Eclipse 705 Installation And Operating Manual

®
Guided Wave Radar
Level Transmitter
Installation and Operating Manual
705
2
UNPACKING
Unpack the instrument carefully. Make sure all components h
ave been removed from the foam protection. Inspect all components for damage. Report any concealed damage to the carrier within 24 hours. Check the contents of the car­ton/crates against the packing slip and report any discrep­ancies to Magnetrol. Check the nameplate model number to be sure it agrees with the packing slip and purchase order. Check and record the serial number for future refer­ence when ordering parts. To avoid moisture ingress in the housing, covers should be fully tightened at all times. For t
he same reason, plugs should remain properly installed in
the cable entries until replaced with a cable gland.
SPECIAL CONDITIONS FOR ATEX INTRINSICALLY SAFE USE
These units are in conformity with the provisions of:
1.  The EMC Directive: 2014/30/EU. T
he units have been tested to EN
61326: 1997 + A1 + A2.
2.  Directive 2014/34/EU for Equipment or protective sys­tem for use in potentially explosive atmospheres. EC­t
ype examination certificate number KEMA99ATEX0518X (intrinsic safe units) or BKI 12 ATEX 0017 (Ex d units) or KEMA99ATEX5014 (Non sparking units).
3.  The PED directive 2014/68/EU (pressure equipment directive). Safety accessories per category IV module H1.
Amplifier nameplate:
-
partnumber
- amplifier
- serial n°
-
temperature/pressure
- approval data
Probe nameplate
- partnumber
-
serial number
0
038
0
344
Because the enclosure of the Guided Wave Radar Level Transmitter Eclipse Model 705-5xxx-x1x and 705-5xxx-x7x and/or Probe Eclipse Model 7xx-xxx-xxx is made of aluminium, if it is mounted in an area where the use of category 1G apparatus is required, it must be installed such, that, even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded.
For applications in explosive atmospheres caused by combustible dust, gases, vapours or mists and where category 1G or 1D apparatus is required, electrostatic charges on the non-metallic parts of the Probe Eclipse Model 7M5-xxx-xxx, Model 7M7-xxx­xxx and Model 7xF-xxx-xxx shall be avoided.
S
ize: 38 mm
(
1 1/2") or
a
djustable
w
rench
Customer supplied brackets are recommended per each 3 m length. (Required for WGH § 19 i
nstallations.)
Not important
min 25 mm (1")
from tank bottom
3
Overfill safe and Overfill proof
Eclipse 7MD/7ML, 7MR/7MM and 7MT/7MN coaxial GWR probes are “Overfill safe” in use and “Overfill proof” certified.
Overfill safe means that the unit is capable to measure up to the process connection.
Overfill proof protection (such as WHG or VLAREM) cer­tifies reliable operation when the transmitter is used as overfill alarm but assumes that the installation is designed in such way that the vessel/ cage cannot overfill.
Eclipse 7MQ/7MS has a transitioning zone (zone in which the unit does not measure accurately) at the top. Maximum level should not be higher than 25 mm (1") up to 200 mm (8") (depending dielectrics - see probe specifications) below the process connection. This may include utilizing a nozzle or spool piece.
Note: When using the 7MQ or 7MS probe, keep transmitter and probe matched as a set.
Metallic (or any conductive) obstructions in the tanks
Metallic obstructions have no influence on the measuring performance of coaxial GWR probes.
Turbulence
Customer supplied mounting brackets are recommended per each 3 m (10’) length and have no influence on the mea­suring performance of coaxial GWR probes.
Stillwell /cages
Coaxial GWR probes are ideally suited for use in stillwells or cages. There is no min. clearance allowance to be taken into consideration.
Shortening of probe length
Coaxial GWR probes can be easily shortened on site when a procedure for this is strictly followed. This procedure can be separately obtained from factory.
Size: 38 mm (1 1/2") or adjustable wrench
1/4" NPT plugged flushing connection
1
/4" NPT
p
lugged
ushing
c
onnection
Customer supplied brackets are recommended p
er each 3 m length. (Required for WGH § 19
installations.)
Not important
min 25 mm (1")
f
rom tank bottom
MOUNTING
C
oaxial type GWR probes
(7MD - 7MQ - 7MR - 7MS - 7MT)
Note: The flushing connection allows to purge the inside of
the coaxial probe without dismantling. Re-assure the use of compatible purging liquid/gas to avoid unwanted chemical reaction.
C
oaxial type GWR probes: Flushing connection
(7ML - 7MM - 7MN)
IMPORTANT:
To avoid damaging during transportation, Eclipse
®
7MD/7ML large coax probes are shipped with 3 transport screws, securing the inner antenna. The 3 screws have to be removed prior to installation. They are located nearby the process connection. A separate label is attached to draw the attention to remove the screws.
To avoid moisture ingress in the housing, covers should be fully tightened at all times. For the same reason, cable gland and plugs should be properly installed in the cable entries.
The unit is preconfigured from factory, based on given application details (when available). Therefore transmitter and GWR probe have the same serial n°.
Please make sure that corresponding serial numbers are mounted together.
