Edwards and the Edwards logo are trademarks of Edwards Limited.
B722-40-880 Issue E
CAUTION
WARNING
WARNING
WARNING
1Introduction
1.1Scope and definitions
This manual provides installation, operation, maintenance and storage instructions for the Edwards DX Compound
Turbomolecular Pumps. You must use the DX pumps as specified in this manual. If you do not, the protection provided
by the DX pumps may be impaired.
Read this manual before you install and operate the DX pump. Important safety information is highlighted as
WARNING and CAUTION instructions; you must obey these instructions. The use of WARNINGS and CAUTIONS is defined
below.
Warnings are given where failure to observe the instruction could result in injury or death to
people.
Cautions are given where failure to observe the instruction could result in damage to the equipment, associated
equipment and process.
Introduction
The units used throughout this manual conform to the SI international system of units of measurement. When flow
rates are specified, the abbreviation ‘sccm’ is used to mean standard cubic centimetres per minute. This is a flow of
3
min-1 at an ambient temperature of 0 ºC and a pressure of 1013 mbar (1.013 x 105 Pa).
1 cm
In accordance with standard EN61010, the following warning label appears on the DX pump:
Warning - refer to accompanying documentation.
Warning - hot surfaces.
The units used throughout this manual conform to the SI international system of units of measurement; where
appropriate US equivalent units of measurement are also given.
1.2General description
Improper use of the equipment could cause damage to it or injury to people. The user is
responsible for the safe operation, installation and monitoring of the system.
The Podule contains electrolytic capacitors and, under certain fault conditions, may emit
dangerous fumes. Ensure that the Podule is operated in a well-ventilated area.
Do not attempt to separate the Podule from the pump since this will cause damage to the electrical connections.
The DX pumps consist of the compound turbomolecular pump with a permanently attached Podule containing drive
electronics.
The Podule controls the electrical supply to the pump. It has no manual controls and can only be operated through
the logic interface. To operate the DX pump you must connect it to your own control equipment and power supply
or alternatively use the Edwards TIC Turbo Instrument Controller or TIC Turbo Controller.
The Podule drives the brush-less d.c. motor in the pump. The pump has three Hall effect devices that operate as
rotor position sensors and ensure that the drive current is correctly commutated around the motor phase-windings.
The vacuum pump contains turbomolecular blades and a Holweck drag mechanism on a single shaft; the Holweck
mechanism allows operation at higher backing pressures than pure turbomolecular pumps.
DX pumps are supplied with an inlet-screen fitted into the bore of the inlet-flange. Both the EXT255iDX and the
EXT75iDX with an NW25 interstage port are supplied with an inlet-strainer that fits into the interstage-port. The inletscreen and inlet-strainer protect the pump against damage that would be caused by debris entering the pump. The
inlet-screen also protects the user against injury from the sharp blades in the pump.
Note:The EXT75iDX with an NW16 interstage port is not supplied with an inlet-strainer.
The DX pumps have a vent-port for venting the pump and vacuum system to atmospheric pressure. The pump is
supplied with a manual vent-valve fitted; this can be replaced with a TAV5 or TAV6 solenoid-operated vent-valve
(available as accessories – see Section 7).
The DX pumps have a purge-port: an inert purge gas can be introduced to protect the bearing and motor from
corrosion, or the bearing lubricant from oxidisation. An optional vent-port adapter and purge restrictor can be fitted
to the purge-port to control the flow rate of the purge gas and to filter the gas supply. (Refer to Section 7).
Air-coolers and a water-cooling block are available as optional accessories to cool the DX pumps. (Refer to Section 7).
