Edwards SD-4WJ Installation Manual

Product description
Related documents
In addition to this document, information about sensor installation and duct smoke detector testing and maintenance can be found in the following:
SuperDuct Four-Wire Smoke Sensor (RJ-45 version) Installation
SuperDuct Four-Wire Duct Smoke Detector Technical Bulletin
Specifications
Dimensions
Wire size
LED indicators: Alarm (red), Trouble (yellow), Power (green)
The SuperDuct four-wire controller coupled with a compatible sensor make up a SuperDuct four-wire duct smoke detector. The sensor sends an alarm signal to the controller when smoke is detected in the HVAC system. Upon receipt of the alarm signal, the controller takes the appropriate actions to provide early warning of the impending fire and prevent smoke from circulating throughout the building. The controller can be configured for a range of operating voltages and supports one or two compatible sensors.
WARNING: SuperDuct duct smoke detectors are not intended as a substitute for open area protection.
The controller comprises a plastic housing, a printed circuit board, and a clear plastic cover. The clear plastic cover is secured to the housing with a single captive screw for easy access to the wiring terminals. Knockouts are provided to route wires into the controller housing.
The controller contains no user serviceable parts.
This document provides installation instructions for the following SuperDuct four-wire controllers:
Model Description
TSD-CJ, ESD-CJ, SD-CJ
TSD-CJG
TSD-4WJ, ESD-4WJ, SD-4WJ
This product will not operate without at least one compatible sensor. The table below lists the compatible four-wire smoke sensors that you can use with the controllers listed above.
Controller Compatible sensor
TSD-CJ, TSD-CJG, TSD-4WJ TSD-SJ, TSD-SJG, TSD-SJCO2
ESD-CJ, ESD-4WJ ESD-SJ
SD-CJ, SD-4WJ SD-SJ
Note: The TSD-CO2 module has not been performance evaluated to UL 2075 or approved by ULC.
Four-wire controller with RJ-45 modular connectors
Four-wire controller with RJ-45 modular connectors and cover gasket
Combination four-wire controller and sensor with RJ-45 modular connectors
Alarm initiation relay
Auxiliary relay
Supervision (trouble) relay
Auxiliary output: 18 Vdc, nom., 30 mA, max. TSD-CO2 module output: 0 to 10 Vdc (0 to 2,000 ppm) Operating environment
Operating voltages: 20 to 29 Vdc (-15 to 10%), 24V (-15 to 10%) at
Operating currents: See table below
Note: The TSD-CO2 module has not been performance evaluated to UL 2075 or approved by ULC.
Installation guidelines
Install in accordance with all applicable national and local codes as determined by the local authority having jurisdiction.
Do not install a controller more than 15 feet away from a sensor.
SuperDuct
Four-Wire Controller (RJ-45 version)
Sheet (P/N 3100686)
(P/N 3100685)
Controller: 6.75 x 5.45 x 1.90 inches Controller with detector: 14.51 x 5.45 x 1.90 inches
High voltage terminals: 12 to 22 AWG All others: 14 to 22 AWG
Quantity: 1 Style: Normally open Ratings: 2.0 A at 30 Vdc (resistive)
Quantity: 2 Style: Form C Ratings: 10 A at 30 Vdc, 10 A at 250 Vac (contacts must switch a minimum of 100 mA at 5 Vdc)
Quantity: 1 Style: Form C Ratings: 2.0 A at 30 Vdc (resistive)
Temperature: -20 to 70 °C (-4 to 158 °F) Temperature with TSD-CO2 module installed: 0 to 55 °C (32 to 131 °F) Humidity: 10 to 93%, RH noncondensing at 68 to 72 °C (154.4 to
161.6°F)
50/60 Hz, 120V (-15 to 10%) at 50/60 Hz, 220/240V (-15 to 10%) at 50/60 Hz
Supply voltage Standby current Alarm current
24 Vdc 77.9 mA 124.3 mA
24 V at 50 Hz 215.3 mA 307.0 mA
24 V at 60 Hz 220.0 mA 316.5 mA
120 V at 50 Hz 91.0 mA 89.0 mA
120 V at 60 Hz 79.0 mA 74.0 mA
220/240 V at 50 Hz 44.9 mA 44.0 mA
220/240 V at 60 Hz 34.5 mA 32.0 mA
Installation Sheet 18AUG05 P/N: 3100687 REV: 2.0 SuperDuct Four-Wire Controller (RJ-45 version) 1 / 4
Run all field wiring through the knockouts located on the bottom of the controller housing. Maintain a 1/4-inch separation between power­limited and nonpower-limited wiring at all times.
