Edwards Signaling Series 51SIN AdaptaBeacon Installation Guide

Installation Instructions for Catalog Series
51SIN Adaptabeacon
®
Signals
WARNING
To prevent leakage and a potential shock hazard, use care when disassembling the signal to prevent tearing of the permanently affixed weatherproof gaskets.
InstallationInstallation
Installation
InstallationInstallation
Install in accordance with the latest edition of the Na­tional Electrical Code and local regulations.
Figure 1. Catalog Series 51SIN
SpecificationsSpecifications
Specifications
SpecificationsSpecifications
Catalog Lamp Number Ratings Life****
51SIN(*)-G1 24V DC 3,180 Hours
51SIN(*)-N5-40W** 120V 50/60 Hz 25,000 Hours
*Letter in this position signifies the color of the lens -- R - red, A
- amber, B - blue, C - clear, G - green, or M - magenta. **UL and cUL listed ***Bulb manufacturer's lumen rating ****Projected lamp life based on manufacturer's calculated lamp life at 65 FPM and 50% duty cycle.
DescriptionDescription
Description
DescriptionDescription
Catalog Series 51SIN Adaptabeacon signals are general purpose visual/audible signaling appliances. The 51SIN series are combination steady-on lights with horn. The signals are PLC compatible and can be flashed either from a PLC or an external relay.
The 51SIN series signals are suitable for indoor or out­door (weatherproof) installation and utilize a standard base that allows direct surface mounting, mounting on a 4" (102 mm) octagon box, or mounting on 1/2" (13 mm) NPT conduit. For outdoor installation, the signals must be mounted on conduit.
0.80A
.402 Lumens***
0.29A
265 Lumens***
1. See Figure 1. Remove the screw in the clamp ring, remove the ring, and lift the lens/lamp assembly off of the base.
2. For indoor installation, the signal may be direct surface mounted, mounted on a 4" (102 mm) octagon box, or mounted on 1/2" (13 mm) NPT conduit. For outdoor (weatherproof) installation, the signal must be conduit mounted. Install the signal base using one of the following applicable mounting procedures.
a. Direct Surface Mounting (indoor installation
only)
Remove the two knockouts for mounting screws from the bottom of the signal base.
Route the field wiring from the required power source through the conduit entrance hole in the base.
Fasten the base to the surface by installing two #10 wood screws (not supplied) or other suitable hardware through the knockout holes in the base. Proceed to step 3 for wiring connections.
b. Mounting on a 4" (102 mm) Octagon Box
(indoor installation only)
Remove the two knockouts for mounting screws from the bottom of the signal base.
Route the field wiring from the required power source through the conduit entrance hole in the base.
Fasten the base to the octagon box (not supplied) by installing the screws supplied with the box through the knockout holes in the base. Proceed to step 3 for wiring connections.
WARNING
To prevent electrical shock, ensure that power is disconnected before installing the signal.
c. Mounting on 1/2" (13 mm) NPT Conduit
(indoor or outdoor installation)
WARNING
To prevent leakage and a potential shock hazard when mounting outdoors, install the signal with the dome facing directly up.
Route the field wiring from the required power source through the conduit entrance hole in the
P/N 3100699 ISSUE 1 © 2003
base. Install the base on the conduit (not supplied).
3. Connect the field wiring to the terminal block in the base of the unit. Polarity must be observed on DC units. Connect the green ground wire lead in accordance with local codes. Place the connected wires inside the base and reassemble the signal on the base.
4. Turn on power and verify that the signal operates properly.
TT
rr
oubleshootingoubleshooting
T
r
oubleshooting
TT
rr
oubleshootingoubleshooting
Should the lamp fail to operate, check that power is on. If power is on, the lamp requires replacement.
3. Turn the bulb counterclockwise and pull straight up to remove.
CAUTION
To prevent property damage and injury. touch glass with bare fingers; grasp glass with a soft, clean cloth or with packaging supplied with the replacement lamp.
4. Grasping bulb with a soft, clean cloth, press into socket and turn clockwise.
5. Reassemble the signal.
6. Turn on power and verify that the signal operates properly.
do not
MaintenanceMaintenance
Maintenance
MaintenanceMaintenance
Lamp Replacement
WARNING
To prevent electrical shock, do not remove or insert lamp when unit is energized.
Refer to the Replacement Parts section below for the required type of lamp.
1. Disconnect power to the signal.
2. Remove the three screws from the top of the skirt and lift off the lens and skirt.
Catalog Number Replacement Part
51SIN(*)-G1
Lamp
P/N P-041695-0099 or Industry Trade No. 1638
Horn
P/N P-047570-0743
Cleaning
CAUTION
To prevent damage to the lens and dome, use abrasive materials or cleaners.
The signal's lens and/or dome should be peridodically cleaned to maintain optimum light visibility. These items may be cleaned with a soft cloth or sponge using mild detergent. Ensure that the lens or dome is completely dry before replacing.
(32W, double contact, bayonet base)
do not
P/N 3100699 ISSUE 1
51SIN(*)-N5-40W
51SIN(*)-G1 51SIN(*)-N5-40W Cat. No. 92-L(*)
*Specify color of lens by adding one of the following letters to the catalog number: A ­amber, B - blue, C - clear, G - green, M - magenta, or R - Red.
Lamp
Cat. No. 50LMP-40W or 25T8DC
Horn
Cat. No. 123A-N5