1.3Drive electronics
The Podule contains the drive electronics that control the pump operation and accessories such as a TAV vent valve
or air cooler. There is a connector socket on the top of the Podule where the TAV vent valve or air cooler can be
plugged-in. (Refer to Section 2.9)
The Podule has two indicator LEDs that signal the status and operation of the pump, that can also be used for faultfinding if a problem should occur. (Refer to Section 2.10)
The drive electronics system has a number of built-in safety features to protect the DX pumps from damage in the
event of sustained high pressure or temperature:
z The electronics constantly monitor the temperature inside the Podule and the temperature of the motor
within the pump. If either part becomes too hot, the electronics reduce the power supplied to the pump
motor and the pump speed will drop. If the pump rotational speed falls below 50% full speed, the electronics
may trip into Fail condition, depending on how you have configured the system. (Refer to Section 1.4.3).
z If the DX pump's inlet pressure increases, the power supplied to the pump-motor increases to counteract the
gas frictional load. However, when the built-in maximum power limit is reached, the speed of the pump will
start to drop. If the pump rotational speed falls below 50% full speed, the electronics may trip into Fail
condition, depending on how you have configured the system. (Refer to Section 1.4.3).
z In the event of an electrical supply failure, the drive electronics uses the motor within the pump as a
generator. This means the DX pumps have their own regenerative supply and do not require a separate
battery for emergency power back-up. The regenerated energy is used to maintain the electrical supply to
the connector socket on the Podule until the pump speed falls to below 50% of full rotational speed: this will
ensure that the vent valve remains shut until below 50% of full rotational speed and will prevent the pump
from venting at full speed, provided that there is not too much loading on the 24 V supply to the pump.
Edwards and the Edwards logo are trademarks of Edwards Limited.
B722-40-880 Issue E
1.4Operational features
In addition to the basic start and stop commands, the DX pumps have several other features for improved
functionality. This allows you to tailor the pump operation to your particular application. Refer to Table 15 for
factory default settings of the parameters discussed in the following Sections.
1.4.1Power limit setting
You can select the maximum power that will be drawn by the pump (refer to Section 4.1.1). The more power you
supply, the quicker the pump will accelerate to reach full speed. Therefore if your application requires fast cycling,
you should set the power limit to the maximum value. If ramp time is not important in your application, you can use
a lower power limit, down to a minimum value, refer to Table 1.
Table 1 - Power l i m i t s
PumpMaximum value settingMinimum value setting
EXT75DX120 W50 W
EXT255DX200 W80 W
You must make sure that the power supply you use is capable of delivering sufficient power to the DX pump. By
choosing a lower power limit setting, you could use a smaller power supply. For more information, refer to
Section 2.7.
Introduction
1.4.2Standby speed
In Standby mode the pump rotational speed is lower than the full rotational speed.
If your application does not require the pump to be running at maximum speed at all times, you can use the Standby
speed feature rather than switching the pump off. This can save you time since you do not have to stop or vent the
pump and you do not have to wait as long for the pump to accelerate back to full speed.
The Standby speed is a user-selectable value (refer to Section 4.1.4).
1.4.3Timer
When the pump is started, an internal timer is automatically started within the drive electronics. If the pump fails
to reach 50% of full rotational speed within the timeout period, the Podule will signal a Fail and will decelerate the
pump to rest. This is a safety feature and prevents the Podule driving the pump at maximum power for a long time,
which could cause damage. The pump may fail to reach 50% speed if the gas load is too high (for example if there is
a leak in the system), if the backing pump fails, or if the pump is too hot.
The timeout period is a user-selectable feature (refer to Section 4.1.6), so if your application requires the pump to
ramp up slowly, you can extend the timeout period. The Timer is permanently enabled for ramp-up.
The Timer has an additional function: if the pump rotational speed drops below 50% full speed for any reason, you
may wish to allow the pump time to recover rather than trigger a Fail condition. The Timer starts as soon as the speed
drops to below 50% full speed. If, during the timeout period, the pump recovers to above 50% full speed then the
Timer will be reset. If the pump rotational speed fails to recover by the end of the timeout period, the Podule will
trigger a Fail condition and will decelerate the pump to rest. When you receive the pump, the Timer function will be
enabled, however you can disable it if you wish to. With the Timer disabled, the pump will Fail and decelerate to
rest as soon as pump rotational speed falls below 50%.
