Crawley Business Quarter,
Manor Royal,
Crawley,
West Sussex, RH10 9LW, UK
declare under our sole responsibility, as manufacturer and person within the EU
authorised to assemble the technical file, that the product(s)
Drypump Profibus Module D397-52-000
to which this declaration relates is in conformity with the followin g standard(s) or
other normative document(s)
EN61326-1:2013 Electrical equipment for measurement, control and
(Class B Emissions, laboratory Use. EMC requirements. General requirements
Industrial Immunity)
and fulfils all the relevant provisions of
2014/30/EU Electromagnetic Compatibility (EMC) Directive
Note: This declaration covers all product serial numbers from the date this Declaration was
signed onwards.
16.07.2015, Eastbourne
Larry Marini, Senior Technical Manager Date and Place
This product has been manufactured under a quality management system certified to ISO 9001:2008
P200-02-820 Issue C
P200-10-085
Issue A
Material Declaration
In accordance with the requirements of the Chinese regulatory requirement on the Ma nagement Methods for the
Restriction of the Use of Hazardous Substances in Electrical and Electronic Products Order No. 32 (also known as
‘China RoHS2’) and SJ/T 11364 Marking for the Restricted Use of Hazardous Substances in Electronic and Electrical
Products:
Product Product Label Meaning
This product contains hazardous substances in at
least one of the homogeneous materials used
which are above the limit requirement in GB/T
D39752000 Drypump Profibus Module
部件名称
Part name
印刷电路组件 (PCA)
Printed Circuit
Assembly (PCA)
电缆/电线/连接器
Cable/wire/connector
机械部件
Mechanical Components
铅
Lead
(Pb)
Mercury
(Hg)
X O X
X O
X O
材料成分声明
Materials Content Declaration
Hazardous Substances
汞
镉
Cadmium
(Cd)
O O O O
O O O O
26572 as detailed in the declaration table below.
These parts can safely be used for the
environmental protection use period as
indicated.
有害物质
六价铬
Hexavalent
Chromium
(Cr VI)
多溴联苯
Polybrominated
biphenyls (PBB)
多溴二苯醚
Polybrominated
diphenyl ethers
(PBDE)
O O O
O: 表示该有害物质在该部件的所有均质材料中的含量低于 GB/T 26572 标准规定的限量要求。
O: Indicates that the hazardous substance contained in all of the homogeneous materials for this part is
below the limit requirement in GB/T 26572.
X: 表示该有害物质在该部件的至少一种均质材料中的含量超出 GB/T26572 标准规定的限量要求。
X: Indicates that the hazardous substance contained in at least one of the homogeneous materials used for
this part is above the limit requirement of GB/T26572.
Edwards and the Edwards logo are trademarks of Edwards Limited.
D397-52-880 Issue D
CAUTION
WARNING
1Introduction
1.1Scope and definitions
This manual provides installation, operation and maintenance instructions for the Edwards Drypump Profibus Module.
You must use the Module as specified in this manual.
Read this manual before you install and operate the Module. Important safety information is highlighted as WARNING
and CAUTION instructions; you must obey these instructions. The use of WARNINGS and CAUTIONS is defined below.
Warnings are given where failure to observe the instruction could result in injury or death to
people.
Cautions are given where failure to observe the instruction could result in damage to the equipment, associated
equipment and process.
Introduction
Throughout this manual, page, figure or title numbers are sequential.
The following labels appear on the module:
Warning - refer to accompanying documentation.
Edwards offer European customers a recycling service.
Edwards take no responsibility for damage or injury caused by improper use of the equipment.
This equipment provides remote control of an Edwards Drypump. You must refer to the safety
information in the Drypump instruction manual.
This unit should not be relied upon for safety related functions.
The Drypump Profibus Module p rovides a Profibus DP V0 slave interface for Edwards drypumps with a PDT (Pump
Display Terminal) port. This does not include older pumps with a PDM (Pump Display Module) port. The module
communicates with the pump using the RS232 interface. Commands received from the Profibus network are relayed
to the pump. Data from the pump is stored in the module and transmitted over the Profibus network when requested.
Most drypumps provide the DC power for the module. The front panel of the module has four L EDs which indicate the
status of the module and the Profibus network. he Profibus slave address is set using ro tary switches. The ba ck panel
of the module has a 9-way 'D' connector for the Profibus network, a 9-way 'D' connector for the RS232 link to the
drypump and a power connector.
Edwards and the Edwards logo are trademarks of Edwards Limited.
2Technical data
WARNING
2.1Mechanical data
Weight0.28 kg
Dimensions129 x 30.5 x 117 mm
Refer to Section 3.2 for installed dimensions and panel cut-out.
