Edwards Signaling B-KME-8130 User Manual

Installation Instructions for Catalog Series
Cheshire, CT 06410 203-699-3300 (Ph) 203-699-3365 (Cust. Serv. Fax) 203-699-3078 (Tech. Serv. Fax)
Description
The Edwards Catalog Series B-KM-8130 and B-KME-8130 (Pro­jector Units) are intermittent duty explosion proof horns that are ideal for use as call signals in hazardous atmospheres where ex­plosion proof and dust tight features are required. The unit is UL and cUL listed for installation in Class I, Division 2, Groups A and B Temp. Code T4A (248F, 120C); Class I, Divisions 1 and 2, Groups C and D; Class II, Divisions 1 and 2, Groups E, F and G; and Class III, Divisions 1 and 2 hazardous locations.
B-KM-8130 and B-KME-8130 Explosion Proof Horns
1. Mount the horn assembly securely to a flat surface in the desired location with (2) screws through the 3/8" (9.5 mm) diameter holes in the housing. See Figure 1.
2. Install conduit in 1/2" (12.7 mm) NPT tapped hole in side of housing.
NOTE: Conduit runs must have a sealing fitting connected
within 18 inches of the enclosure.
3. Connect wires (2 for B-KM Series or 4 for B-KME Series) using wire nuts (supplied) in accordance with applicable local codes (Figure 2).
Electrical Specifications
Intermittent Duty Cycle ................... 5 minutes on/5 minutes off
AC Grill Model -- Alternating Current, 60 Hz*
Coil
Resistance
Cat. No. Voltage Current (A) VA (ohms) B-KM-8130-G5 24V AC 2 48 1 B-KM-8130-N5 120V AC 0.45 54 24 B-KM-8130-R5 240V AC 0.2 48 103.2 B-KME-8130-NR5 120V AC 0.45 54 24.4
240V AC 0.25 60 98
*The low capacity of bell ringing transformers make them unsuitable for use with low voltage signals. Signaling transformers are required.
Installation
W ARNING
T o reduce the risks of electrical shock and ignition of hazardous atmospheres, do not apply power until the unit installation has been completed and unit is tightly assembled and secured.
These products are intended to be installed in accordance with the applicable requirements in the latest editions of either the Na­tional Fire ProtectionAssociation publication NFPA 70, the Na­tional Electrical Code, or the Canadian Standards Association publication C22.1-02, the Canadian Electrical Code, Part I, and in accordance with the local authorities having jurisdiction.
4. For B-KM-8230 Series, connect green ground wire to external ground.
Maintenance
W ARNINGS
T o reduce the risk of equipment damage and ignition of hazardous atmospheres, keep the assembly tightly closed when circuits are energized.
Ensure that all power is off before performing main­tenance.
1. Check and inspect the unit at least once a year for damage or wear.
2. Inspect all electrical and mechanical components to see if there is any internal corrosion or wire discoloration.
CA UTION
When reassembling fixture, make certain that the threads and taper joint between housing and brass cover are clean.
Figure 1. Single Projector Unit (B-KM-8130 Series)
P-047550-1609 ISSUE 6 © 2003
Figure 2. Wiring Diagrams
P-047550-1609 ISSUE 6