoring via thermo optical sensors, and dual temperature monitoring via primary control board. Tankless water heater user interface must have the following capabilities:
Specications
Tankless Electric Water Heater
*The wetted surface of this product contacted by water contains less than
0.25% lead and meets NSF/ANSI 372
Selectable display including Celsius/Fahrenheit, inlet temperature, outlet temperature, ow rate, and setpoint temperature. Capable of displaying ow rate in gallons per minute or liters per minute. Diagnostic features to include error and fault code display. Control board must maintain error/fault history of 9 events. Capable of factory coded temperature setting (max. and min.) Capable of rmware upgrades via USB port Capable of BMS integration - contact factory Conforms to ANSI Z358.1 tepid water without additional mixing or purge features (inlet temperatures must not exceed 100ºF).
Information and product specications contained in this document are subject to change without notice. REV 2020-01
5
SafeAdvantage (NEMA 4 Incl.)
L1
L2 L3
For Safety Applications – Eye/Face Wash and Drench Showers
Specications
Tankless Electric Water Heater
Sux Denitions
EE Emergency Eyewash. Max. outlet
temperature 90°F. Conforms to ANSI Z3581.1 tepid water without additional mixing valve. Shipped with display "Locked."
EFD Emergency Eye, Face & Drench.
Max. outlet temperature 90°F. Conforms to ANSI Z3581.1 tepid water without additional mixing valve. Shipped with display "Locked."
Note: Models with an EE or EFD sufx are not to be fed to a thermostatic mixing valve. If a thermo­static mixing valve is required, heater of non EE or EFD must be specied. Note: Models with an EE or EFD sufx have a 90°F maximum temperature. Temperature rise data is provided for reference, but temperature
is electronically limited to factory preset not to
exceed temperature.
PHD Pressure Drop 63-150 kW
Flow Rate (GPM) Delta PSI
2 0 3 0
4 0 6 0 8 1
11 3 12 4 15 6 18 8 20 10 22 13 24 14 27 17 30 22 33 26 35 30 37 34 40 43
MODEL NUMBER
VOLTS 208 Three Phase Delta
AP032208 EE N4
AP032208 EE N4X
AP036208 EE N4
AP036208 EE N4X
AP041208 EFD N4
AP041208 EFD N4X
AP054208 EFD N4
AP054208 EFD N4X
AP064208 EFD N4
AP064208 EFD N4X
VOLTS 480 Three Phase Delta
AP036480 EE N4
AP036480 EE N4X
AP039480 EE N4
AP039480 EE N4X
AP048480 EFD N4
AP048480 EFD N4X
AP054480 EFD N4
AP054480 EFD N4X
AP063480 EFD N4
AP063480 EFD N4X
AP072480 EFD N4
AP072480 EFD N4X
AP096480 EFD N4
AP096480 EFD N4X
AP108480 EFD N4
AP108480 EFD N4X
AP126480 EFD N4
AP126480 EFD N4X
C
AP144480 EFD N4
C
AP144480 EFD N4X
VOLTS 600 Three Phase Delta
C
AP061600 EFD N4
C
AP061600 EFD N4X
C
AP071600 EFD N4
C
AP071600 EFD N4X
C
AP102600 EFD N4
C
AP102600 EFD N4X
C
AP130600 EFD N4
C
AP130600 EFD N4X
C
AP150600 EFD N4
C
AP150600 EFD N4X
† Temperature electronically limited to factory preset temperature.