The Podule produces an analogue output that allows you to monitor four different system parameters:
z Measured pump rotational speed
z Measured motor power
z Measured motor temperature
z Measured controller temperature
The analogue output signal ranges from 0 to 10 V and is directly proportional to the system parameter (refer to
Section 2.8).
Connect the analogue output to a suitable meter or indicator to display the appropriate system parameter or connect
to your control equipment (for example, to operate other components in the pumping system at preset values).
You can only monitor one system parameter at a time using the analogue output. However, it is easy to configure the
Podule to monitor a different system parameter (refer to Section 4.1.7).
1.4.5Automatic vent options
An Edwards TAV vent valve can be connected directly to the DX pump’s Podule. The Podule is capable of controlling
a number of different venting options.
The drive electronics can control the rate of venting. Using this feature the pump can be vented from full rotational
speed in a controlled manner that will not damage the pump bearings. Once the pump rotational speed has dropped
to below 50% of maximum speed, it is safe to hard vent (open the vent valve fully.)
There are many venting options available to you, such as:
z Hard vent when rotational speed drops below 50%
z Controlled vent when above 50% speed and hard vent below 50% speed
z Hard vent immediately through a suitable restrictor
A full list of the venting options is given in Section 3.8.
In addition there is a feature that allows a delayed start of the DX pump. With this feature you can close the vent
valve before you start the DX pump. This allows the backing pump to reduce the pressure in the vacuum system
before starting the DX pump.
If you do not wish to use the Podule to control a TAV vent valve, you could use it to run a fan instead. You can
configure the Podule so that the fan is permanently enabled.
1.4.6Normal speed setting
The Normal Speed is a user-selectable parameter that can be set anywhere from 50% to 100% of full rotational speed.
When the pump reaches Normal Speed, a signal is available on the Normal pin of the logic interface connector. You
can use this signal to control your application since it shows that pump speed, and therefore vacuum performance,
has reached a minimum specific level. The default setting is 80% of full rotational speed. Refer to Section 4.1.5 for
instructions on altering the Normal Speed setting.
Edwards and the Edwards logo are trademarks of Edwards Limited.
B722-40-880 Issue E
1.4.7Electronic braking
The pump has a user selectable Electronic Braking option, which is disabled by default. With this option disabled the
pump will draw power from the supply when accelerating and running and will coast down when decelerating.
The Electronic Braking function may be enabled to reduce the pump deceleration time and to recover some energy
from the pump. This is achieved by returning power from the pump to the electrical supply. The rate at which
electrical energy is returned to the supply is regulated so as to limit the supply voltage to 24 V +10%. In order to
achieve the fastest electronic braking times there must be somewhere for the returned power to go such as:
z a supply capable of receiving the returned power
z other devices sharing the 24 V bus with the pump
z a load resistor of approximately 10 Ω switched across the 24 V supply when decelerating the pump
1.5Logic interface
The Podule can only be operated through the logic interface. The signals on the logic interface are of three types:
z Control inputs: these are switch-type signals that are used to control the pump
z Status outputs: these outputs identify the status of the system
Introduction
z Analogue output: this provides a 0 – 10 V output for a number of pump parameters.
The logic interface has been designed to include both serial and parallel modes of control and monitoring, operating
through one connector. The pump can be operated using either serial or parallel method or some combination of the
two.
The logic interface can be plugged directly into the Edwards TIC Turbo Controller or TIC Turbo Instrument Controller
and then use the functionality that they provide. Alternatively, the logic interface can be connected to a customers
own control system. The most useful arrangements are described in the sections below.
For more information about the logic interface, refer to Section 2.8.
1.5.1Parallel control and monitoring
The simple parallel interface is a quick and easy way to control the pump; this is the same interface used on existing
24V Edwards Turbo Pumps. The controls that are available to use are Start and Standby. You can monitor the system
status using the Normal, Fail and Analogue output signals.
Note:The Serial Enable switch MUST be open (no connection).
Refer to Section 3.6 for more detailed instructions of how to use the parallel interface.