2.2Operating and storage data
Ambient operating temperature0 °C to 40 °C
HumidityMaximum 90% RH non-condensing
Maximum altitude2000 m
IP ratingIP30 - indoor use only
Ambient storage temperature-30°C to 70°C
D397-52-880 Issue D
Technical data
2.3Electrical data
Do not exceed the maximum supply voltage. Excessive supply voltage will cause permanent
damage to the control electronics and may result in a mechanical hazard in some failure
conditions.
Electrical supply9 V d.c. to 52 V d.c.
Power consumption5 W maximum Switch on surge 500 mA maximum
FuseNo internal fuse
2.3.1D.C. Power connector
Connector type2 Way Receptacle. Mating part is cable-mount
Terminal Block. Suitable parts inclu de: Phoenix MSTB
Connector type9-way ‘D’ type socket (Refer to Figure 2)
Profibus Data signalsElectrically compliant with RS485 specification.
Profibus Power Supply10 mA supply (protected) for external terminator
ChassisFor Profibus cable screen connection
Repeater control signalDigital signal, nominally 0-5 V but with series 340 ohm
Figure 2 - Pin connections for 9-way ‘D’ type socket
Isolated from chassis.
resistors if required.
resistor. High = module transmitting. Low = Receiving
or Idle.
Table 1 - Pin connections for 9-way ‘D’ type socket
PinAllocation
1
2
3
4
5
6
7
8
9
Shell
Chassis (box)
Not connected
Profibus Data + (B)
Control Signal for Repeater
Profibus Data reference (isolated)
Profibus 5V output (isolated)
Not connected
Profibus Data - (A)
Not connected
Chassis (box)
Remove all of the packaging material and check the module . If the module is damaged, follow the Edwards return of
equipment procedures that are laid out in the back of this manual. Do not use the module if it is damaged.
Check that your package contains the items that are listed in Table 3. If any of the s e it ems are missing, notify your
supplier in writing within three days. If the module is not to be used immediately, store the module in suitable
conditions as described in Section 6.1.
Table 3 - Component checklist
?
)
QuantityDescriptionCheck(
1Module
1Instruction manual
1Cable for connection between pump PDT port and Profibus
The unit is IP30 rated. Please ensure that the unit is not installed where fluids can enter into the module.
The module can be rack mounted, panel mounted, DIN rail mounted or free-standing. Sufficient space must be
provided at the rear of the unit for the cables. If right-angled connectors are used additional space will be requ ired.
If the unit is to be used free-standing it should be laid flat to ensure stability. The four self-adhesive rubber feet can
be used to prevent sliding. Figure 4 shows the dimensions of the module with the rubber feet attached.
Edwards and the Edwards logo are trademarks of Edwards Limited.
D397-52-880 Issue D
3.2.1Rack mounting
For rack mounting the unit should be fitted in a space 6HP wide x 3U high, using the 2-off M2.5 screws provided.
3.2.2Panel mounting
For panel mounting cut the aperture in the panel using the dimensions shown in Figure 5. The module can be fixed
into the panel with the 2-off M2.5 screws.
Figure 5 - Panel mounting the module (mm)
Installation
3.2.3DIN rail mounting
For DIN rail mounting the 2 clips should be attached to the module using 2-off M3 screws provided (one in the centre
of each clip), as shown in Figure 6. The clips should then be roughly aligned with the box sides. The clips can then
be fitted to a suitable DIN-rail, as shown in Figure 6.
It is recommended to use end stops on a DIN rail system.
When installing the module ensure that the cables are laid out and secured in a manner that will
not create a trip hazard.
The Profibus module should not be connected to a Drypump when the pump or tool are "On Process".
The Profibus module uses a Drypump's PDT port (normally a 5-way XLR socket) for communication with the Drypump.
It is not possible to connect any other devices to the same PDT port when that port is used by the Profibus module,
for example a PDT.
Some PDT connectors are not able to supply enough power to operate the Profibus modu le . However for mos t pump
types an alternative power source will be available. See Table 4 below.
Table 4 - Drypump connections
Drypump TypePDT Port PositionDrypump Connection Ports
iXHFrontUse rear PDT port only
iXHRearPDT port only (see Section 3.3.1)
iXL (Large)FrontUse rear PDT port only
iXL (Large)RearPDT port only (see Section 3.3.1)
pXHFrontUse rear PDT port only
pXHRearPDT port only (see Section 3.3.1)
iGX RemoteFrontPDT port only (see Section 3.3.1)
iGX RemoteRearPDT + LON for power (see Section 3.3.2)
iGX SystemableEitherExternal power required - Contact Edwards for advice
pHMBUpperPDT port only (see Section 3.3.1)
pHMBLowerPDT + LON for power (or upper PDT only)
iHFrontPDT + LON for power (see Section 3.3.2)
iFFrontPDT + LON for power (see Section 3.3.2)
If the pump has several accessories at tached, guidance should be so ught from Edward s to ensure the pump is ab le to
provide enough power.
