Edwards Signaling Series 49 AdaptaBeacon, Series 50 AdaptaBeacon, Series 50SIN AdaptaBeacon, Series 51 AdaptaBeacon, Series 52 AdaptaBeacon Installation Guide

Installation Instructions for Catalog Series 49, 50, 50SIN,
51 and 52 AdaptaBeacon
DescriptionDescription
Description
DescriptionDescription
Catalog Series 49, 50, 50SIN, 51 and 52 AdaptaBeacon sig­nals are UL and cUL listed, general purpose visual and visual/audible signaling appliances. The 49 and 50 series are flashing lights. The 50SIN is a steady-on light. The 51 series are combination flashing lights with horn. The 51 series come in single and double horn versions; the double horn version is denoted by a 2H in its catalog number. The 52 series are rotating lights.
The 49, 50, 50SIN, 51 and 52 series signals are suitable for indoor or outdoor (weatherproof) installation and uti­lize a standard base that allows direct surface mounting, mounting on a 4" (102 mm) octagon box, or mounting on 1/2" (13 mm) NPT conduit. For outdoor installation, the signals must be mounted on conduit.
For product specification details see Table 2. Refer to Table 3 for available replacement lamps, flashers, domes and lenses.
PLC Compatibility
The electrical input load requirements for PLC compat­ible signaling devices are listed in Table 1. Signaling devices may be directly connected to output cards that meet these input load requirements.
®
Signals
InstallationInstallation
Installation
InstallationInstallation
WARNINGS
To prevent electrical shock, ensure that power is disconnected before installing the signal.
To prevent electrical shock, use care when disassembling the signal to pre vent tearing of the permanently affixed gaskets provided for weatherproofing.
Install in accordance with the latest edition of the Na­tional Electrical Code and local regulations.
1. For the 49, 50, 50SIN, 51 and 52 series signals, remove the base from the signal using one of the following applicable procedures.
49 Series: See Figure 1. Remove the screw in the clamp ring, remove the ring, and lift off the dome. Loosen the three screws in the base of the lens and turn the lens clockwise to remove. Then remove the two screws that are partially set into the raised area of the lamp assembly mounting plate, lift the assembly off of the base, and pull the wire leads out of the conduit entrance hole in the base. Proceed to step 2 for installation of the base.
Table 1. PLC Compatibility
Operating Maximum off state Continuous on Surge (inrush/duration)
Cat. No. voltage* leakage current (mA) current (mA) (A/ms**)
50( )-N5-40WH 120V AC 25 300 2/8 50SIN( )-N5-40WH 120V AC 25 290 0.47/8 51( )-N5-40W 120V AC 25 350 2/8 *All AC volts at 60 Hz
**Amps/milliseconds
P-047550-0541 ISSUE 13 © 2003
Figure 1. Catalog Series 49 Flashing Lights
Figure 2. Catalog Series 50 and 50SIN
Flashing Lights
50 and 50SIN Series: See Figure 2. Remove the screw in the clamp ring, remove the ring, lift the lens/ lamp assembly off of the base, and pull the wire leads out of the conduit entrance hole in the base. Proceed to step 2 for installation of the base.
51 Series: See Figure 3. Remove the screw in the clamp ring, remove the ring, lift the lens/lamp assembly off of the base, and pull the wire leads out of the conduit entrance hole in the base. Proceed to step 2 for installation of the base.
52 Series: See Figure 4. Remove the screw in the clamp ring, remove the ring, and lift off the dome. Then remove the two screws in the rotating lamp assembly mounting plate, lift the assembly off of the base, and pull the wire leads out of the conduit entrance hole in the base. Proceed to step 2 for installation of the base.
2. For indoor installation, the signal may be direct surface mounted, mounted on a 4" (102 mm) octagon box, or mounted on 1/2" (13 mm) NPT conduit. For outdoor (weatherproof) installation, the signal must be conduit mounted. Install the signal base using one of the following applicable mounting procedures.
Direct Surface Mounting (indoor installation only)
NOTE: For proper operation of the 52 series rotating
lights, the signals must be installed with the dome facing either directly up or directly down.
Remove the two knockouts for mounting screws from the bottom of the signal base.
Route the field wiring from the required power source through the conduit entrance hole in the base. Power source requirements are in Tables 2 and 3.
Route the field wiring from the required power source through the conduit entrance hole in the base. Power source requirements are in Tables 2 and 3.
Fasten the base to the octagon box (not supplied) by installing the screws supplied with the box through the knockout holes in the base. Proceed to step 3 for wiring connections.
Mounting on 1/2" (13 mm) NPT Conduit (indoor or outdoor installation)
NOTE: For proper operation of the 52 series rotating
lights when mounting indoors, the signals must be installed with the dome facing either directly up or directly down.
WARNING
To prevent leakage and potential electrical shoc k when mounting outdoor s, the signals must be installed with the dome facing directl y up.
Route the field wiring from the required power source through the conduit entrance hole in the base. Power source requirements are in Table 2 located on the last page of these instructions.
Install the base on the conduit (not supplied). Proceed to step 3 for wiring connections.
3. Using wire nuts (not supplied), connect the field wiring to the signal's wire leads. Polarity is not important. A green ground wire is provided on all units. Connect the green ground wire lead in accordance with local codes. Place the connected wires inside of the base and reassemble the signal on the base.
Fasten the base to the surface by installing two #10 wood screws (not supplied) or other suitable hardware through the knockout holes in the base. Proceed to step 3 for wiring connections.
Mounting on a 4" (102 mm) Octagon Box (indoor installation only)
NOTE: For proper operation of the 52 series rotating
lights, the signals must be installed with the dome facing either directly up or directly down.
Remove the two knockouts for mounting screws from the bottom of the signal base.