4
MOUNTING
Overfill safe and Overfill proof
Eclipse twin rod GWR probes use software to ignore level readings in the transitioning zone at the top of the GWR probe. The maximum level is a minimum of 150 mm (6") below the process connection. This may include utilizing a nozzle or spool piece to raise the probe. Twin rod probes are overfill proof certified but not overfill safe in use.
Eclipse twin cable GWR probes, used in media with low dielectrics (hydrocarbons, powders) may require the setting of a blocking distance (zone in which the unit will not mea­sure) of 300 mm up to 500 mm (12" to 20") depending probe length. The longer the probe, the longer the blocking dis­tance will be. Eclipse twin cable GWR probes are not over­fill proof certified and not overfill safe in use.
Metallic (or any conductive) obstructions in the tanks
Objects in the proximity within 25 mm (1") or closer such as pipes, support beams, metal ladders etc… may cause erro­neous readings.
Turbulence
7MB: Customer supplied brackets are recommended per each 3 m (10') length and have no influence on the mea­suring performance of 7MB GWR probes. Use the “off cen­ter” rod to fasten the brackets (see above drawings).
7M5/7M7: It is recommended to secure the probe if signifi­cant turbulence exists. Optional weights are available to keep the probe taught. The probe should not make any con­tact with the metal tank wall. The 7M7 (liquids) probe can be attached to the bottom of the tank – it is not recommended to attach the 7M5 (solids) probe at the bottom of the tank.
Stillwell/cages
Min. 3" / DN 80 size nozzles, stillwells or by-pass cages are required for a good operation. Twin rod/cable probes should be min 25 mm (1") away from any metal tank wall. 7M5/7M7 have a 76 mm (3") inactive section. For nozzles < 3"/ DN 80, this section should be flush with the bottom of the nozzle or extend into the vessel.
IMPORTANT:
Twin rod/cable probes should be installed into a metal tank, stillwell or by-pass cage to meet CE requirements (EN 61326: 1997 + A1 + A2) electromagnetic compatibility.
Tank or cage wall
Off center rod
min 25
(1)
Size: 47 mm (1 7/8") or adjustable wrench
min. 25 mm (1")
from any metal
object
m
in 25 mm (1")
from tank bottom
Use half open brackets f
or twin rod probes.
Twin rod (7MB) / Twin cable (7M5 - 7M7) GWR probes
For twin cable: min 25 mm (1") from any metal object
M
ounting considerations for 7MB
Nozzle should be DN80 (3") diameter or larger.
Mounting considerations for 7M5/7M7
For nozzles < DN80 (3") diameter, the bottom of the inac­tive section of the probe should be flush with the bottom of the nozzle or extend into the vessel.
5
MOUNTING
1
3 mm Ø
(
0.50")
1
3
2
4
7M7/7M5 probe can be shortened in field.
a.raise the weight (1) to expose the two
securing devices (2)
b.loosen the two #10-32 set screws (3)
on both securing devices using a
2.5 mm (3/32") hex wrench and slide
the securing devices off of the probe c. slide the TFE weight off of the probe. d.cut and remove the required cable (4)
l
ength
e.remove 90 mm (3 1/2") of the rib
between the two cables f. strip 16 mm (5/8") of coating from the
two cables. g.slide the TFE weight back on to the
probe. h.enter new probe length (cm or inches)
in software (See page 12, Item 9)
Note: Probe can be attached to the tank b
ottom using the noose or the 13 mm Ø (0.50") hole provided in the TFE weight. 7M7 GWR probes: cable tension should not exceed 89 N 7M5 GWR probes: pull down force should not exceed 1360 kg (3000 lbs)
Twin rod (7MB) / Twin cable (7M5 - 7M7) GWR probes
Cage GWR probe (7MG)
Shortening of probe length
7MB probes can be shortened safely in the field. Make sure to re-install the bottom spacer for proper alignment and to adapt t
he probe length/ 4-20 mA settings in the menu.
Twin cable probes can be safely shortened in the field using below procedure. Make sure to adapt the probe length / 4-20 mA settings in the menu.
Vent
Drain
Customer or magnetrol supplied cage/bridle or still well.
Venting holes
Bottom spacer
Bottom spacer
For cage/still well: 2": Ø 13 mm (0.50") rod
For cage/still wells: 3": Ø 19 mm (0.75") tubing 4": Ø 25 mm (1.00") tubing
Overfill safe
All 7MG GWR probes are overfill safe. Overfill safe means that the impedance match of the waveguide (probe) is aligned from electronics down to the bottom of the GWR probe. This allows the Eclipse 705 to measure up to the pro­cess flange without any dead zone at the top of the GWR probe.
Metallic (or any conductive) obstructions in the tanks
Metallic obstructions have no influence on the measuring performance of cage GWR probes.
Stillwell/cages
The cage GWR probe is a single rod GWR probe which uses an existing or new cage, bridle or schedule pipe still­well to re-create the same propagation of signal of a coaxi­al GWR probe. Cage GWR probes are suited for 2", 3" or 4" size diam. and use an impedance matching part that aligns in the same way with the characteristic impedance of a standard coaxial style GWR probe.
Shortening of probe length
Cage GWR probes can be easily shortened on site. Always re-install the bottom spacer and adapt the new probe length in the menu of the amplifier.