Edwards and the Edwards logo are trademarks of Edwards Limited.
D397-52-880 Issue D
3.3.1Connection to a PDT Port only
If connecting to a PDT port capable of powering the Profibus module then either use the cable provided in the kit
(5m long) or cable length may be increased using 5-way XLR extension cables. See Section 7.2.
Connect the 9-way D-type free socket and the DC power connector to the Profibus module. Connect the 5-way XLR
plug to the Drypump PDT port.
3.3.2Connection to a PDT Port and a LON Port
Where connections to both a PDT socket and a LON socket is required the LON/PDT power/RS-232 splitter cable mu st
be used. See Section 7.2. This is to be used with the cable provided in this kit. The 5-way XLR plug of the long cable
should be connected to the 5-way XLR socket of the short splitter cable to make one cable assemb ly. The XLR plugs
can then be connected to the pump and the 9-way D-type and power connector connected to the Profibus module.
Cable length may be increased using 5-way XLR extension cables. See Section 7.2.
Figure 7 - Profibus module rear connections
Installation
3.4Profibus network connection
Standard Profibus network cables and connectors compliant to EN50170 should be used to connect the Edwards
Drypump Profibus module to your system.
Bus-termination is not supplied with the module, but must be used as for a normal Profibus DP system. Bus
termination must be used at both end s of th e Prof ibus tr unk and not anywhere else. If the module is placed at one
end of the trunk a connector containing the standard termination resistors should be used. The appropriate 5 V and
0 V signals are supplied on the standard pins for this purpose.
The Profibus module is for connection to a Profibus DP network and operates as a V0 slave only.
The Profibus master requires a GSD file for each slave. The GSD file for this slave is contained on the CD supplied
with the unit and has the file name "EDW0BC2.GSD", which is registered with the Profibus association.
When configuring your system the "ID" number will be 0BC2 and the unit's description will be “Edwards Drypump”.
Note:The GSD file should not be altered.
4.2Quick start set up instructions
1. Install the module and connect the cables as described in Section 3.
2. Set the address switches on the Profibus module. See Section 4.4.
3. Apply power (or power cycle the Profibus module, for example by disconnecting then reconnecting the power
connector).
4. Load the GSD file into your Profibus system configurator.
5. Select "Edwards Drypump" as a slave and set the address to match the address switches.
6. Select Module 11 to provide on and off control of the Drypump and select Module 992 to monitor pump alert
state. Add other Profibus software modules as required.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Table 5 - Front panel symbols and their functions
SymbolNameFunction
Data exchangeModule is in data exchange as defined by the Profibus standard.
Off-lineModule is not in data exchange as defined by the Profibus standard.
ErrorON at the same as Offline LED = Configuration or parameterisation
error:
Flashing at 1 Hz = Invalid address selected.
PowerInternal 5 V supply is operating.
D397-52-880 Issue D
Operation
Upper address
switch
Lower address
switch
Sets value of upper nibble of address (Hexadecimal).
Sets value of lower nibble of address (Hexadecimal).
4.4Address set-up
The module address can be set from 1 to 125 using the two hexadecimal rotary switches on the front panel. The lower
switch defines the lower half of the address byte (nibble) and the uppe r switch defines the upper half of the address
byte. Each node on a Profibus network must have a unique address. The address swi tches will only be read by the
unit at power-up. Any change of address setting after power-up will be ignored until next power-up.
Note:If the address is set to a value greater than 125 (decimal) or 0, the RED error LED will flash at 1 Hz and the
module will go online. If this occurs either, change the address and cycle the power or remove power and
change the address.
4.5Baud-rate
All 10 standard DP baud-rates are supported. These are: 9.6kBd; 19.2kBd; 45.45kBd; 93.75kBd; 187.5kBd; 500kBd;
1.5MBd; 3MBd; 6MBd; 12MBd. The unit has no facility for adjusting baud-rate as detection is automatic, and it will
therefore respond to the baud-rate chosen by the master.
4.6Software format
The Slave software is based upon a modular configurab le architecture so the us er has considerable cont rol of the
contents of the data exchange messages.
The software modules (defined in the GSD files) relate to the controller serial communications objects.
When the unit is linked onto the Profibus it will be parameterised and then configured before entering data exchange.
The configuration choices ar e in the GSD file and it s comments describe th e data content of the input and output
bytes. These choices will often be made using a third party configurator such as SyCon that presents a user-friendlier
interface.