Installation instructions
Please read these instructions thoroughly before installing. In addition to this document, important information can be found in Technical Bulletin P/N 3100685.
Step 1: Mount the controller
Mount the controller on a flat section of HVAC duct or sheet metal as shown in Figure 1 using the sheet metal screws provided in the hardware kit. The controller does not have to be mounted next to the sensor.
HVAC duct
Conduit coupling
(supplied by installer)
Coupling nut
(supplied by installer)
Conduit support
plate
Controller
#10 sheet metal screw
Figure 1: Controller mounting diagram
If you are installing a controller combined with a sensor, mount both on a flat section of HVAC duct as shown in Figure 2.
Exhaust
tube
Airflow
Sampling
tube
(3X)
Figure 3: Conduit support plate installation
Jumper configuration
Set the controller configuration jumpers as described below.
Note: Failure to remove JP1 prevents the controller from indicating a trouble condition with the sensor connected to J2. It does not prevent the controller from responding to an alarm signal.
JP1
JP2 & JP3
Figure 4: Controller jumper locations
JP1 jumper settings
Position Description
IN
OUT Controller connected to two sensors
Controller connected to one sensor (factory setting)
JP2, JP3 jumper settings
HVAC duct
#10 sheet metal screw
Figure 2: Mounting a controller combined with a sensor
Step 2: Attach the conduit support plate
Open the controller and remove the terminal block cover. Attach the conduit support plate as shown in Figure 3.
P/N: 3100687 REV: 2.0 18AUG05 Installation Sheet 2 / 4 SuperDuct Four-Wire Controller (RJ-45 version)
Sensor
(2X)
Controller
Position Description
Controller connected to 24 Vdc, 24 Vac, or 120 Vac (factory setting)
Controller connected to 220/240 Vac
JP2 JP3
JP2 JP3
Controller to sensor wiring
Connect the controller to the sensor as shown in Figure 5. Make sure the cable grommets are seated securely into their respective openings.
RJ-45 cable assembly
(ordered separately)
J1
J1
J2
First sensor
Controller
J1
RJ-45 cable assembly
(ordered separately)
Optional second sensor
Figure 5: Controller to sensor wiring diagram
RJ-45 cable assemblies are available in the lengths listed below.
Model Description
SD-RJ5 RJ-45 wiring harness kit (5 ft)
SD-RJ10 RJ-45 wiring harness kit (10 ft)
SD-RJ15 RJ-45 wiring harness kit (15 ft)
Nonpower-limited
Power-limited
Figure 6: Power-limited and nonpower-limited wiring areas
Figure 7 shows the terminal block cover that is installed on the controller. The markings identify the function and number of the screw terminals found underneath.
REM
ALARM
LED OUT
(+)
ALARM
CONTACT
SUPV.
CONTACT
N.C. N.O.
COM
MULTI­SHUT­DOWN
RESET AUX
230V *
120V 120V
NL
120VAC
* FOR 230VAC,
REF. INSTALL SHEET
31006873100730
AUX
18Vdc
OUTPUT
(-) (+)
201019918817716615514413312211
24VAC
or 20-29Vdc (-) (+)
CONTACT
COM
N.O. N.C.
N.C. N.O. COM COMN.O.