P-047550-0541 ISSUE 13
WARNINGS
To avoid risk of injur y, do not remove or insert lamp when unit is ener gized.
To avoid risk of injur y, install lens before energizing the unit.
4. Turn on power and verify that the signal operates properly.
Figure 3. Catalog Series 51 Flashing Lights
TT
rr
oubleshootingoubleshooting
T
r
oubleshooting
TT
rr
oubleshootingoubleshooting
Should the lamp fail to operate, check that power is on. If power is on, either the lamp or the solid state flasher module (the module is not used in the 52 series signals) requires replacement. Replace the lamp first as directed in the "Lamp Replacement" section that follows. Should the replacement lamp also fail to operate, the flasher module must be replaced. Refer to Table 3 for the re­quired replacement flasher. Instructions for replacing the flasher are provided with the flasher.
NOTE: Should both the lamp and horn fail to operate
in a 51 Series signal, replace the flasher module.
MaintenanceMaintenance
Maintenance
MaintenanceMaintenance
with Horn
WARNINGS
To avoid risk of injury, do not remove or insert lamp when unit is ener gized.
To avoid risk of injur y, install lens before energizing the unit.
Figure 4. Catalog Series 52 Rotating Lights
WARNING
To prevent electrical shock, use care when disassembling the signal to pre vent tearing of the permanently affixed gaskets provided for weatherproofing.
49 Series: See Figure 1. Remove the screw in the clamp ring, remove the ring, and lift off the dome. Loosen the three screws in the base of the lens and turn the lens clockwise to remove. Replace the lamp.
50 and 50SIN Series: See Figure 2. Remove the three screws from the top of the trim ring and lift off the lens and ring. Replace the lamp.
51 Series: See Figure 3. Remove the three screws from the top of the skirt and lift off the lens and skirt. Re­place the lamp.
CAUTION
To prevent damage to the lens and/or dome, use abrasive materials or cleaners.
do not
Lamp Replacement
Refer to Table 3 for the required lamp. After discon­necting power, replace the lamp using one of the fol­lowing applicable procedures:
WARNING
To prevent electrical shock, ensure that power is disconnected prior to disassemb ly.
52 Series: See Figure 4. Remove the screw in the clamp ring, remove the ring, and lift off the dome. Replace the lamp.
Cleaning
The signal's lens and/or dome should be peridodically cleaned to maintain optimum light visibility. These items may be cleaned with a soft cloth or sponge using mild detergent. Ensure that the lens or dome is completely dry before replacing.
P-047550-0541 ISSUE 13
Table 2. Specifications
Catalog Number Rated Voltage Current
49(*)-R5 240V 50/60 Hz 0.10 amp 50(*)-R5 240V 50/60 Hz 0.10 amp 52(*)-R5 240V 50/60 Hz 0.10 amp 49(*)-N5-40WH 120V 50/60 Hz 0.30 amp 50(*)-N5-40WH 120V 50/60 Hz 0.30 amp 50SIN(*)-N5-40WH 120V 50/60 Hz 0.29 amp 51(*)-N5-40W 120V 50/60 Hz 0.29 amp 52(*)-N5-40WH 120V 50/60 Hz 0.35 amp 50(*)-G5-20WH 24V 50/60 Hz 0.80 amp 51(*)-G5-20W 24V 50/60 Hz 1.1 amp 52(*)-G5-20WH 24V 50/60 Hz 0.80 amp
Table 3. Replacement Parts
Replacement lamps, flashers, lenses and domes for the 49, 50, 50SIN, 51 and 52 series signals may be obtained from your Edwards distr ibutor. The catalog n umbers or part numbers for these components are as f ollows.
Replacement Component
Signal Catalog Number Replacement Component Part Number
49(*)-N5-40WH, 50(*)-N5-40WH, Lamp - 40 Watt Halogen 50LMP-40WH or 50LMP-40W** 50SIN(*)-N5-40WH, 52(*)-N5-40WH 25T8DC**
51(*)-N5-40W Lamp - 40 Watt 50LMP-40W or 25T8DC
49(*)-R5, 50(*)-R5, 52 (*)-R5 Lamp - 25 Watt P-041917-0039 or
industry trade no. 25T8/240V/DC/CL
50(*)-G5-20WH, 52(*)-G5-20WH Lamp - 20 Watt Halogen 50LMP-20WH or industry trade no. 1638**
51(*)-G5-20W Lamp - 20 Watt 50LMP-20W or industry trade no. 1638
49(*)-N5-40WH, 50(*)-N5-40WH, Solid state flasher module P-041917-0026 51(*)-N5-40W
50(*)-G5-20WH, 51(*)-G5-20W Solid state flasher module P-041917-0029
49(*)-R5, 50(*)-R5 Solid state flasher module P-041917-0038
51(*)-N5-40W Horn 123A-N5
51(*)-G5-20W Horn 123A-G5
49(*)-N5-40WH, 49(*)-R5 Dome (Clear) 52-LC
52(*)-G5-20WH, 52(*)-N5-40WH, Dome 52-L(*) 52(*)-R5 (Amber, Blue, Clear, Green, Magenta or Red)
49(*)-N5-40WH, 49(*)-R5, Lens 92-L(*) 50(*)-N5-40WH, 50(*)-R5, (Amber, Blue, Clear, Green, Magenta or Red) 50(*)-G5-20WH, 50SIN(*)-N5-40WH, 51(*)-G5-20W, 51(*)-N5-40W
*Specify color of item by adding one of the following letters to the catalog number: A - amber, B - blue, C - clear, G - green, M - magenta, or R - red (e .g., a red dome f or the 52 ser ies signal is 52-LR). **The listed non-halogen b ulb may be used instead of the halogen b ulb.
P-047550-0541 ISSUE 13
Loading...