16-bit values are transmitted with the MSB first and the LSB last.
Only the Profibus mandatory 7 bytes of parameterisat ion data are used by the Dryp ump Profibus slave. None of these
values can be adjusted by the user.
4.6.2Configuration
During configuration the user can define what modules are required and in which order the data is transferred. The
unit adds the input and output data bytes to the message maps in the order that they are de fined in the configuration
message.
Example:
Module = Mod_A 3 bytes in (Ai1, Ai2, Ai3), 1 byte out (Ao1)
Module = Mod_B 2 bytes in (Bi1, Bi2), 2 bytes out (Bo1, Bo2)
A) Configure Mod_A, Mod_B gives
Output map: -
Byte1Byte2Byte3
Ao1Bo1B02
Input map:-
Byte1Byte2Byte3Byte4Byte5
Ai1Ai2Ai3Bi1Bi2
B) Configure Mod_B, Mod_A gives
Output map:-
Byte1Byte2Byte3
Bo1Bo2Ao1
Input map:-
Byte1Byte2Byte3Byte4Byte5
Bi1Bi2Ai1Ai2Ai3
Data is always referred to the Master so outp ut is control data from Mas ter to Slave a nd input da ta is feed ba ck from
Slave to Master. There are many software modules a nd many bytes of da ta. Care must be tak en in correctly selecting
and aligning the data into your system.
Modules should have no more than one entry in the configuration list. For reliable operation do not exceed the
maximum number of configuration items.
Configuration itemMaximum number
Modules40
Input and output bytes added together116
Edwards and the Edwards logo are trademarks of Edwards Limited.
D397-52-880 Issue D
4.6.3Diagnostics description
The modules use extended diagnostics in the format below.
Max_Diag_Data_Len = 12
Bytes1-678 and 910 and 1112
MandatoryNo of bytes of
Description
A configuration error will be signalled if the number of modules co nfigured exceeds the maximum number allowed
by the Profibus module.
Loss of serial comms may take up to 20 seconds to be signalled. If this occurs the Slave will signal the Master with a
‘Data High’ flag in the Frame Control byte but will continue to be in data exchange with the data values all set to
zero. The extended diagnostics message will be available to the Master.
If RS232 communications are restored the Slave will again signal the Master with a ‘Data High’ flag in the Frame
Control byte and will return to ‘good’ data exchange values. Again the extended diagnostics message will be available
to the Master.
extended
diagnostics (6)
Not used (values
always zero)
Module failed
configuration,
MSB in 10, LSB
in 11
Serial comms
lost (0=OK,
1=lost)
Operation
4.6.4Data exchange values
The Edwards Drypump GSD file has been designed to control all types of Edwards Drypumps with a PDT port. This
includes:
Many different pump families (for example iH, iGX, iXH).
Different pump types (standard Drypumps, mechanical boosters and proximity boosters).
Variations of which accessories are fitted (for example gas modules, exhaust and water sensors).
Due to the many possible hardware variations some of the GSD file modules will not be applicable or suitable for a
particular pump.
Rather than attempting to define the exact pump configuration before data exchange (a process that would take
several minutes) and signal a configuration error for an inappropriate Profibus configur ation select ion, the module
will accept any configuration and enter data exchange very quickly. However at the start of data exchange this means
almost no data will actually be available to the Profibus unit and thus not to the Profibus user. Instead a "CONDITION
BYTE" is appended to most of the configurable modules. The condition byte indicates whether the data in that module
is both present and valid. The condition byte uses bits as st atus flags. Flags are use d for 'Valid Object No.' and 'Valid
Reading'. A valid object number indicates the pump has messages for that object number. A valid reading indicates
that the object number does not have its "No Reading" flag set. These flags will show condition as invalid (flag bit
value of 0) until known to be valid. Thus data exchange will start with the Condition byte status flags set to invalid.
The user should ignore all other (preceding) data within that software module until both status flags indicate data is
valid.
The condition byte also provides Alarm and Warning bit flags. See below.
Bit No.FunctionMeaning of 0Meaning of 1
7Reserved
6Reserved
5AlarmNo AlarmAlarm
4WarningNo WarningWarning
3Reserved
2Reserved
1Valid ReadingInvalidValid Reading
0Valid Object No.InvalidValid Object
Thus a good condition byte will have the value 03 (hex). Data is not valid (should be ignored) u nless both valid flags
are set.
The Warning and Alarm flags may be inhibited in the Drypump setup. In this case a Warning or Alarm will not be
indicated over Profib us.
The update rate (latency) varies significantly for different parameters, typically between a second and a minute. In
addition a Drypump takes up to 15 seconds from power-up before it starts to communicate with peripherals.