AUX
CONTACT
CAUTION: HIGH VOLTAGE
Figure 7: Terminal block cover
NOT
USED
1
(-)
Notes
If strain relief is required, secure the cable using the cable clamps provided with the cable kit
If you are connecting the controller to two sensors, remove JP1
Field wiring
Bring all field wiring into the controller through the knockouts on the bottom of the housing as shown in Figure 6. Keep all power-limited wiring in the shaded area and all nonpower-limited wiring in the area that is not shaded.
Remove the terminal block cover and connect the field wiring as shown in Figure 8. Replace the terminal block cover when finished.
Note: Maintain a 1/4-inch separation between power-limited and nonpower-limited wiring at all times.
Testing
After completing the installation, test the controller to ensure that it is operating correctly before leaving the site. For details, refer to Technical Bulletin P/N 3100685.
Installation Sheet 18AUG05 P/N: 3100687 REV: 2.0 SuperDuct Four-Wire Controller (RJ-45 version) 3 / 4
EOLR [4]
(supplied by
Auxiliary
equipment
Auxiliary
equipment
installer)
5956A
1
2
Alarm
18 Vdc ( )
Auxiliary
equipment
+
6
17
Controller B
J1
RJ-45 cable [9]
J1
1st sensor
17
Controller A
2nd sensor [1]
Auxiliary
equipment
6
J1
7
16
JP1
J2
RJ-45 cable [9]
J1
7
16
JP1
J2
8
18
230V
Alarm initiation
contacts [2]
5
CAUTION
Do not use looped wires under
terminals 5 and 4. Break wire runs
to provide supervision of connections.
Auxiliary
equipment
8
18
5
4
10
Alarm initiation
contacts [2]
4
10
L
9
+
24V AC/DC24V AC/DC
[11]
Supervision relay
(supplied by installer)
230V
9
L
120V/220V/240V [5]
14
120 V
JP2 JP3
3
N
14
120V
JP2 JP3
3
N
13
19
Supervision relay
contacts [3]
Trouble
Power
Alarm
5
SD-TRK4 or SD-TRM4 [6]
Supervision relay
contacts [3]
4
+
18 Vdc ( )
13
19
Wire must be
2
15
Reset/Test
1
15
added by installer
20
1
12
3
2
18 Vdc ( )
2
20
Multiple fan shutdown [8]
1
12
2
1
TB3
output [10]
TSD-CO2 module
Auxiliary
equipment
+
2
1
TB3
output [10]
TSD-CO2 module
CAUTION
RJ-45 cable [9]
J1
1st sensor
RJ-45 cable [9]
J1
2nd sensor [1]
+
Do not use looped wires under
terminals 5 and 4. Break wire runs
to provide supervision of connections.
on fire alarm
control panel [7]
Initiating device circuit
+
120V/220V/240V [5]
Notes
[1] Remove JP1 when the controller is connected to two
sensors
[2] Alarm initiation contacts shown in normal condition. Contacts
close on alarm.
[3] Supervision relay contacts shown in normal condition.
Contacts change over on sensor or controller trouble.
[4] Install end-of-line resistor on last controller only. EOLR value
determined by fire alarm control panel.
[5] Move JP3 to the 230V position only when using 220V or
240V to operate the controller
[6] No more than two remote test/reset stations can be
connected to the same controller. Wiring is nonsupervised.
Maximum wire resistance is 10 ohms per wire.
[7] Control panel provides supervision and determines wire
requirements
[8] Wiring is nonsupervised. Wire resistance from first controller
to last controller can not exceed 5 ohms.15 controllers, max.
[9] Wiring is supervised by the controller. Maximum wire
distance is 15 ft.
[10] TSD-C02 module has not been performance evaluated to
UL 2075 or approved by ULC
[11] Only required when using a remote test/reset station and
the controller is wired to a fire alarm control panel. Otherwise,
use the supervision relay contacts as shown on Controller B.
Figure 8: Controller wiring diagram
P/N: 3100687 REV: 2.0 18AUG05 Installation Sheet 4 / 4 SuperDuct Four-Wire Controller (RJ-45 version)
Loading...