6
MOUNTING
Single rod (7MF - 7MH - 7MJ) / Single cable (7M1 - 7M2) GWR probes
Size: 38 mm (1 1/2") or adjustable wrench
Size: 38 mm (1 1/2") or adjustable wrench
High Level shutdown and Overfill protection
Special consideration is necessary in any high level shut­down / overfill protection application where single rod GWR probes are used. To ensure proper measurement, the guid­ed wave radar probe should be installed so the maximum overfill level is at a minimum of 120 mm (4.8") up to 910 mm (36") – blocking distance depending application below the process connection. Consult factory for further information.
Metallic (or any conductive) obstructions in the tanks
Objects in the proximity of the probe may cause erroneous readings.
Turbulence
The bottom of the probe should be stabilized if turbulence will cause a deflection of more than 75 mm at 3 m (3" at 10') of length. Optional bottom spacers in TFE (for 7MF) or PEEK (for 7MJ) should be used to stabilize the probe, in case turbulence exists. It is recommended to secure the probe (7M1/7M2) if significant turbulence exists (see above drawing at right side). Optional weights are available to keep the probe taught. The 7M1 (liquids) probe can be attached to the bottom of the tank – it is not recommended to attach the 7M2 (solids) probe at the bottom of the tank. The probe should not make any contact with the metal tank wall.
Stillwell/cages
Max. 6” / DN 150 size stillwells or by-pass cages or a metal tank wall within 150 mm (6”) of the probe, will allow the unit to measure accurately in media with dielectrics down to
ε
r
1,9.
Nozzles do not restrict the performance by ensuring the fol­lowing:
1. Nozzle must be 50 mm (2") or larger diameter.
2. Nozzle inside diameter (A) should be ≥ to nozzle height (B). If this is not the case, it is recommended to adjust BLOCKING DISTANCE and/or SENSITIVITY settings.
IMPORTANT:
Single rod/cable probes should be installed into a metal tank, stillwell or by-pass cage to meet CE requirements (EN 61326: 1997 + A1 + A2) electromagnetic compatibility.
When used in a non-metallic vessel flange (metal) mounting is recommended for optimal performance.
Distance to probe
Acceptable objects
< 150 mm (6") Continuous, smooth, parallel,
conductive surface (e.g. metal tank wall);
probe should not touch
tank wall
> 150 mm (6") < 1"/DN25 diameter pipe and
beams, ladder rungs
> 300 mm (12") < 3"/DN80 diameter pipe and
beams, concrete walls
> 450 mm (18") All remaining objects
Pipe reducers
should not be used
Correct installation
A
B
7
MOUNTING
Shortening of probe length
Single rod/cable probes can be shortened safely in the field. Make sure to adapt the probe length/ 4-20 mA settings in the menu and the re-install of a bottom spacer when applicable.
Single cable probes can be safely shortened in the field using below procedure. Make sure to adapt the probe length/ 4-20 mA settings in the menu.
13 mm fl (0.50")
1
2
3
4
7M1/7M2 probe can be shortened in field.
a.raise TFE weight (1) exposing secur-
ing device (2)
b.loosen both #10-32 set screws (3)
using 2.5 mm (3/32") hex wrench and remove securing device
c. cut and remove needed cable length
(4)
d
.re-attach securing device (2) and
tighten screws
e.enter new probe length (cm or inch-
es) in software (See page 12, Item 9)
13 mm Ø (0.50")
Note: Probe can be attached to the tank
bottom using the noose or the 13 mm Ø (0.50") hole provided in the TFE weight. 7M1 GWR probes: cable tension should n
ot exceed 89 N (20 lbs). 7M2 GWR probes: pull down force should not exceed 1360 kg (3000 lbs)
Single rod (7MF - 7MH - 7MJ) / Single cable GWR probes
Overfill safe and Overfill proof
Eclipse 7EK GWR probes are “Overfill safe” in use and “Overfill proof” certified.
Overfill safe means that the unit is capable to measure up to the process connection. Units with “non overfill safe” probes use software to ignore level readings in the block­ing distance or transitioning zone. When level rises too high in this zone, the unit may consider the end of probe reflec­tion as the real level and may report an empty vessel instead of an overfilling vessel.
Overfill proof protection (such as WHG or VLAREM) cer­tifies reliable operation when the transmitter is used as overfill alarm but assumes that the installation is designed in such way that the vessel/cage cannot overfill.
The 7EK probe is designed to replace without modification top/bottom mounted displacer transmitters. The unit will measure over the entire probe length and indicate for
20.5 mA above the highest measurable point and 3.8 below the lowest measurable point.
Top/Bottom GWR probes (7EK)
1 1/2" or 2" socket weld or NPT
1
1/2" or 2"
F
langed
8
MOUNTING
Do not insulate the
high frequency connector
in case of high temperature
applications
Insulation
WRONG GOOD
M
ax +150 °C (+300 °F)
Max +100 °C (+212 °F) for Ex d unit
360° rotatable: Position for optimum wiring/viewing
Max. rotation 270°
Size: 38 mm (1 1/2") or adjustable wrench Recommended torque 60 Nm (45 ft-lbs)
Remove protection
Remove
protection
C
AUTION: be careful not to bend or dirty the gold, high frequency male connector (a) and its female connector (b). Clean with iso­propyl alcohol and cotton swabs, if necessary
(a)
(b)
Transmitter
Integral
Remote
9
WIRING
CAUTION: power must be switched OFF before wiring the unit.
