Edwards Signaling Series 6534-110-N5 Electronic Strobe Signal Appliance Installation Guide

Installation Instructions for Catalog Series 6534-110-N5
Electronic Strobe Signal Appliance
SAFETY INSTRUCTIONS
A qualified electrician familiar with local code requirements must install this product. Failure to follow the safety precau­tions in this instruction sheet could result in product or property damage, severe personal injury, or death.
WARNINGS
This device will not operate without electrical power. As fires frequently cause power interruptions, discuss further safeguards with your local fire protection specialist.
T o reduce the risk of shock, do not connect A C or battery power to the fire alarm control panel until directed in these instructions.
To reduce the risk of shock, do not tamper with unit when circuit is energized. Disconnect all power and allow 5 minutes for stored energy to dissipate before handling.
CAUTION
Electrical supervision requires wire run to be broken at each device connection.
This unit is not serviceable or repairable. Should the unit fail to operate, contact the supplier for replacement.
DESCRIPTION
Catalog Number 6534-110-N5 is an electronic strobe signaling appliance that complies with ADA regulations, Chapter 28 Part
36. These appliances are intended for indoor/outdoor use in gen-
eral signaling applications. For outdoor use, the strobe must be installed with an Edwards weatherproof back box.
this information with applicable local codes to maximize device effectiveness.
NOTE: Refer to Chart 1 for installation restrictions.
1. Select any single gang 2" (51 mm) deep minimum electrical box. Install the electrical box using suitable hardware.
For Flush Mount: 1 gang Handy box, or Iberville 1104 style, or equivalent.
For Surface Mount: Edwards, Wiremold 1 gang box, or equivalent.
For Outdoor Mount (Surface Only): Edwards 897B-008 or 897C-008 red weatherproof box.
2. Bring signaling circuit field wiring into the electrical box.
3. (Figure 2) Position the mounting plate onto the electrical box. Secure the plate using two pan head slotted screws (supplied).
4. (Figure 3) Connect this unit to a signal circuit that outputs 120V AC 60 Hz for signal power. For additional wiring connection details, see the installation instructions for the signaling application.
5. When connections are complete, mount the unit onto the mounting plate. Fasten it using two countersunk Phillip head screws (supplied).
6. Apply power and activate the strobe unit to verify that it is operating properly.
MAINTENANCE
CAUTION
This unit is not serviceable or repairable. Should the unit fail to operate, contact the supplier for replacement.
Perform a visual inspection and an operational test twice a year or as directed by the local authority having jurisdiction.
INSTALLATION
CHART 1 - SPECIFICATIONS FOR CATALOG SERIES 6534-110-N5 STROBE
Agency Approvals UL Listed to: Standard 1638 - Visual Signal Appliances (Indoor/Outdoor)
Complies with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule
Operating Voltage 120V AC
Operating Current 90 mA (RMS)
Flash Rate (per second) 1 fps
Light Output (candela) UL 1638 120 cd Operating Environment - Indoor 93% relative humidity @ 86ºF (30ºC), 32 to 120ºF (0 to 49ºC) variable ambient temperature
Outdoor 95% relative humidity @ 90ºF (32ºC), -40 to 150ºF (-40 to 66ºC) variable ambient temperature
Peak current rating < 350 mA
P-047550-1690 ISSUE 1
© 1996
90 75 60 45 30
15
3
0
-15
-30
-45
-60
-75
-90 0 25 50 75 100 125 150 175
(cd)
Horizontal
90 75 60 45 30
15
3
0
-15
-30
-45
-60
-75
-90 0 25 50 75 100 125 150 175
(cd)
Vertical
0
25
50
75
10 0
12 5
15 0
Ceiling
Figure 1. Typical Strobe Light Output Distribution Patterns
O
-90
HORIZONTAL
-90
UL Minimum Requirement
Typical Output
O
90
VERTICAL
O
O
90
SIDE VIEW,
WALL MOUNTED
FRONT VIEW,
WALL MOUNTED
MOUNTING
PLATE
Figure 2. Detailed View
KEY:
- Wire nut
- Strobe
CAUTION: This unit is designed to be used on signal circuits that output a voltage of 120V AC. Electrical supervision requires wire run to be broken at each device. Do not loop strobe leads around signaling circuit field wires.
Figure 3. Connecting Strobe Unit
SIDE VIEW,
CEILING MOUNTED
P-047550-1690 ISSUE 1