A system operating in pure parallel mode has no facility to adjust the configuration settings stored in the Podule (for
example, power limit setting or controlled venting options). This would place a restriction in that all these features
would be at their factory default settings. However, the Podule could be configured separately before fitting the DX
pump to the system. This is covered in more detail in Section 1.5.5.
The serial communications link provides complete control and monitoring using just three signal lines. The Serial data
RX and TX use the same connector pins as the parallel signals Standby and Fail respectively.
The Serial Enable signal MUST be linked to 0 V for the system to accept commands in Serial control mode. This is a
safety feature and acts as an interlock. In addition, the parallel Start signal must be left unconnected for Serial
commands to be accepted in full Serial control mode.
The Podule will still provide the Normal and Analogue signals on the logic interface connector even when operating
in full Serial control mode. The status of the Normal signal can also be obtained by interrogating the system status
via the Serial interface.
For more information about the Serial interface, refer to Section 3.7.
1.5.3Serial control with parallel monitoring
Since Normal and Analogue signals remain available even using Serial control mode, it is possible to control the pump
via the Serial interface whilst monitoring these signals using a parallel link.
Again, the Serial data RX and TX use the same connector pins as the parallel signals Standby and Fail respectively so
these parallel control and monitoring signals are not available. The Serial Enable signal MUST be linked to 0 V and
the Start switch must remain open (no connection).
1.5.4Parallel control with occasional serial monitoring or serial set-up
This method of control is best for users who normally wish to operate the pump in parallel mode but occasionally
want to adjust the configuration settings stored in the Podule or to monitor operational status of the pump.
Whilst operating in Parallel mode, the same controls and monitoring signals are available as described in
Section 1.5.1. It must be remembered that the Serial data RX shares the same connector pin as the Standby signal so
the pump cannot be commanded into Standby speed using this line.
The Serial Enable signal must be linked to 0 V for serial communications to take place. We suggest that you make a
special cable for serial communications that includes a link between Serial Enable and 0 V. This way, Serial Enable
is automatically activated when the cable is connected and then deactivated when the cable is removed.
1.5.5Podule configuration (serial set-up)
All the configuration settings stored within the Podule are retained even when power to the DX pump is removed.
This means that it is possible to use a separate system to configure the Podule before fitting the DX pump to your
application. This gives the benefit of tailoring the pump functionality to a customer application and allows the pump
to be operated using a simple parallel interface system.
To configure the DX pump, either use your own simple serial system or use the Edwards TIC Turbo Controller or Turbo
Instrument Controller. The TICs have a feature which allows storage of a DX pump’s configuration. The configuration
can then be downloaded to another DX pump. This is useful when configuring a number of DX pumps with the same
settings before they are fitted to a system.
The TIC is supplied with a Windows
The program has a simple user interface which means that it is not necessary to use the ASCII message protocol
described in Section 3.7. The TIC PC Program has a facility to save multiple DX pump configurations which can then
be downloaded into other DX pumps.
TM
based PC program wh ich allo ws the DX pump to be c onfigur ed from a si ngle PC.
Edwards and the Edwards logo are trademarks of Edwards Limited.
2Technical data
WARNING
WARNING
WARNING
WARNING
2.1General
Table 2 - G e n e ral d a t a
General itemsReference data
PerformanceRefer to Ta bl e 3
DimensionsRefer to Figure 1 and 2
Maximum inlet-flange temperature
ISO63 / ISO100 / NW4070 °C with cooling water
DN63CF (EXT75DX) / DN100CF (EXT255DX)100 °C bakeout, with cooling water
Maximum permitted external magnetic field
EXT255DX3.5 mT horizontal field, 7 mT vertical field
EXT75DX5 mT
Pollution degreeCAN/CSA, UL, EN61010 part 1
Equipment typeFixed equipment, for indoor use only
Enclosure protection (installed)
EXT255DX and 255iDXIP50
EXT75DX and 75iDX/NW25IP50
EXT75iDX/NW16IP50
B722-40-880 Issue E
Technical data
2.2Pumping media
Vent dangerous gases and gas mixtures safely, do not expose people to these gases. If pumping
hazardous gases or vapours, observe the safety recommendations of the supplier of the gas/
vapour.