–+
I
S
®
L
OOP
C
URRENT
IS
0 %
100 %
Positive supply to (+) terminal N
egative supply to (-) terminal
Shield wire to green grounding screw (resistance to ground must be < 1 Ω).
Standard shielded twisted pair cable recommended. Non shielded cable can be used per NAMUR NE 21 for field strenghts up to 10 V/m).
Use certified flameproof cable gland(s) and cable for Explosion proof area.
Current loop test point (HART
®
only)
ANALOG I/O
or
DIGITAL I/O
(only for units with HART)
Customer supplied local current meter
Do not connect shield
Ex
Non Ex
Ex
Non Ex
Ex
Non Ex
IMPORTANT:
The shield wire should only be grounded at ONE side only. It is recommended to connect the shield to ground in the field (at the transmitter side - as shown above) but connecting in the control room is also allowed.
LOOP RESISTANCE
1200
1000
800
600
400
200
0
0 10 20 30 40 Vdc
20,5 mA
24 Vdc
630
11
Ω
Galvanic Barrier (only needed for intrinsically safe units): HART
®
: max. 28,4 V DC @ 124 mA
Foundation Fieldbus™ / Profibus PA™: max. 17,5 V DC @ 380 mA
10
Display Action Comment
Units!
cm
Units
cm
Units!
cm
CONFIGURATION
NOTE: When connected to an approved barrier, the intrinsically safe electronics of the Eclipse allow to remove the covers with power switched on – even if the area is known to be hazardous
2 line – 8 characters LCD Default display cycles every 5 s through Status «STATUS» / Level
«
LEVEL» / % output «% OUTPUT» / Loop «LOOP».
Up/Down and Enter pushbuttons
IMPORTANT: The Eclipse amplifier can be bench configured without GWR probe connected. Ignore the start up message «No Level Signal» / «STA-
TUS» / «WeakSgnl» in this case.
Press :
The last character on the first line of the display changes to «!». This sign con­firms that the values/choices of the second line can be modified via the and push buttons.
Press
*
Scroll through the choices or increase/decrease the values on the second line of the display by and pushbuttons.
*
Accept values/choices as selected by pushbutton.
Press
Scroll through the menu.
PASSWORD
DISPLAY ACTION COMMENT
Ent Pass
0
New Pass
4096
Ent Pass!
1
NOTE: Password protection is activated when after 5 minutes no keystrokes are sensed.
Display shows «0»
Factory default setting Data is not protected
Press and last character changes into «!» Enter your personal password with and (any value between 1 and 255) Press to confirm
Setting password
Press and enter old password Press and last character changes into «!» Enter your new password with and (any value between 1 and 255) Press to confirm
Changing password
Display shows an encrypted value, enter your password or call Magnetrol for assistance to recoop your password if necessary
Data is protected by a valid Password
11
20 mA Level (100%-point)
Reference point
Probe Type
Probe
L
ength
Offset
Safety Zone
Inch or cm
Dielectric o
f medium
Blocking distance
4 mA Level (
0%-point)
TERMINOLOGY
BEFORE STARTING
Offset = cm or inches
The offset is the distance between reference point (e.g. bottom of tank) and end of probe. From the reference point both 4 mA and 20 mA levels are calibrated. When offset is set at zero, the end of the probe is the reference point.
4 mA Level = cm or inches
or zero level point, is measured from the reference point. The unit has a transition zone at the bottom of the probe. Min. level to enter for media with:
ε
r = 2.0: 150 mm (6") + Offset
ε
r = 80: 25 mm (1") + Offset
20 mA Level = cm or inches
or 100 % level point, is measured from the reference point. The unit has a transition zone at the top of the probe. Transition zone varies depending on probe type and media: see probe specifications page 34 and continuing.
P
robe length = cm or inches, record the exact probe length as
printed on the nameplate: 705-xxxx-xxx / 7Mx-xxx-xxx
Dielectric Select the dielectric scale of the media to measure: 1.4–
1.7 or 1.7–3 or 3–10 or 10–100. When the dielectric is known, it will enhance the overall accuracy of the unit but select the dielectric scale ALWAYS to the lowest expected dielectricum.
CONFIGURATION
Start from run mode:
1. Select the desired language for configuration: English, French, German or Spanish in the language screen (32) «language». Scroll up for quickly reaching the language selection screen.
2. Define type of measurement: a. Level only (pages 12 & 13) b. Level and Volume (pages 14 & 15) c. Interface only (pages 16 & 17) d. Interface and Volume (pages 18 & 19) Scroll down until the screen reads «MeasType». The unit will now show only the applicable screens for the selected type of measurement.
3. Scroll one screen down and select the applicable engineering unit in «LvlUnits», all configuration values will be entered in that engineering unit.
4. Move to the loop control screen «LoopCtrl», select the loop control in function of the type of measurement «MeasType» selected.
5. Refer to the configuration procedure of the selected type of measurement.
6. Refer to page 20 for all hidden diagnostic screens and advanced configuration parameters. These screens allow the advanced user to configure the unit for special applications or to troubleshoot the unit in the field. It is NOT recommended to access this toolset without proper guidance or having followed proper training.