Drypumps have more than one control device that in principle can control the pump. The Drypump will only let one
control device have control at a time. This is indicated by this module. At power-up no control device has control.
To start a pump, or turn ON any item like a valve, a control device (e.g. Profibus, PDT) must take control. That
control device must release control before another control device can turn ON any item. However, in some cases a
control device can turn OFF an item without having control. The Profibus module only takes control of the pump
when it receives a run command from the tool using Module 11 and no other control device has control.
Output bytes: None
Input bytes: Bytes 1 and 2 form a 16-bit unsigne d number which is the object number of the unit which has control
of the pumping system. Example values (decimal): 0=No Control; 61=Drypump Front Panel;
101=PDM1; 102=PDM2; 103=PDT Front; 104=PDT Rear; 110=Profibus in Control; 221=Micro-TIM.
Byte 3 is condition byte (see Section 4.6.4).
4.7.4Module 992 - Alert Status
This module is a summary of all the warnings and alarms from the pump (except those inhibited by the Drypump
internal setting). It does not just sign al alarms and warnings from configured Profibus modules but signals all rece ived
alarms and warnings including from functions that cannot be configured through Profibus.
The four input bytes are bit flags. If a flag value is 0 that function has no alert. If the exact caus e of a warning is
unclear it is recommended the user investigate the pump locally using a PDT.
Output bytes: None
Input bytes: Byte 1 Bit 7 = Alarm - EMS system
Byte 1 Bit 6 = Alarm - Drypump drive
Byte 1 Bit 5 = Alarm - Mechanical booster drive
Byte 1 Bit 4 = Alarm - Proximity booster drive
Byte 1 Bit 3 = Alarm - Drypump temperature
Byte 1 Bit 2 = Alarm - Mechanical booster temperature
Byte 1 Bit 1 = Alarm - Proximity booster temperature
Byte 1 Bit 0 = Alarm - Exhaust temperature
Byte 2 Bit 7 = Alarm - Exhaust pressure
Byte 2 Bit 6 = Alarm - Gas
Byte 2 Bit 5 = Alarm - Gate valve
Byte 2 Bit 4 = Alarm - Water flow
Byte 2 Bit 3 = Alarm - Service due
Byte 2 Bit 2 = Alarm - System controller - system
Byte 2 Bit 1 = Alarm - System controller - device
Byte 2 Bit 0 = Alarm - other (any alarm not in categories above).
Byte 3 Bit 7 = Warning - EMS system
Byte 3 Bit 6 = Warning - Drypump drive
Byte 3 Bit 5 = Warning - Mechanical booster drive
Byte 3 Bit 4 = Warning - Proximity booster drive
Byte 3 Bit 3 = Warning - Drypump temperature
Byte 3 Bit 2 = Warning - Mechanical booster temperature
Byte 3 Bit 1 = Warning - Proximity booster temperature
Byte 3 Bit 0 = Warning - Exhaust temperature
Byte 4 Bit 7 = Warning - Exhaust pressure
Byte 4 Bit 6 = Warning - Gas
Byte 4 Bit 5 = Warning - Gate valve
Byte 4 Bit 4 = Warning - Water flow
Byte 4 Bit 3 = Warning - Service due
Byte 4 Bit 2 = Warning - System controller - system
Byte 4 Bit 1 = Warning - System controller - device
Byte 4 Bit 0 = Warning - other (any warning not in categories above).
For example input bytes 00 80 00 E0 would indicate an exhaust pressure alarm + warn ings for exhaust
pressure, gas and gate valve.
To start the pump after the pump has stopped due to an alarm, the tool controller must send a Stop command
Edwards and the Edwards logo are trademarks of Edwards Limited.
D397-52-880 Issue D
4.7.5Module 11 - Pump Control
This is the main control software module. It is used to start and stop ALL connected pump s in sequence. The general
start sequence is DP(s) then MB(s) then PB(s). The shut down sequence is the reverse.
Output byte: Single byte is pump control.
Values: 1=On
2=Fast shut down,
3=Auto shut down (slow),
Other values - ignored.
Note:The value is only sent from the Profibus module to the pump on change of demand state (to prevent rapid
cycling if the pump had an alarm state). Thus if the demand state is on, but the pump has been stopped by
something other than the Profibus module, it will be necessary to demand an Off and then an On to restart
the pump.
Input bytes:Byte 1 reports the state (feedback) specifically of the DP.
Values: 0=Off
1=Off going On (starting)
2=On going off fast (stopping fast)
3=On going off slow (stopping slow)
4=On.
2nd input byte is condition byte (see Section 4.6.4).
Operation
4.7.6Module 14 - DP Run Hours
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number for DP run time in hours.
