Eemax AP032208, AP032208 EE, AP032208 S, AP036208, AP036208 EE User Manual

...
In USA
Assembled
SpecAdvantage
For Commercial and Industrial Applications
Applications
Designed for low duty cycle applications where precise temperature controls and low pressure drop are required
Performance Features
Designed for commercial and industrial applications
Capable of high volume and high temperature applications at low duty cycle
Fully modulating - Predictive control algorithm and diverse safety features ensures precise temperature control
T&P not required per UL499 (check local codes)
Thermo-Optical Sensor for infrared element monitoring
Field programmable, updatable rmware, and adjustable
Optional Features (NEMA cabinet required)
N4 (powder coated steel), N4X (304SS) N4X6 (316SS) enclosures
Free standing legs
Freeze protection for harsh climate, up to -30°F
Non-fused or fused electrical disconnect
GFCI
Explosion proof – C1D2 Compliant, local certication required. Class Z purge and pressurization system provided with pressure switch for alarm controls. For classication other than C1D2 please contact the factory to discuss options.
Siren and beacon - audible and visual alarm (C1D2 compliant when paired with explosion proof package)
Product Specications
Min. Operating Pressure: 35 PSI
Max. Operating Pressure: 150 PSI
Optimum Operating Pressure: 60-90 PSI
U.S. Patent #'s: US20140023354 and US20140178057
Installation Requirements
Properly sized water hammer arrestor
Minimum 35 PSI dynamic pressure at inlet
Sediment lter installed on inlet
Special Design Service
Inquiries for units for unique applications are welcome. Call our Technical Service department at 1-800-543-6163.
Custom orders non-refundable
Information and product specications contained in this document are subject to change without notice. REV 2020-01
Specications
Tankless Electric Water Heater
*The wetted surface of this product contacted by water contains less than
0.25% lead and meets NSF/ANSI 372
Suggested Specication
Tankless water heater shall be an Eemax SpecAdvantage model number AP_________________________.
Optional factory installation in a ____(N4/N4X/N4X6) enclosure.
Enclosure to be tted with the following features:
_____ FP Freeze protection (-30°F) _____ EDS Non-fused disconnect _____ FDS Fused disconnect _____ EP Explosion proof (C1D2 compliant) _____ GFCI True RMS GFCI with digital display and reset _____ SK 24" legs for free standing applications _____ RD Remote display _____ SB Siren and Beacon _____ DC Dry contact _____ ES Emergency stop - push button
Tankless water heater must have water connections on the bottom, and be constructed with NSF 61 listed materials. Direct heating element to be non-ferrous, cartridge style, designed for eld replacement. Tankless water heater to utilize a dual PID algorithm, actively managing power application to real-time system demand. Integrated ow meter capable of volumes in excess of 30 GPM drives predictive control algorithm. Water heater must be protected by redundant safeties. Redundant safeties to include thermo mechanical safety switches, infrared element monitoring via thermo optical sensors, and dual temperature monitoring via primary control board. Tankless water heater user interface must have the following capabilities:
Selectable display including Celsius/Fahrenheit, inlet temperature, outlet temperature, ow rate, and setpoint temperature.
Capable of displaying ow rate in gallons per minute or liters per minute.
Diagnostic features to include error and fault code display.
Control board must maintain error/fault history of 9 events.
Capable of factory coded temperature setting (max. and min.)
Capable of rmware upgrades via USB port
Capable of BMS integration - contact factory
Compliant with ANSI Z358.1 tepid water without additional mixing or purge features (inlet temperatures must not exceed 100°F when selecting an EE or EFD option)
9
SpecAdvantage
L1
L2 L3
For Commercial and Industrial Applications
Specications
Tankless Electric Water Heater
Sux Denitions
S Sanitation. Shipped at 180°F
with temp range of 100°F-190°F max.
EE Emergency Eyewash. Max.
outlet temperature 90°F. Conforms to ANSI Z3581.1 tepid water without additional mixing valve. Shipped with display "Locked."
EFD Emergency Eye, Face &
Drench. Max. outlet temperature
90°F. Conforms to ANSI Z3581.1 tepid water without additional mixing valve. Shipped with display "Locked."
Note: Models with an EE or EFD sufx are not to be fed to a thermostatic mixing valve. If a thermo­static mixing valve is required, heater of non EE or EFD must be specied. Note: Models without a sufx are set to a maximum temperature of 140°F if the turn on is greater than 1.5 GPM. Models with a 1.0 or 1.5 GPM turn on are limited to 120°F.
PHD Pressure Drop 63-150 kW
Flow Rate (GPM) Delta PSI
2 0 3 0
4 0 6 0 8 1
11 3 12 4 15 6 18 8 20 10 22 13 24 14 27 17 30 22 33 26 35 30 37 34 40 43
MODEL NUMBER
VOLTS 208 Three Phase Delta
AP032208
AP032208 EE
AP032208 S
AP036208
AP036208 EE
AP036208 S
AP041208
AP041208 EFD
AP041208 S
AP054208
AP054208 EFD
AP054208 S
AP064208
AP064208 EFD
AP064208 S
VOLTS 480 Three Phase Delta
AP036480
AP036480 EE
AP036480 S
AP039480
AP039480 EE
AP039480 S
AP048480
AP048480 EFD
AP048480 S
AP054480
AP054480 EFD
AP054480 S
AP063480
AP063480 EFD
AP063480 S
AP072480
AP072480 EFD
AP072480 S
AP096480
AP096480 EFD
AP096480 S
AP108480
AP108480 EFD
AP108480 S
AP126480
AP126480 EFD
AP126480 S
C
AP144480
C
AP144480 EFD
C
AP144480 S
VOLTS 600 Three Phase Delta
C
AP061600 EFD
C
AP071600 EFD
C
AP102600 EFD
C
AP130600 EFD
C
AP150600 EFD
* Units with a 1.0 or 1.5 GPM turn-on are limited to 120°F only. Contact Eemax support for applications above 120°F.
