Edwards SIGA-270, SIGC-270F, SIGC-270B, SIGA-270P, SIGC-270PB User Manual

...
LIFE SAFETY & INCIDENT MANAGEMENT
Manual Pull Stations
SIGA-270, SIGA-270P, SIGA-278
EDWARDS® Catalog u Intelligent Initiating
SIGA-270 SERIES
Overview
The SIGA-270 and SIGA-278 series Manual Pull Stations are part of EDWARDS’s Signature Series system. The SIGA-270 Fire Alarm Manual Pull Stations feature our very familiar teardrop shape. They are made from die-cast zinc and finished with red epoxy powder­coat paint complemented by aluminum colored stripes and mark­ings. With positive pull-lever operation, one pull on the station handle breaks the glass rod and turns in a positive alarm, ensuring protection plus fool-proof operation. Presignal models (SIGA-270P) are equipped with a general alarm (GA) keyswitch for applications where two stage operation is required. The up-front highly visible glass rod discourages tampering, but is not required for proper operation.
EDWARDS’s double action single stage SIGA-278 station is a contemporary style manual station made from durable red colored lexan. To initiate an alarm, first lift the upper door marked “LIFT THEN PULL HANDLE”, then pull the alarm handle.
Standard Features
Note: Some features described here may not be supported by all control sys­tems. Check your control panel’s Installation and Operation Guide for details.
• Traditional familiar appearance
SIGA-270 models feature our familiar teardrop design with simple positive pull action and sturdy die-cast metal body.
• One stage (GA), two stage (pre-signal), and double action models
SIGA-270 models are available for one or two stage alarm systems. The single stage double action SIGA-278 features a rugged Lexan housing with keyed reset mechanism.
SIGA-278
• Break glass operation
An up-front visible glass rod on the SIGA-270 discourages tampering.
• Intelligent device with integral microprocessor
All decisions are made at the station allowing lower com­munication speed while substantially improving control panel response time. Less sensitive to line noise and loop wiring properties; twisted or shielded wire is not required.
• ADA Compliant
Meets ADA requirements for manual pull stations.
• Electronic Addressing with Non-volatile memory
Permanently stores programmable address, serial number, type of device, and job number. Automatically updates historic information including hours of operation, last maintenance date, number of alarms and troubles, and time and date of last alarm.
• Automatic device mapping
Each station transmits wiring information to the loop control­ler regarding its location with respect to other devices on the circuit.
• Diagnostic LEDs
Status LEDs; flashing GREEN shows normal polling; flashing RED shows alarm state.
• Designed for high ambient temperature operation
Install in ambient temperatures up to 120 °F (49 °C).
Patented
MEA
7150-1657:
0129
S2318
Page 1 of 4 DATA SHEET E85001-0279
Not to be used for installation purposes. Issue 1
Application
The operating characteristics of the fire alarm stations are deter­mined by their sub-type code or “Personality Code”. NORMALLY­OPEN ALARM - LATCHING (Pesonality Code 1) is assigned by the factory; no user configuration is required. The device is configured for Class B IDC operation. An ALARM signal is sent to the loop controller when the station’s pull lever is operated. The alarm con­dition is latched at the station.
Compatibility
Signature Series manual stations are compatible only with ED­WARDS’s Signature Loop Controller.
Warnings & Cautions
This device will not operate without electrical power. As fires fre­quently cause power interruption, we suggest you discuss further safeguards with your local fire protection specialist.
Testing & Maintenance
To test (or reset) the station simply open the station and operate the exposed switch. The SIGA-270 series are opened with a tool; the SIGA-278 requires the key which is supplied with that station.
The station’s automatic self-diagnosis identifies when it is defec­tive and causes a trouble message. The user-friendly maintenance program shows the current state of each Signature series device and other pertinent messages. Single devices may be deactivated temporarily, from the control panel. Availability of maintenance features is dependent on the fire alarm system used.
Scheduled maintenance (Regular or Selected) for proper system operation should be planned to meet the requirements of the Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and ULC CAN/ULC 536 standards.
Typical Wiring
The fire alarm station’s terminal block accepts #18 AWG (0.75mm2) to #12 AWG (2.5mm2) wire sizes. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications.
Wiring Notes
1 Refer to Signature Loop Controller manual for maximum wire distance.
2. All wiring is power limited and supervised.
Figure 4. Single Stage Systems
Figure 5. Two Stage Systems
Page 2 of 4 DATA SHEET E85001-0279
Not to be used for installation purposes. Issue 1
Installation
L
IF
T
NORMAL
Cover Release
Screw
Compatible
Electrical Box
with ½-inch
raised covers
Glass Rod
Release Lever
Toggle Switch
Back Plate
Do not use boxes with
rounded
openings.