No offset
(Offset at 0 cm)
Positive offset
(Offset at 10 cm)
Negative offset
(Offset at -15 cm)
75 cm
100 %
0 %
15 cm
10 cm
20 mA = 75 cm
4 mA = 15 cm
20 mA = 85 cm
4 mA = 25 cm
20 mA = 60 cm
4 mA = 0 cm
Safety zone: In addition to the blocking distance,
the user can introduce a safety zone to warn for liquid level entering this zone beneath the blocking distance. The loop signal will shift in this zone to a selectable fault signal. The unit will go to normal read out, when level drops lower than the safety zone, unless a latched fault signal is used. The safety zone is disabled from fac­tory. Safety zone related settings include: «SZ Fault»: to select the preferred error signal «SZ Height»: to define the safety zone area «SZ Alarm Reset»: to manually reset a latched «SZ Fault»
12
= Quick Start up
MENU: STEP BY STEP PROCEDURE – Eclipse 705: Level only
Screen Action Comment
Run modeConfiguration
1
2
3
4
7
10
12
13
16
17
*Status*
*
Level*
*%Output*
*Loop*
Level
xx.x
%Output
xx.x%
Loop
xx.xx mA
5
PrbModel (select)
MeasType (select)
6
PrbMount (select)
9
Probe Ln
xxx.x
8
LvlUnits (select)
Lvl Ofst
xxx.x
1
1
Dielctrc (Select)
Senstvty
xxx
Loop Ctrl
(Select)
14
Set 4mA
xxx.x
Damping
xx sec
15
Set 20mA
xxx.x
Fault
(Select)
T
ransmitter Display
T
ransmitter default values cycle every 5 seconds. Status «Status»,
L
evel «Level», % Output «% Output», and Loop «Loop».
T
ransmitter Display
T
ransmitter displays level value in selected engineering units.
Transmitter Display Transmitter displays % Output measurement derived from 20 mA
span.
T
ransmitter Display
T
ransmitter displays Loop measurement (mA).
Select the type of probe Select as per the 3 first digits of the probe partnumber. The partnumber
i
s shown on the nameplate: e.g. 705-510A-A11/7MT-A230-218, select
7
xT-x from the list.
S
elect the type of probe
m
ounting.
Select NPT «NPT», BSP «BSP» or Flange «Flange». (consult facto-
ry when a «7xK» GWR probe is used)
Select the type of measurement
Select level «Levl Only».
S
elect units for level
c
m «cm», m «m», inches «inches» or feet «feet».
E
nter the exact length of
p
robe.
E
nter as per the 3 last digits of the probe partnumber on the nameplate:
- rigid probes, enter value cm or inches,
-
flexible probes, enter value in meters or feet
e
.g. 705-510A-A11/7MR-A230-218, enter «218» cm probe length.
Enter the offset value. When entering configuration values from the end of the probe is
cumbersome, an offset can be introduced to determine a new reference point. This reference point can be either below the probe (positive offset) or at the probe (negative offset). See page 11 “Terminology”.
Enter the dielectric range value of the media
Select: «
1.4–1.7»; «1.7–3»; «3–10» or «10–100»
«1.7–3» is recommended for dielectrics ≥ 1,7
Enter sensitivity value Allows fine adjustment of internal gain.
Select primary variable (PV)
Primary variable is the loop controlling parameter. Select level
«Lvl only»
Enter the level value for the 4 mA point.
A transition zone may exist at the bottom of the probe. See Functional Specifications Probe, see page 34 and continuing.
Enter the level value for the 20 mA point.
A transition zone / blocking distance may exist at the top of the probe. See Functional Specifications Probe, see page 34 and continuing.
Enter the damping factor. A Damping factor (1-10 seconds) may be added to smooth a noisy
display and/or output due to turbulence.
Enter the value for error.
Select «3.6 mA», «22 mA» or hold last value «HOLD». In case of loop failure, error signal will follow the failing trend; meaning the unit will show 3.6 mA when the reviewed loop current by the device is found too low. The unit will show 22 mA in case the reviewed loop current is found too high.
13
MENU: STEP BY STEP PROCEDURE – Eclipse 705: Level only
Screen Action Comment
Diagnostics
23
2
6
27
28
29
30
Poll Adr
xx
Trim 4
xxxx
2
5
Trim Lvl
xx.x
2
4
Loop Mode
Trim 20
xxxx
Loop Tst
xx.x mA
LvlTicks
xxxxx
New Pass
xxx
31
32
Language
Mdl705HT
Ver xx.xx
33
DispFact (select)
18
19
20
2
1
22
BlockDis
xx.x
SZ Fault (select)
SZHeight
xx.x
SZ Alarm
Reset
Threshld (select)
E
nter distance in
selected level units
A
llows to ignore level measurements near the top of the probe, caused by e.g. condensation, crystalization. Make sure that the liquid level does NOT enter this zone. Consult factory or the ‘Troubleshooting’ section before entering any value. Normaly to be u
sed with single rod probe.
Select the safety zone fault.
Select «None» (None), «3.6mA», «22mA», «Latch 3.6mA» or «
Latch 22mA». When either «Latch 3.6 / 22mA» signals is
s
elected, the loop current remains in alarm until it is manually cleared
w
ith the «SZAlarm» screen ( for safety zone explanation see T
erminology - page 11).