Do not use the DX pump to pump pyrophoric or explosive gas mixtures, as it is not suitable for this
purpose. The pump and its connections are not designed to contain an explosion.
In the interstage versions of the DX pumps, gas pumped through the interstage port will mix with
gas pumped through the pump inlet. Ensure that the gases will not react or combine to form
dangerous gases and substances.
Do not expose any part of the human body to vacuum.
Do not use the DX pump to pump gases containing more than 20% oxygen unless the pump is gas purged. If you
do, the lubricant will polymerise and the pump may fail prematurely.
Do not use a DX pump to pump mercury vapour and do not allow mercury (for example, from a McLeod gauge)
to come into contact with the pump. If you do, the pump rotor may corrode and fail.
Note:Concentrations of gases may be modified by the compression of the pump.
The pumps are designed to pump the following residual gases normally used in high-vacuum systems:
z Airz Carbon dioxide
z Methanez Neon
z Propanez Krypton
z Butanez Helium
z Carbon monoxidez Ethane
z Nitrogenz Argon
z Hydrogen
You can use the pump to pump oxygen and water vapour, subject to the following conditions:
z Oxygen – when the pump is purged by an inert gas, oxygen can be pumped at concentrations above 20% by
volume. Refer to Section 2.4 for Purge gas specification. However, if the pump is not purged, the oxygen
concentration must be less than 20% by volume.
z Water vapour - you must ensure that vapour does not condense inside the pump; refer to Section 3.9.3.
If you wish to pump a gas not in the list above, contact your supplier for advice. If you do not contact your supplier,
you may invalidate the warranty on the pump. The pump is not suitable for pumping aggressive or corrosive gases.
Table 3 - D X p u mps tec h n i c al data
Parameter
EXT75DX
ISO63
EXT75DX
63CF
EXT75DX
NW40
EXT75DX
ISO100
Mass3.0 kg4.9 kg2.9 kg3.2 kg
Inlet-flangeDN63ISO-KDN63CFDN40NWDN100ISO-K
Outlet-flangeDN16NWDN16NWDN16NWDN16NW
Vent-port1/8 inch BSP1/8 inch BSP1/8 inch BSP1/8 inch BSP
Purge-port1/8 inch BSP1/8 inch BSP1/8 inch BSP1/8 inch BSP
Pumping speeds are without inlet-screen or inlet-strainer. Inlet-screens and inlet-strainers reduce speed by
approximately 10%.
†
Ultimate pressure 48 hours after bakeout with 2-stage rotary vane backing-pump
‡
Ultimate pressure 48 hours after bakeout with Pb < 5 mbar (500 Pa).
‡
<5 x 10-8 mbar
(DN100ISO-K inlet-
flange)
<5 x 10-8 mbar
(DN100ISO-K inlet-
flange)
EXT255DX
100CF
<5 x 10-9 mbar
(DN100CF inlet-flange)
Table 5 - D X p u mps tec h n i c al data
ParameterEXT75DXEXT255DX
Critical backing pressure
N
2
*
8 mbar12 mbar
He6.5 mbar9 mbar
H
2
Minimum backing pump displacement0.6 m3 h
Maximum Continuous Backing Pressure
†
2.5 mbar2.5 mbar
-1
0.6 m3 h
(at Ultimate Inlet Pressure)
Nitrogen:
Water Cooling (40 °C a mbient)
‡
4 mbar7 mbar
Forced Air Cooling (35 °C ambient)5 mbar5 mbar
Natural Convection Cooling (30 °C ambient)2 mbar2 mbar
Maximum continuous inlet pressure
†
(at Ultimate Backing Pressure)
Nitrogen:
Water cooling (40 ºC ambient)
‡
2 x 10-2 mbar1 x 10-2 mbar
Forced Air cooling at (35 ºC ambient)3 x 10-2 mbar8 x 10-3 mbar
Natural Convection Cooling (30 °C ambient)8 x 10-3 mbar2 x 10-3 mbar
Argon:
Water cooling (40 ºC ambient)
‡
4 x 10-3 mbar7 x 10-3 mbar
Forced Air cooling at (35 ºC ambient)4 x 10-3 mbar5 x 10-3 mbar
-3
Natural Convection Cooling (30 °C ambient)1 x 10
Recommended backing pump
**
Operating attitudeVertical and upright
through to horizontal ± 2 °
Nominal rotational speed90,000 revolutions per
Starting time to 90% speed
††
mbar1 x 10-3 mbar
RV3RV12
Vertical and upright
through to horizontal ± 2 °
60,000 revolutions per
minute
minute
110 seconds78 seconds
Sound power level (1 metre away)< 50 dB(A)<50 dB(A)
*
Pumping speed is reduced to 90% of its original value.