Byte 3 is condition byte (see Section 4.6.4).
4.7.7Module 20 - DP Number of Starts
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number which is the number of times the DP has been
started.
Byte 3 is condition byte (see Section 4.6.4).
4.7.8Module 21 - DP Time to Stop
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number for number of seconds it will take the pump to stop.
If pump is not in the process of stopping the value will be zero.
Byte 3 is condition byte (see Section 4.6.4).
4.7.9Module 3 - DP Current
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit signed number for DP current in 0.1A.
Byte 3 is condition byte (see Section 4.6.4).
4.7.10Module 4 - DP Power
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number for DP power in 0.1kW.
This module will only be valid on inverter driven pumps.
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number for actual DP speed in 0.1Hz.
Byte 3 is condition byte (see Section 4.6.4).
4.7.12Module 994 - DP Speed Relative
This module will only be valid on inverter driven pumps.
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number for actual DP speed in 0.1% of configured full speed.
Byte 3 is condition byte (see Section 4.6.4).
4.7.13Module 699 - DP Speed Demand
This module should only be used on inverter driven pumps.
Output bytes: 2 Bytes which are a 16-bit unsigned number for DP speed demand in 0.1% of configured full speed.
Input bytes:None
4.7.14Module 55 - DP Body Temperature
The actual meaning and measurement location of this temperature measurement will vary between pump families
and pump types, even if a valid temperature reading is indicated by the condition byte.
For iXH parameter is DP body temperature
For iGX parameter isDP body temperature
For iH/iF/iL parameter is DP motor temperature
Output bytes: None
Input bytes:Bytes 1 and 2 are a 16-bit signed number for DP temperature in °C.
Byte 3 is condition byte (see Section 4.6.4).
4.7.15Module 57 - DP End Cover Temperature
The actual meaning and measurement location of this temperature measurement will vary between pump families
and pump types, even if a valid temperature reading is indicated by the condition byte.
For iXH parameter is DP end cover temperature
For iGX parameter isDP motor temperature
For iH/iF/iL parameter is DP body temperature
Output bytes: None
Input bytes:Bytes 1 and 2 are a 16-bit signed number for DP temperature in °C.
Byte 3 is condition byte (see Section 4.6.4).
4.7.16Module 70 - DP Body Temperature 2
The actual meaning and measurement location of this temperature measurement will vary between pump families
and pump types, even if a valid temperature reading is indicated by the condition byte.
For iXH parameter is DP body temperature 2 (but not fitted to most pumps)
For iGX parameter isNot used
For iH/iF/iL parameter is DP High Vacuum Stage (but only fitted to the largest pumps)
Output bytes: None
Input bytes:Bytes 1 and 2 are a 16-bit signed number for DP temperature in °C.
Edwards and the Edwards logo are trademarks of Edwards Limited.
D397-52-880 Issue D
4.7.17Module 63 - Pump Internal Temperature
The actual meaning and measurement location of this temperature measurement will vary between pump families
and pump types, even if a valid temperature reading is indicated by the condition byte.
For iXH parameter is DP internal temperature
For iGX parameter isNot used
For iH/iF/iL parameter is Not used
Output bytes: None
Input bytes:Bytes 1 and 2 are a 16-bit signed number for temperature in °C.
Byte 3 is condition byte (see Section 4.6.4).
4.7.18Module 12 - MB Override
This module provides MB state feedback. It can als o be used to override the control of Mod ule 11 (as normally MB
operation would follow DP) to stop a booster. It can fu rther start a booster, but only if the Profibus module has
control of the pump. (See Section 4.7.3). Use this command with caution as if the Profibus module does not have
control it will be possible to stop the booster but not restart it. It is also not recommended to run the MB with the
DP stopped.
Output byte:Single byte is MB override.
Values: 1=On
2=Off
Other values - ignored.
Operation
Note:Demand value is only sent from the Profibus module to the pump on change of state.
Input bytes:Byte 1 reports the state (feedback) specifically of the booster.
Values: 0=Off
1=Off going on
2=On going off fast
3=On going off slow
4=on.
2nd input byte is condition byte (see Section 4.6.4).
4.7.19Module 7 - MB Current
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit signed number for MB curre nt in 0.1A.
Byte 3 is condition byte (see Section 4.6.4).
4.7.20Module 8 - MB Power
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number for MB Power in 0.1kW.
Byte 3 is condition byte (see Section 4.6.4).
4.7.21Module 174 - MB Speed Absolute
This module will only be valid on inverter driven pumps.
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number for actual MB speed in 0.1Hz.
Byte 3 is condition byte (see Section 4.6.4).
4.7.22Module 995 - MB Speed Relative
This module will only be valid on inverter driven pumps.