"C" indicates evaluation and compliance to either Underwriters Laboratories (UL) or Intertek (ETL) under CAN/CSA-C22.2 No. 64/No. 88.
kW
109,189
32
109,189
32
122,832
36
122,832
36
139,898
41
139,898
41
184,256
54
184,256
54
218,377
64
218,377
64
122,837
36
122,837
36
133,074
39
133,074
39
48 163,783 58 1.0 6 AWG 82° 66° 55° 16° 14° 13° 11°
48 163,783 58 1.0 6 AWG 82° 66° 55° 16° 14° 13° 11°
184,256
54
184,256
54
63 214,965 76 2.5 4 AWG 86° 72° 22° 19° 17° 14°
63 214,965 76 2.5 4 AWG 86° 72° 22° 19° 17° 14°
245,674
72
245,674
72
96 327,552 116 2.5 1 AWG 33° 29° 25° 22°
96 327,552 116 2.5 1 AWG 33° 29° 25° 22°
368,511
108
368,511
108
126 429,930 151 2.5 2/0 AWG 43° 37° 33° 29°
126 429,930 151 2.5 2/0 AWG 43° 37° 33° 29°
491,348
144
491,348
144
208,141
61
208,141
61
242,262
71
242,262
71
348,038
102
348,038
102
130 443,578 125 2.5 1 AWG 44° 39° 34° 30°
130 443,578 125 2.5 1 AWG 44° 39° 34° 30°
150 511,821 144 2.5 1/0 AWG 51° 45° 39° 34°
150 511,821 144 2.5 1/0 AWG 51° 45° 39° 34°
BTU/H
AMPS
PER
PHASE
89 1.0 3 AWG 73° 55° 44° 36° 11° 10°
89 1.0 3 AWG 73° 55° 44° 36° 11° 10°
100 1.0 3 AWG 82° 61° 49° 41° 12° 11°
100 1.0 3 AWG 82° 61° 49° 41° 12° 11°
113 1.0 2 AWG 70° 56° 47° 14° 12° 11°
113 1.0 2 AWG 70° 56° 47° 14° 12° 11°
150 1.5 1/0 AWG 74° 61° 18° 16° 14° 12°
150 1.5 1/0 AWG 74° 61° 18° 16° 14° 12°
178 2.5 3/0 AWG 87° 73° 22° 19° 17° 15°
178 2.5 3/0 AWG 87° 73° 22° 19° 17° 15°
43 1.0 8 AWG 82° 61° 49° 41° 12° 11°
43 1.0 8 AWG 82° 61° 49° 41° 12° 11°
47 1.0 8 AWG 89° 67° 53° 44° 13° 12° 10°
47 1.0 8 AWG 89° 67° 53° 44° 13° 12° 10°
65 1.5 6 AWG 74° 61° 18° 16° 14° 12°
65 1.5 6 AWG 74° 61° 18° 16° 14° 12°
87 2.5 3 AWG 82° 25° 21° 19° 16°
87 2.5 3 AWG 82° 25° 21° 19° 16°
130 2.5 1 AWG 37° 32° 28° 25°
130 2.5 1 AWG 37° 32° 28° 25°
173 2.5 2/0 AWG 49° 43° 38° 33°
173 2.5 2/0 AWG 49° 43° 38° 33°
59 2.5 6 AWG 83° 69° 21° 18° 16° 14°
59 2.5 6 AWG 83° 69° 21° 18° 16° 14°
68 2.5 4 AWG 81° 24° 21° 19° 16°
68 2.5 4 AWG 81° 24° 21° 19° 16°
98 2.5 3 AWG 35° 30° 27° 23°
98 2.5 3 AWG 35° 30° 27° 23°
TURN ON
(GPM)
RECOMMENDED
WIRE SIZE
(75° C/CU)
3.0
GPM
4.0
GPM
5.0
GPM
TEMPERATURE RISE °F
6.0
20.0
GPM
GPM
23.0 GPM
26.0 GPM
30.0 GPM
Electrical conguration and requirements
All Eemax three phase units are custom made to order and as such, are non-returnable and non-refundable. Check your electrical supply, making sure all criteria for operating your Eemax water heater are met.
Eemax 600V, 480V and 208V Three Phase Units Delta Conguration
Requires: 3 Lives and 1 Ground (earth)
6
Information and product specications contained in this document are subject to change without notice. REV 2020-01