†
Above this pressure, rotational speed drops below nominal. Values for maximum continuous inlet pressure
obtained using a RV12 backing pump. Refer to Section 3.9 for cooling conditions.
‡
Cooling water temperature at 15 °C. Cooling water flow rate at 30 l hr-1.
**
A suitable diaphram pump with ultimate <5 mbar may also be used.
††
Power limit setting 80 W (EXT75DX), 160 W (EXT255DX).
Edwards and the Edwards logo are trademarks of Edwards Limited.
B722-40-880 Issue E
2.3Vent gas specification and vent control data
Although the pump may be vented to atmosphere, high relative humidity of the air may greatly increase the
subsequent pump-down time. To reduce pump-down times you should vent with dry, clean gases. Refer to Section 3.8
for a description of the vent options and the vent valve connection and refer to Section 4.1.3 for configuring the
venting options.
Table 6 - Vent gas specification and vent control
Vent gas specification and controlReference data
Vent gasDry air, nitrogen, argon or other inert gases
Maximum dew point at atmospheric pressure-22 °C
Maximum size of particulates1
Maximum concentration of oil0.1 parts per million
Recommended time for rotational speed to reach 50%> 15 seconds
Maximum allowed rate of pressure riseRefer to Figure 3
Figure 3 - Maximum allowed rate of pressure rise during venting: pressure against time (with pump initially at
Purge gasDry air, nitrogen, argon or other inert gases
Maximum dew point at atmospheric pressure-22 °C
Maximum size of particulates1
Maximum concentration of oil0.1 parts per million
Allowable purge gas flow (when required)20 to 50 sccm (0.33 to 0.84 mbar l s
Recommended purge gas flow25 sccm (0.42 mbar l s-1, 42 Pa l s-1)
Maximum allowable purge gas supply pressure2 bar (gauge); 29 psi, 3 x 105 Pa
Table 8 - Cooling water specification
Cooling water specificationReference data
QualityMechanically clean and optically clear with no deposits
pH value6.0 to 8.0
Maximum calcium carbonate concentration75 parts per million
Maximum chloride concentration100 parts per million
Minimum oxygen concentration4 parts per million
Minimum cooling water flow rate (at 15 °C)15 l hr
Water temperatureRefer to Ta bl e 5
Maximum water pressure5 bar (gauge), 73.5 psig, 6 x 10
Materials exposed to cooling-waterNickel plated brass
µm
or turbidity
-1
or 33 to 84 Pa l s-1)
-1
5
Pa
2.5Cooling water
The above cooling water specification corresponds to a typical high-quality drinking water specification. Check with
your water supply authority if you are in doubt about the quality of your supply.
2.6Materials exposed to gases pumped
The following materials and component types are exposed to the gases pumped:
Aluminium alloys, stainless steels, fluoroelastomer and nitrile O-rings, hydrocarbon lubricant, felt, rare earth
magnets, silicon nitride, phenolic resin, carbon-fibre reinforced epoxy resin, fire retardant polypropylene,
polyamide and PVC.
Edwards and the Edwards logo are trademarks of Edwards Limited.