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number for actual MB speed in 0.1% of configured full speed.
This module should only be used on inverter driven pumps.
Output bytes: 2 Bytes which are a 16-bit unsigned number for MB speed demand in 0.1% of configured full speed.
Input bytes:None
4.7.24Module 54 - MB Body Temperature
The actual meaning and measurement location of this temperature measurement will vary between pump families
and pump types, even if a valid temperature reading is indicated by the condition byte.
For iXH parameter is MB body temperature
For iGX parameter isMB body temperature
For iH/iF/iL parameter is MB body temperature
Output bytes: None
Input bytes:Bytes 1 and 2 are a 16-bit signed number for MB temperature in °C.
Byte 3 is condition byte (see Section 4.6.4).
4.7.25Module 62 - MB End Cover Temperature
The actual meaning and measurement location of this temperature measurement will vary between pump families
and pump types, even if a valid temperature reading is indicated by the condition byte.
For iXH parameter is MB end cover temperature
For iGX parameter isMB motor temperature
For iH/iF/iL parameter is Not Used.
Output bytes: None
Input bytes:Bytes 1 and 2 are a 16-bit signed number for MB temperature in °C.
Byte 3 is condition byte (see Section 4.6.4).
4.7.26Module 812 - PB Override
This module provides PB state feedback. It can also be used to override the control of Module 11 (as normally PB
operation would follow DP) to stop a booster. It can fu rther start a booster, but only if the Profibus module has
control of the pump. (See Section 4.7.3). Use this command with caution as if the Profibus module does not have
control it may be possible to stop the booster but not restart it. It is al so not recom mended to run t he PB with the
DP stopped.
Output byte:Single byte is MB override.
Values: 1=On
2=Off
Other values - ignored.
Note:Demand value is only sent from the Profibus module to the pump on change of state.
Input bytes:Byte 1 reports the state (feedback) specifically of the booster.
Values: 0=Off
1=Off going on
2=On going off fast
3=On going off slow
4=On.
2nd input byte is condition byte (see Section 4.6.4).
4.7.27Module 817 - PB Run Hours
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number for PB run time in hours.
Edwards and the Edwards logo are trademarks of Edwards Limited.
D397-52-880 Issue D
4.7.28Module 818 - PB Number of Starts
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number which is the number of times the booster has been
started.
Byte 3 is condition byte (see Section 4.6.4).
4.7.29Module 820 - PB Current
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit signed number for PB current in 0.1A.
Byte 3 is condition byte (see Section 4.6.4).
4.7.30Module 821 - PB Power
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number for PB Power in 0.1kW.
Byte 3 is condition byte (see Section 4.6.4).
4.7.31Module 823 - PB Speed Absolute
Operation
This module will only be valid on inverter driven pumps.
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number for actual PB speed in 0.1Hz.
Byte 3 is condition byte (see Section 4.6.4).
4.7.32Module 996 - PB Speed Relative
This module will only be valid on inverter driven pumps.
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number for actual PB speed in 0.1% of configured full speed.
Byte 3 is condition byte (see Section 4.6.4).
4.7.33Module 697 - PB Speed Demand
This module should only be used on inverter driven pumps.
Output bytes: 2 bytes which are a 16-bit unsigned number for PB speed demand in 0.1% of configured full speed.
Input bytes:None
4.7.34Module 813 - PB Body Temperature
The actual meaning and measurement location of this temperature measurement will vary between pump families
and pump types, even if a valid temperature reading is indicated by the condition byte.
For iXH parameter is PB body temperature
For pHMB parameter is PB body temperature
For iH/iF/iL parameter is Not Used
Output bytes: None
Input bytes:Bytes 1 and 2 are a 16-bit signed number for PB temperature in °C.
The actual meaning and measurement location of this temperature measurement will vary between pump families
and pump types, even if a valid temperature reading is indicated by the condition byte.
For iXH parameter is PB end cover temperature
For pHMB parameter is PB motor temperature
For iH/iF/iL parameter is Not Used
Output bytes: None
Input bytes:Bytes 1 and 2 are a 16-bit signed number for PB temperature in °C.
Byte 3 is condition byte (see Section 4.6.4).
4.7.36Module 35 - Nitrogen Flow Rate
Requires gas module with this feature.
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number for Nitrogen flow rate in slm (Standard litres per
minute).
Byte 3 is condition byte (see Section 4.6.4).
4.7.37Module 68 - Active Utility Control
Active Utility Control is used to reduce pump speed (saving energy) and nitrogen flow, when the chamber is not
processing. The Drypump may need to be set up to operate in this mode. The Profibus module must have control of
the pump to turn AUC on or off. (See Section 4.7.3).
