Edwards Signaling Series 49 AdaptaBeacon, Series 50 AdaptaBeacon, Series 50SIN AdaptaBeacon, Series 51 AdaptaBeacon, Series 52 AdaptaBeacon Installation Guide

Installation Instructions for Catalog Series 49, 50, 50SIN,
51 and 52 AdaptaBeacon
DescriptionDescription
Description
DescriptionDescription
Catalog Series 49, 50, 50SIN, 51 and 52 AdaptaBeacon sig­nals are UL and cUL listed, general purpose visual and visual/audible signaling appliances. The 49 and 50 series are flashing lights. The 50SIN is a steady-on light. The 51 series are combination flashing lights with horn. The 51 series come in single and double horn versions; the double horn version is denoted by a 2H in its catalog number. The 52 series are rotating lights.
The 49, 50, 50SIN, 51 and 52 series signals are suitable for indoor or outdoor (weatherproof) installation and uti­lize a standard base that allows direct surface mounting, mounting on a 4" (102 mm) octagon box, or mounting on 1/2" (13 mm) NPT conduit. For outdoor installation, the signals must be mounted on conduit.
For product specification details see Table 2. Refer to Table 3 for available replacement lamps, flashers, domes and lenses.
PLC Compatibility
The electrical input load requirements for PLC compat­ible signaling devices are listed in Table 1. Signaling devices may be directly connected to output cards that meet these input load requirements.
®
Signals
InstallationInstallation
Installation
InstallationInstallation
WARNINGS
To prevent electrical shock, ensure that power is disconnected before installing the signal.
To prevent electrical shock, use care when disassembling the signal to pre vent tearing of the permanently affixed gaskets provided for weatherproofing.
Install in accordance with the latest edition of the Na­tional Electrical Code and local regulations.
1. For the 49, 50, 50SIN, 51 and 52 series signals, remove the base from the signal using one of the following applicable procedures.
49 Series: See Figure 1. Remove the screw in the clamp ring, remove the ring, and lift off the dome. Loosen the three screws in the base of the lens and turn the lens clockwise to remove. Then remove the two screws that are partially set into the raised area of the lamp assembly mounting plate, lift the assembly off of the base, and pull the wire leads out of the conduit entrance hole in the base. Proceed to step 2 for installation of the base.
Table 1. PLC Compatibility
Operating Maximum off state Continuous on Surge (inrush/duration)
Cat. No. voltage* leakage current (mA) current (mA) (A/ms**)
50( )-N5-40WH 120V AC 25 300 2/8 50SIN( )-N5-40WH 120V AC 25 290 0.47/8 51( )-N5-40W 120V AC 25 350 2/8 *All AC volts at 60 Hz
**Amps/milliseconds
P-047550-0541 ISSUE 13 © 2003
Figure 1. Catalog Series 49 Flashing Lights
Figure 2. Catalog Series 50 and 50SIN
Flashing Lights
50 and 50SIN Series: See Figure 2. Remove the screw in the clamp ring, remove the ring, lift the lens/ lamp assembly off of the base, and pull the wire leads out of the conduit entrance hole in the base. Proceed to step 2 for installation of the base.
51 Series: See Figure 3. Remove the screw in the clamp ring, remove the ring, lift the lens/lamp assembly off of the base, and pull the wire leads out of the conduit entrance hole in the base. Proceed to step 2 for installation of the base.
52 Series: See Figure 4. Remove the screw in the clamp ring, remove the ring, and lift off the dome. Then remove the two screws in the rotating lamp assembly mounting plate, lift the assembly off of the base, and pull the wire leads out of the conduit entrance hole in the base. Proceed to step 2 for installation of the base.
2. For indoor installation, the signal may be direct surface mounted, mounted on a 4" (102 mm) octagon box, or mounted on 1/2" (13 mm) NPT conduit. For outdoor (weatherproof) installation, the signal must be conduit mounted. Install the signal base using one of the following applicable mounting procedures.
Direct Surface Mounting (indoor installation only)
NOTE: For proper operation of the 52 series rotating
lights, the signals must be installed with the dome facing either directly up or directly down.
Remove the two knockouts for mounting screws from the bottom of the signal base.
Route the field wiring from the required power source through the conduit entrance hole in the base. Power source requirements are in Tables 2 and 3.
Route the field wiring from the required power source through the conduit entrance hole in the base. Power source requirements are in Tables 2 and 3.
Fasten the base to the octagon box (not supplied) by installing the screws supplied with the box through the knockout holes in the base. Proceed to step 3 for wiring connections.
Mounting on 1/2" (13 mm) NPT Conduit (indoor or outdoor installation)
NOTE: For proper operation of the 52 series rotating
lights when mounting indoors, the signals must be installed with the dome facing either directly up or directly down.
WARNING
To prevent leakage and potential electrical shoc k when mounting outdoor s, the signals must be installed with the dome facing directl y up.
Route the field wiring from the required power source through the conduit entrance hole in the base. Power source requirements are in Table 2 located on the last page of these instructions.
Install the base on the conduit (not supplied). Proceed to step 3 for wiring connections.
3. Using wire nuts (not supplied), connect the field wiring to the signal's wire leads. Polarity is not important. A green ground wire is provided on all units. Connect the green ground wire lead in accordance with local codes. Place the connected wires inside of the base and reassemble the signal on the base.
Fasten the base to the surface by installing two #10 wood screws (not supplied) or other suitable hardware through the knockout holes in the base. Proceed to step 3 for wiring connections.
Mounting on a 4" (102 mm) Octagon Box (indoor installation only)
NOTE: For proper operation of the 52 series rotating
lights, the signals must be installed with the dome facing either directly up or directly down.
Remove the two knockouts for mounting screws from the bottom of the signal base.
P-047550-0541 ISSUE 13
WARNINGS
To avoid risk of injur y, do not remove or insert lamp when unit is ener gized.
To avoid risk of injur y, install lens before energizing the unit.
4. Turn on power and verify that the signal operates properly.