S
elect the safety zone value
E
nter safety zone in cm or inches (see Terminology - page 11).
Reset safety zone latch fault
Clear a latched safety zone alarm «SZFault».
S
elect the type of threshold
«
Fixed» = the first reflection from the top will be considered as level
(
default setting)
«
CFD» = the strongest reflection from the top will be considered as
l
evel.
O
nly change to «CFD», in case the unit is reading incorrect level.
A
djustment of trim level «Trim Lvl» may be necessary when t
hreshold is changed.
Enter HART ID number. Select a HART poll address (0-15). Enter 0 for a single transmitter
installation.
E
nable/Disable
D
etermines whether the loop is fixed at 4.0 mA or controlled by the PV.
E
nter value
t
o adjust level reading.
A
llows to compensate for a fixed level deviation.
Fine tune the 4 mA point. Attach a mA meter to the output. If the output does not equal 4.0 mA,
adjust the value on the display to equal 4.00 mA.
Fine tune the 20 mA point. Attach a mA meter to the output. If the output does not equal
20.0 mA, adjust the value on the display to equal 20.00 mA.
Enter a mA output value. Set mA Output to any given value to perform loop test .
Diagnostic display. Shows time of flight from fiducial pulse to reflected signal from level.
Enter new password. Use arrows to select desired value. Values between 0 and 255.
Select language
Select «English», «Français», «Deutsch» or «Espagnol».
None, do not adjust.
Factory setting. «Ver» refers to software version.
Advanced diagnostics. See page 20.
No offset
(Offset at 0 cm)
Positive offset
(Offset at 10 cm)
Negative offset
(Offset at -15 cm)
75 cm
100 %
0 %
15 cm
10 cm
20 mA = 75 cm
4 mA = 15 cm
20 mA = 85 cm
4 mA = 25 cm
20 mA = 60 cm
4 mA = 0 cm
OFFSET
14
= Quick Start up
MENU: STEP BY STEP PROCEDURE – Eclipse 705: Level & Volume
Screen Action Comment
Run mode
Configuration
1
2
3
4
8
11
12
13
19
20
*Status* *
Volume*
*%Output*
*Loop*
Volume
xxx
%Output
xx.x%
Loop
xx.xx mA
5
Level
xxx
MeasType (select)
7
PrbMount (select)
6
PrbModel (select)
1
0
Probe Ln
xxx.x
9
LvlUnits (select)
Lvl Ofst
xxx.x
14
Dielctrc (Select)
VolUnits (select)
StrapTbl
xx pnts
17
Set 4mA
xxx.x
Damping
xx sec
18
Set 20mA
xxx.x
15
Senstvty
xxx
16
Loop Ctrl
(Select)
Fault
(Select)
T
ransmitter Display
T
ransmitter default values cycle every 5 seconds. Status «Status»,
V
olume «Volume», % Output «% Output», and Loop «Loop».
T
ransmitter Display
T
ransmitter displays Volume Value in selected engineering units.
Transmitter Display Transmitter displays % Output measurement derived from 20 mA
span.
T
ransmitter Display
T
ransmitter displays Loop measurement (mA).
Transmitter Display
Transmitter displays level in selected volume units «LvlUnits».
S
elect the type of probe
S
elect as per the 3 first digits of the probe partnumber. The partnumber
i
s shown on the nameplate: e.g. 705-510A-A11/7MT-A230-218, select
7xT-x from the list.
Select the type of probe mounting.
S
elect NPT «NPT», BSP «BSP» or Flange «Flange».
(consult facto-
ry when a «
7xK» GWR probe is used)
Select the type of measurement
Select level and volume «Lvl&Vol».
S
elect units for level
c
m «cm», m «m», inches «inches» or feet «feet».
Enter the exact length of probe.
Enter as per the 3 last digits of the probe partnumber on the nameplate:
- rigid probes, enter value cm or inches,
- flexible probes, enter value in meters or feet e
.g. 705-510A-A11/7MR-A230-218, enter «218» cm probe length.
Enter the offset value. When entering configuration values from the end of the probe is
cumbersome, an offset can be introduced to determine a new reference point. This reference point can be either below the probe (positive offset) or at the probe (negative offset). See page 11 “Terminology”.
Select units for volume
Liters «l» or gallons «g».
Enter level/volume pairs in max 20 steps
Liters «l» or gallons «g».
Enter the dielectric range value of the media
Select: «
1.4–1.7»; «1.7–3»; «3–10» or «10–100»
«1.7–3» is recommended for dielectrics ≥ 1,7
Enter sensitivity value Allows fine adjustment of internal gain.
Select primary variable (PV)
Primary variable is the loop controlling parameter. Select level
«Lvl only» or volume «volume»
Enter the level value for the 4 mA point.
A transition zone may exist at the bottom of the probe. See Functional Specifications Probe, see page 34 and continuing.
Enter the level value for the 20 mA point.
A transition zone / blocking distance may exist at the top of the probe. See Functional Specifications Probe, see page 34 and continuing.
Enter the damping factor. A damping factor (1-10 seconds) may be added to smooth a noisy
display and/or output due to turbulence.
Enter the value for error.