† Temperature electronically limited to factory preset temperature.
"C" indicates evaluation and compliance to either Underwriters Laboratories (UL) or Intertek (ETL) under CAN/CSA-C22.2 No. 64/No. 88. ** Contact Eemax for applications requiring lower turn on.
kW BTU/H
109,189
32
109,189
32
109,189
32
122,837
36
122,837
36
122,837
36
143,310
41
143,310
41
143,310
41
184,256
54
184,256
54
184,256
54
218,377
64
218,377
64
218,377
64
122,837
36
122,837
36
122,837
36
133,074
39
133,074
39
133,074
39
163,783
48
163,783
48
163,783
48
184,256
54
184,256
54
184,256
54
214,965
63
214,956
63
214,965
63
245,674
72
245,674
72
245,674
72
327,566
96
327,566
96
327,566
96
368,511
108
368,511
108
368,511
108
429,930
126
429,930
126
429,930
126
491,348
144
491,348
144
491,348
144
208,141
61
242,262
71
348,038
102
443,578
130
511,821
150
AMPS
PER
PHASE
89 1.0* 3 AWG 73° 55° 44° 36° 11° 10°
89 1.0 3 AWG 55° 44° 36° 11° 10°
89 2.5** 3 AWG 73° 55° 44° 36° 11° 10°
100 1.0* 3 AWG 82° 61° 49° 41° 12° 11°
100 1.0 3 AWG 49° 41° 12° 11°
100 2.5** 3 AWG 82° 61° 49° 41° 12° 11°
113 1.0* 2 AWG 93° 70° 56° 47° 14° 12° 11°
113 1.0 2 AWG 56° 47° 14° 12° 11°
113 2.5** 2 AWG 93° 70° 56° 47° 14° 12° 11°
150 1.5* 1/0 AWG 92° 74° 61° 18° 16° 14° 12°
150 1.5 1/0 AWG 18° 16° 14° 12°
150 6.0** 1/0 AWG 123° 92° 74° 61° 18° 16° 14° 12°
178 2.5 3/0 AWG 109° 87° 73° 22° 19° 17° 15°
178 2.5 3/0 AWG 22° 19° 17° 15°
178 6.0** 3/0 AWG 146° 109° 87° 73° 22° 19° 17° 15°
43 1.0* 8 AWG 82° 61° 49° 41° 12° 11°
43 1.0 8 AWG 49° 41° 12° 11°
43 2.5** 8 AWG 82° 61° 49° 41° 12° 11°
47 1.0* 8 AWG 89° 67° 53° 44° 13° 12° 10°
47 1.0 8 AWG 53° 44° 13° 12° 10°
47 2.5** 8 AWG 89° 67° 53° 44° 13° 12° 10°
58 1.0* 6 AWG 109° 82° 66° 55° 16° 14° 13° 11°
58 1.0 6 AWG 55° 16° 14° 13° 11°
58 2.5** 6 AWG 109° 82° 66° 55° 16° 14° 13° 11°
65 1.5* 6 AWG 92° 74° 61° 18° 16° 14° 12°
65 1.5 6 AWG 18° 16° 14° 12°
65 2.5** 6 AWG 123° 92° 74° 61° 18° 16° 14° 12°
76 2.5 4 AWG 108° 86° 72° 22° 19° 17° 14°
76 2.5 4 AWG 22° 19° 17° 14°
76 6.0** 4 AWG 143° 108° 86° 72° 22° 19° 17° 14°
87 2.5 3 AWG 98° 82° 25° 21° 19° 16°
87 2.5 3 AWG 25° 21° 19° 16°
87 6.0** 3 AWG 123° 98° 82° 25° 21° 19° 16°
116 2.5 1 AWG 109° 33° 29° 25° 22°
116 2.5 1 AWG 33° 29° 25° 22°
116 6.0** 1 AWG 131° 109° 33° 29° 25° 22°
130 2.5 1 AWG 37° 32° 28° 25°
130 2.5 1 AWG 37° 32° 28° 25°
130 6.0** 1 AWG 148° 123° 37° 32° 28° 25°
151 2.5 2/0 AWG 43° 37° 33° 29°
151 2.5 2/0 AWG 43° 37° 33° 29°
151 6.0** 2/0 AWG 143° 43° 37° 33° 29°
173 2.5 2/0 AWG 49° 43° 38° 33°
173 2.5 2/0 AWG 49° 43° 38° 33°
173 6.0** 2/0 AWG 49° 43° 38° 33°
59 2.5 6 AWG 21° 18° 16° 14°
68 2.5 4 AWG 24° 21° 19° 16°
98 2.5 3 AWG 35° 30° 27° 23°
125 2.5 1 AWG 44° 39° 34° 30°
144 2.5 1/0 AWG 51° 45° 39° 34°
TURN ON
(GPM)
RECOMMENDED
WIRE SIZE
(75° C/CU)
3.0
GPM
4.0
GPM
5.0
GPM
TEMPERATURE RISE °F
6.0
20.0
GPM
GPM
23.0 GPM
26.0 GPM
30.0 GPM
Electrical conguration and requirements
All Eemax three phase units are custom made to order and as such, are non-returnable and non-refundable. Check your electrical supply, making sure all criteria for operating your Eemax water heater are met.
Eemax 600V, 480V and 208V Three Phase Units Delta Conguration
Requires: 3 Lives and 1 Ground (earth)
10
Information and product specications contained in this document are subject to change without notice. REV 2020-01