Edwards EST EDW2151A Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
WARNING
EDW2151A Low Profile Photoelectronic Plug-in Smoke Detector
Specications
Size Height: 2.0 inches (51 mm) installed in B401A Base Diameter: 4.1 inches (104 mm) installed in B401A Base
6.1 inches (155 mm) installed in B110LPA Base Weight: 3.1 oz. (88 g) Operating Temperature Range: 0°C to 49°C (32°F to 120°F) Operating Humidity Range: 10% to 93% Relative Humidity noncondensing Operating Voltage 8.5 to 35VDC Standby Current 120 uA Latching Alarm: Reset by momentary power interruption.
625 6th Street East, Owen Sound, Ontario N4K-5P8
TEL:519-376-2430, FAX: 519-376-1296
Before Installing
Please thoroughly read the manual A05-1003, Applica­tions Guide for System Smoke Detectors, which provides
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector must be tested and maintained regularly following CAN/ULC S536 requirements. The de­tector should be cleaned at least once a year.
General Description
The EDW2151A low-prole photoelectronic detector uses
a state-of-the-art optical sensing chamber. This detector is designed to provide open area protection and to be used with compatible ULC listed control panels only. The ca­pability of plugging this detector into a variety of special bases makes it more versatile than equivalent direct-wired models.
Two LEDs on each detector provide local 360° visible
alarm indication. They ash every ve seconds indicating
that power is applied and the detector is working properly. The LEDs latch on in alarm. Remote LED annunciator ca­pability is standard and may be implemented through an optional accessory RA100ZA. The alarm can be reset only by a momentary power interruption. This detector may be tested by activating the internal reed switch with a magnet, or by using the CSENS-RDRA infrared sensitivity reader.
Base Selection And Wiring Guide
Refer to the installation instructions for the Plug-in Detector Bases for base selection and wiring instructions. Edwards has a variety of detector bases available for this smoke detector, including 2-wire applications with and without re­lays and/or current limiting resistors, 4-wire and 120VAC
D100-101-00 1 I56-1580-000
applications.
All bases are provided with screw terminals for power, ground, remote annunciator connections and relay contact connections, if applicable. The electrical ratings for each detector-base combination are also included in the base installation instructions.
Installation
Installation shall comply with the latest version of CAN/ ULC S524, Installation of Fire Alarm Systems.
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations.
NOTE: Verify that all detector bases are installed, that the initiating-device circuits have been tested, and that the wiring is correct. (Refer to detector base manual for testing procedure.)
Remove power from initiating-device circuits before install­ing detectors.
1. Install detectors: a. Place the detector into the detector base. b. Turn the detector clockwise until the detector drops
into place.
c. Continue turning detector clockwise to lock it in place.
2. Tamper Resistance: The detector bases can be made tamper resistant. When capability is enabled, detectors cannot be removed from the base without the use of a tool. See the detector base installation manual of the detector base for details in using this capability.
3. After all detectors have been installed, apply power to
the control unit.
CAUTION
CAUTION
LED Status
Indicators
Magnet Test
Marker
Test Magnet
Position
Test Magnet
Position
Magnet Test
Marker
CSENS-RDRA
Location
4. Test the detector using the magnet as described under TESTING.
5. Reset the detector at the system control panel.
6. Notify the proper authorities that the system is back on line.
Dust covers are an effective way to limit the entry of dust into smoke detector sensing chambers. However, they may not completely prevent airborne dust particles from entering the detector. Therefore, Edwards recommends the removal of detectors before beginning construction or other dust producing activity.
Be sure to remove the dust covers from any sensors that were left in place during construction as part of returning the system to service.
Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
Testing
Before testing, notify the proper authorities that the smoke detector system is undergoing maintenance and will tem­porarily be out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms. De­tectors must be tested after installation and as part of peri­odic maintenance. Test EDW2151A as follows:
NOTE: Before testing the detector, check to ensure the LEDs blink. If they do not, the detector has lost power (check the wiring) or it is defective (return it for repair).
A. Test Magnet (p/n M02-04-01 or M02-09-00)
1. Place the magnet against the cover in the location designated by the raised mark to activate the test fea­ture (see Figure 1).
2. The LEDs should latch ON within 5 seconds indicat­ing alarm and annunciating the panel.
B. Test Module (CSENS-RDRA) Use the CSENS-RDRA Sensitivity reader to measure
the sensitivity of the detectors. Please refer to the CSENS-RDRA instruction manual for operating details.
B. Aerosol Generator (Gemini 501) Set the generator to represent 4% to 5%/ft. obscura-
tion as described in the Gemini 501 Manual. Using the bowl- shaped applicator, apply aerosol until unit alarms.
Notify the proper authorities that the system is back on line.
Detectors that fail these tests should be cleaned as de­scribed under MAINTENANCE and retested. If the detec­tors still fail these tests, they should be returned for repair.
Cleaning
Before removing the detector, notify the proper authorities that the smoke detector system is undergoing maintenance and will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.
Figure 1. Bottom and side views showing position of test magnet:
D100-101-00 2 I56-1580-000
C0145-00
Loading...
+ 2 hidden pages