Select «3.6 mA», «22 mA» or hold last value «HOLD». In case of loop failure, error signal will follow the failing trend; meaning the unit will show 3.6 mA when the reviewed loop current by the device is found too low. The unit will show 22 mA in case the reviewed loop current is found too high.
15
MENU: STEP BY STEP PROCEDURE – Eclipse 705: Level & Volume
Screen Action Comment
Advanced configurationDiagnostics
26
29
30
31
32
33
Poll Adr
xx
Trim 4
xxxx
28
Trim Lvl
xx.x
27
Loop Mode
Trim 20
xxxx
Loop Tst
xx.x mA
LvlTicks
xxxxx
New Pass
xxx
34
35
Language
Mdl705HT
Ver xx.xx
21
22
23
2
4
25
BlockDis
x.x
SZ Fault (select)
SZHeight
xx.x
SZ Alarm
Reset
Threshld (select)
E
nter distance in
selected level units
A
llows to ignore level measurements near the top of the probe, caused by e.g. condensation, crystalization. Make sure that the liquid level does NOT enter this zone. Consult factory or the ‘Troubleshooting’ section before entering any value. Normaly to be u
sed with single rod probe.
Select the safety zone fault.
Select «None» (None), «3.6mA», «22mA», «Latch 3.6mA» or «
Latch 22mA». When either «Latch 3.6 / 22mA» signals is
s
elected, the loop current remains in alarm until it is manually reset
w
ith the «SZAlarm» reset screen ( for safety zone explanation see T
erminology - page 11).
S
elect the safety zone value
E
nter safety zone in cm or inches (see Terminology - page 11).
Reset safety zone latch fault
Select «Reset» «No» or «Yes» to reset alam when either «Latch
3.6mA» or «Latch 22mA» was selected in «SZFault».
S
elect the type of threshold
«
Fixed» = the first reflection from the top will be considered as level
(
default setting)
«
CFD» = the strongest reflection from the top will be considered as
l
evel.
O
nly change to «CFD», in case the unit is reading incorrect level.
A
djustment of trim level «Trim Lvl» may be necessary when t
hreshold is changed.
Enter HART ID number. Select a HART poll address (0-15). Enter 0 for a single transmitter
i
nstallation.
E
nable/Disable
D
etermines whether the loop is fixed at 4.0 mA or controlled by the PV.
E
nter value
t
o adjust level reading.
A
llows to compensate for a fixed level deviation.
Fine tune the 4 mA point. Attach a mA meter to the output. If the output does not equal 4.0 mA,
adjust the value on the display to equal 4.00 mA.
Fine tune the 20 mA point. Attach a mA meter to the output. If the output does not equal
20.0 mA, adjust the value on the display to equal 20.00 mA.
Enter a mA output value. Set mA Output to any given value to perform loop test.
Diagnostic display. Shows time of flight from fiducial pulse to reflected signal from level.
Enter new password. Use arrows to select desired value. Values between 0 and 255.
Select language
Select «English», «Français», «Deutsch» or «Espagnol».
None, do not adjust.
Factory setting. «Ver» refers to software version.
Advanced diagnostics. See page 20.
Strapping table
max. Pt 20 Lvl = ...... cm
Pt 4 Lvl = 200 cm Pt 3 Lvl = 120 cm Pt 2 Lvl =   50 cm Pt 1 Lvl =     0 cm
max. Pt 20 Vol = ...... l
Pt 4 Vol = 3000 l Pt 3 Vol = 2000 l Pt 2 Vol = 1000 l Pt 1 Vol =       0 l
36
DispFact (select)
NOTE: Consult page 13 for level offset «Lvl Ofst» details.
16
= Quick Start up
MENU: STEP BY STEP PROCEDURE – Eclipse 705: Interface
Screen Action Comment
Run mode
Configuration
1
2
3
4
8
1
1
12
15
18
19
*Status*
*
IfcLevel*
*%Output*
*Loop*
IfcLevel
xx.x
%Output
xx.x%
Loop
xx.xx mA
5
Level
xxx
MeasType (select)
7
PrbMount (select)
6
PrbModel (select)
1
0
Probe Ln
xxx.x
9
LvlUnits (select)
Lvl Ofst
xxx.x
13
Dielctrc (Select)
14
Senstvty
xxx
Upr Diel (Select)
Loop Ctrl
(Select)
16
Set 4mA
xxx.x
Damping
xx sec
17
Set 20mA
xxx.x
Fault
(Select)
T
ransmitter Display
T
ransmitter default values cycle every 5 seconds. Status «Status»,
I
nterface level «Ifclevel», % Output «% Output», and Loop
«
Loop».
T
ransmitter Display
T
ransmitter displays interface level in selected engineering units.
Transmitter Display Transmitter displays % Output measurement derived from 20 mA
span.
T
ransmitter Display
T
ransmitter displays Loop measurement (mA).
Transmitter Display
Transmitter displays interface level in selected level units «LvlUnits».
S
elect the type of probe
S
elect as per the 3 first digits of the probe partnumber. The partnumber is shown on the nameplate: e.g. 705-510A-A11/7MT-A230-218, select 7xT-x from the list.
S
elect the type of probe
m
ounting.