B722-40-880 Issue E
2.7Electrical data
DX pumps can be driven either by your own system or by the Edwards TIC Turbo Instrument Controller or TIC Turbo
Controller.
If you wish to use your own system, the size of the power supply you must use depends on your application. The power
limit setting determines how quickly you can ramp up the pump and dictates the size of power supply you will need.
If you have serial communications capability, or have access to an Edwards TIC, you can select the power limit setting
of the DX pump. Refer to Table 9 for the maximum and minimum power limit settings for DX pumps and for the
associated maximum input current requirements. If your application requires rapid cycling of the pump, you can
achieve faster ramp times if you use a power supply that delivers higher current, up to a maximum in accordance
with Table 9.
If you do not have the facility to adjust the power limit setting, you must use a power supply capable of delivering
enough current to meet the Edwards factory default power limit setting, shown in Table 9. For the EXT75DX this
would be around 4 amps and for the EXT255DX it would be around 7 amps.
If you intend to drive the DX pump using an Edwards TIC, be aware that there are several variants. Contact Edwards
to determine which is most suitable for your application.
2.8Logic interface connector
Technical data
DX pumps have a 15-way logic interface connector on the end of the logic interface cable (see Figure 1 and 2, items
11 and 3 respectively). The logic interface connector can be plugged directly into the Edwards TIC Turbo Instrument
Controller or TIC Turbo Controller. You must use a suitable connector mating half (not supplied) to connect the DX
pump to your own equipment. Refer to Table 9 for the connector mating half type and to Table 10 for Logic Interface
connector pins for the electrical connections.
Table 9 - Logic interface technical data
Logic interface itemEXT75DXEXT255DX
Connector
DX pumps electrical supply:
Allowable voltage range
(including any ripple)
Maximum voltage ripple0.5 V r.m.s.0.5 V r.m.s.
Maximum input current with
maximum power limit setting
Maximum input current with
minimum power limit setting
Fuse (or equivalent current
limiting device) rating
Factory default setting80 W160 W
Maximum power limit120 W200 W
Minimum power limit50 W80 W
Hardware control input signal:
Enabled control voltage: low
(close)
Disabled control voltage: high
(open)
*
15-way D-type male15-way D-type male
24 V d.c. +5%, -10%
(21.6 to 25.2 V d.c.)
<6 A at 24 V during ramp<10 A at 24 V during ramp
<3 A at 24 V<5 A at 24 V
6 A type 'T' IEC approved or
6 A time delay fuse UL/CSA approved
0 to 0.8 V d.c. (I
nominal)
4 to 26.4 V d.c. (Internal pull up to
6.35 V nominal)
= 0.55 mA
out
24 V d.c. +5%, -10%
(21.6 to 25.2 V d.c.)
10 A type 'T' IEC approved or
10 A time delay fuse UL/CSA
approved
FailOff (3.3 kΩ pull up to 12 V d.c.)Off (3.3 kΩ pull up to 12 V d.c.)
OKOn (<0.1 V d.c. sinking 1.7 mA,
<0.8 V d.c. sinking 20 mA)
Rating20 mA to 0 V20 mA to 0 V
*
Mating half of connector not supplied.
0 to 10 V d.c. (directly proportional
to measured parameter)
Motor speed: 0 - 1000 Hz (0-100%)
Motor power: 0 - 200 W
Motor temperature: 0 - 100 °C
Controller temperature: 0 - 100 °C
On (<0.1 V d.c. sinking 1.7 mA,
<0.8 V d.c. sinking 20 mA)
2.9Podule connector socket
The DX pump has a 2-way Podule Connector Socket in the top of the Podule. When you receive the pump, this
connector will be concealed by a black protective cover. If you intend to use the connector, this cover should be
removed by levering with a small screwdriver. The mating plug for this connector is supplied with the pump.
The connector is intended to drive a vent valve or fan connected to the two pins. The connecto r mat in g p lu g i s shown
in Figure 4, with the polarity of the pins marked when the vent valve/fan is energised.
The podule connector plug is available as an accessory, see Section 7.4.