Single-stage Signature Series fire alarm manual pull stations mount to North American 2½ inch (64 mm) deep 1-gang boxes.
Two stage presignal (270P) models require 1½ inch (38 mm) deep 4-inch square boxes with 1-gang, ½-inch raised covers. Openings
must be angular. Rounded openings are not acceptable. Recommended box: Steel City Model 52-C-13; in Canada, use Iberville Model CI­52-C-49-1/2.
All models include terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size. EDWARDS recommends that these fire
alarm stations be installed according to latest recognized edition of national and local fire alarm codes.
Electronic Addressing: The loop controller electronically addresses each manual station, saving valuable time during system com-
missioning. Setting complicated switches or dials is not required. Each station has its own unique serial number stored in its on-board memory. The loop controller identifies each device on the loop and assigns a “soft” address to each serial number. If desired, the stations can be addressed using the SIGA-PRO Signature Program/Service Tool.
Figure 1. SIGA-278 installation
Figure 3. SIGA-270P, SIGC-270PB installation
Figure 2. SIGA-270, SIGC-270F, SIGC-270B installation
Page 3 of 4 DATA SHEET E85001-0279
Not to be used for installation purposes. Issue 1
LIFE SAFETY & INCIDENT MANAGEMENT
Contact us...
Email: edwards.fire@fs.utc.com Web: edwards-fire.com
1016 Corporate Park Drive Mebane, NC 27302
EDWARDS is a registered mark in the United States and other countries.
© 2018 United Technologies Corporation. All rights reserved.
Specifications
Catalog Number
Description
Addressing Requirements
Operating Current
Construction & Finish
270F, SIGC-270B
Single Action
- One Stage
Uses 1 Module
Address
Standby = 250µA
Activated = 400µA
Diecast Zinc - Red Epoxy
with aluminum markings
Type Code
SIGA-270, SIGC-
Operating Voltage
Storage and Operating Environment
Storage Temperature: -4ºF to 140ºF (-20ºC to 60ºC) Humidity: 0 to 93%
LED Operation
Compatibility
Agency Listings
Note: SIGC-270F, SIGC-270B and SIGC-270PB are ULC listed only. Suffix “F” indicates French markings. Suffix “B” indicates English/French biling ual markings.
15.2 to 19.95 Vdc (19 Vdc nominal)
Operating Temperature: 32ºF to 120ºF (0ºC to 49ºC)
On-board Green LED - Flashes when polled
On-board Red LED - Flashes w hen in alarm
Use With: Signature Loop Controller
UL, ULC (note 1), MEA, CSFM, FM
SIGA-270P,
SIGC-270PB SIGA-278
Single Action -Two
Stage (Presignal)
Uses 2 Module
Addresses
Standby = 396µA
Activated = 680µA
Double Action
- One Stage
Uses 1 Module
Address
Standby = 250µA
Activated = 400µA
Lexan - Red with
white markings
Factory Set
RH
Ordering Information
Catalog Number Description
Ship Wt. lbs (kg)
SIGA-270 One Stage Fire Alarm Station, English Markings - UL/ULC Listed SIGC-270F One Stage Fire Alarm Station, French Markings - ULC Listed SIGC-270B One Stage Fire Alarm Station, French/English Markings - ULC Listed
SIGA-270P
SIGC­270PB
SIGA-278
Two Stage (Presignal) Fire Alarm Station, English Markings - UL/ULC Listed
Two Stage (Presignal) Fire Alarm Station, French/English Markings
- ULC Listed Double Action (One Stage) Fire Alarm Station, English Markings
- UL/ULC Listed
1 (0.5)
Accessories
32997 GA Key w/Tag - for pre-signal station (CANADA ONLY) 276-K2 GA Key - for pre-signal station (USA ONLY) 276-K1 Station Reset Key, Supplied with all Key Reset Stations 27165 12 Glass Rods - for SIGA-270 series (CANADA ONLY)
0.1 (.05)
270-GLR 20 Glass Rods - for SIGA-270 series (USA ONLY) 276-GLR 20 Glass Rods - for SIGA-278 series 276B-RSB Surface Mount Box, Red - for SIGA pull stations 1 (0.6)
Page 4 of 4 DATA SHEET E85001-0279