Select NPT «NPT», BSP «BSP» or Flange «Flange». (consult facto-
ry when a «
7xK» GWR probe is used)
Select the type of measurement
Select interface «Interface».
Select units for level
cm «cm», m «m», inches «inches» or feet «feet».
E
nter the exact length of
probe.
E
nter as per the 3 last digits of the probe partnumber on the nameplate:
-
rigid probes, enter value cm or inches,
-
flexible probes, enter value in meters or feet
e.g. 705-510A-A11/7MR-A230-218, enter «218» cm probe length.
Enter the offset value. When entering configuration values from the end of the probe is
cumbersome, an offset can be introduced to determine a new reference point. This reference point can be either below the probe (positive offset) or at the probe (negative offset). See page 11 “Terminology”.
Enter the dielectric range value of the upper media.
Enter the dielectrics of the upper layer liquid (between 1,4 and 5,0) – only upper layer dielectrics need to be entered.
Select the dielectric range value of the lower media
Select: «
10–100»
Enter sensitivity value
Allows fine adjustment of internal gain.
Select primary variable (PV)
Primary variable is the loop controlling parameter. Select inter­face level «Ifc Level» or top level «Lvl Only»
Enter the level value for the 4 mA point.
A transition zone may exist at the bottom of the probe. See Functional Specifications Probe, see page 34 and continuing.
Enter the level value for the 20 mA point.
A transition zone / blocking distance may exist at the top of the probe. See Functional Specifications Probe, see page 34 and continuing.
Enter the damping factor. A damping factor (1-10 seconds) may be added to smooth a noisy
display and/or output due to turbulence.
Enter the value for error.
Select «3.6 mA», «22 mA» or hold last value «HOLD». In case of loop failure, error signal will follow the failing trend; meaning the unit will show 3.6 mA when the reviewed loop current by the device is found too low. The unit will show 22 mA in case the reviewed loop current is found too high.
17
MENU: STEP BY STEP PROCEDURE – Eclipse 705: Interface
Screen Action Comment
26
25
3
0
31
32
35
Poll Adr
xx
IfcThrs
(select)
2
4
Threshld
Trim 20
xxxx
Loop Tst
xx.x mA
28
29
Trim Lvl
xx.x
2
7
Loop Mode
Trim 4
xxxx
LvlTicks
xxxxx
New Pass
xxx
36
37
Language
Mdl705HT
Ver xx.xx
33
34
IfcTicks
xxxx
Medium
20
21
22
2
3
BlockDis
x.x
SZ Fault (select)
SZHeight
xx.x
SZ Alarm
Reset
E
nter distance in
selected level units
A
llows to ignore level measurements near the top of the probe, caused by e.g. condensation, crystalization. Make sure that the liquid level does NOT enter this zone. Consult factory or the ‘Troubleshooting’ section before entering any value. Normaly to be u
sed with single rod probe.
Select the safety zone fault.
Select «None» (None), «3.6mA», «22mA», «Latch 3.6mA» or «
Latch 22mA». When either «Latch 3.6 / 22mA» signals is
s
elected, the loop current remains in alarm until it is manually reset
w
ith the «SZAlarm» reset screen ( for safety zone explanation see T
erminology - page 11).
S
elect the safety zone value
E
nter safety zone in cm or inches (see Terminology - page 11).
Reset safety zone latch fault
Clear a latched safety zone alarm «SZFault».
S
elect top level threshold.
D
efault selection for most common applications is «Fixed».
S
elect interface threshold.
D
efault selection for all applications is «CFD». In case the unit does not track the correct interface layer, select «Fixed».
Enter HART ID number. Select a HART poll address (0-15). Enter 0 for a single transmitter
installation.
E
nable/Disable
D
etermines whether the loop is fixed at 4.0 mA or controlled by the P
V.
Enter value to adjust level reading.
Allows to compensate for a fixed level deviation.
Fine tune the 4 mA point. Attach a mA meter to the output. If the output does not equal 4.0 mA,
adjust the value on the display to equal 4.00 mA.
Fine tune the 20 mA point. Attach a mA meter to the output. If the output does not equal
20.0 mA, adjust the value on the display to equal 20.00 mA.
Enter a mA output value. Set mA Output to any given value to perform loop test .
Diagnostic display. Shows time of flight from fiducial pulse to reflected signal from level.
Diagnostic display. Shows time of flight through the upper liquid layer.
Diagnostic display.
Shows type of detected upper liquid; unknown «Unknown» oil only «Oil Only», thin oil layer «Thin Oil», thick oil layer «Thick Oil», or no level «Dry Probe».
Enter new password. Use arrows to select desired value. Values between 0 and 255.
Select language
Select «English», «Français», «Deutsch» or «Espagnol».
None, do not adjust.
Factory setting. «Ver» refers to software version.
Advanced diagnostics. See page 20.
38
DispFact (select)
No offset
(Offset at 0 cm)
Positive offset
(Offset at 10 cm)
Negative offset
(Offset at -15 cm)
75 cm
100 %
0 %
15 cm
10 cm
20 mA = 75 cm
4 mA = 15 cm
20 mA = 85 cm
4 mA = 25 cm
20 mA = 60 cm
4 mA = 0 cm
OFFSET
Advanced configuration
Diagnostics
Loading...
+ 39 hidden pages