Output byte:Single byte is AUC control. Values: 1=On (speed and flow reduced); 2=Off (speed and flow normal);
Other values - ignored.
Note:Demand value is only sent from the Profibus module to the pump on change of state.
Input Bytes:Byte1 AUC state
Values: 0=Off (normal)
1=Off going On
2=On going off fast
3=On going off slow
4=On (reduced).
2nd input byte is condition byte (see Section 4.6.4).
4.7.38Module 39 - Exhaust Pressure
Requires gas module with this feature.
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit signed number for exhaust pressure in 0.1 kPa.
Byte 3 is condition byte (see Section 4.6.4).
4.7.39Module 56 - Exhaust Gas Temperature
Requires exhaust gas temperature sensor to be fitted.
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit signed number for exhaust gas temperature in °C.
Byte 3 is condition byte (see Section 4.6.4).
4.7.40Module 84 - Exhaust Pipe Temperature
Requires exhaust pipe temperature sensor to be fitted.
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit signed number for exhaust pipe temperature in °C.
Edwards and the Edwards logo are trademarks of Edwards Limited.
D397-52-880 Issue D
4.7.41Module 52 - Water Flow Rate
Requires water flow sensor to be fitted.
Output bytes: None
Input bytes:Bytes 1 and 2 form a 16-bit unsigned number for water flow rate in 0.1 l/min.
Byte 3 is condition byte (see Section 4.6.4).
4.7.42Module 161 - Gate Valve
This module provides gate valve control and demand status if a gate valve is fitted to the pump. It can be used to
turn off the valve, however, it can only turn on the valve if the Profibus module has control of the pump. (See
Section 4.7.3). Use this command with caution as if the Profibus module does not have control it may be possible to
turn off the valve but not turn it back on.
Output byte:Single byte is gate valve control.
Values: 1=On
2=Off
Other values - ignored.
Note:Demand value is only sent from the Profibus module to the pump on change of state.
Input bytes:Byte1 valve demand state
Values: 0=Off
1=Off going On
2=On going off fast
3=On going off slow
4=On.
2nd input byte is condition byte (see Section 4.6.4).
Operation
Note:If demand status is not the same as actual state, a warning will be raised in Module 992.
4.7.43Module 53 - Active Gauge
Requires active gauge to be fitted.
Output bytes: None
Input bytes:Bytes 1-4 are 32-bit IEEE754 format floating point value.
Byte 5 is units (59=Pascals, 66=volts).
Byte 6 is condition byte (see Section 4.6.4).
4.7.44Module 993 - Profibus Software Version
Output bytes: None
Input bytes:Input bytes are Profibus code version in ASCII
1st character is s/w type e.g. 0x50 = P (Production)
2nd character is revision letter e.g. 0x41 = A.
Edwards and the Edwards logo are trademarks of Edwards Limited.
D397-52-880 Issue D
6Storage and disposal
6.1Storage
Store the Profibus module in clean dry conditions until required. When required for us e, install the Profibus module
as described in Section 3.
6.2Disposal
Dispose of the Profibus module and any components safely in accordance with all local and national safety and
environmental requirements.
Alternatively, you may be able to recycle the Profibus module and/or cables; contact Edwards or your supplier for
advice (also see below).
The Profibus module and associated cables are within the scope of the European Directive on Waste Electrical and
Electronic Equipment, 2002/96/EC. Edwards offer European customers a recycling service for the Profibus module/
cables at the end of the product’s life. Edwards' Registration Number as a UK producer of electrical and electronic
products is WEE/BF0054TQ. Contact Edwards for advice on how to return the Profibus module/cables for recycling.
Edwards products, spares and accessories are available from Edwards companie s in Belgium, Brazil, Canada, France ,
Germany, Hong Kong, Italy, Japan, Korea, Switzerland, United Kingdom, U.S.A. and a world-wide network of
distributors. The majority of thes e centres employ Service Engineers w ho have undergone co mprehensive Edwa rds
training courses.
Order spare parts and accessories from your nearest Edwards company or distributor. When you order, please state
for each part required:
Model and Item Number of your equipment
Serial number (if any)
Item Number and description of the part.
7.2Accessories
CABLE LON/PDT POWER/RS232D397-52-016
5 WAY XLR EXTENSION CABLE 3MD373-70-591
5 WAY XLR EXTENSION CABLE 5MD373-70-592
5 WAY XLR EXTENSION CABLE 10MD373-70-595
5 WAY XLR EXTENSION CABLE 15MD373-70-596
5 WAY XLR EXTENSION CABLE 25MD373-70-597
PDT ADAPTOR, RJ12 PLUG/5 WAY XLR SOCKETD373-70-726