Eclipse 5600 No Purge, 5600 Modulation, 5600 Purge Installation Manual

Installation Guide 818
1/15/2015
Eclipse Veri-Flame Single
Burner Monitoring System
Model 5600
Modulation Model
Purge ModelNo Purge Model
Copyright 2008 by Eclipse, inc. All rights reserved worldwide. This publication is protected by federal regulation and shall not be copied, distributed, transmitted, transcribed or translated into any human or computer language, in any form or by any means, to any third parties, without the express written consent of Eclipse, inc.
Disclaimer Notice
In accordance with the manufacturer’s policy of continual product improvement, the product presented in this brochure is subject to change without notice or obligation.
The material in this manual is believed adequate for the intended use of the product. If the product is used for purposes other than those specified herein, confirmation of validity and suitability must be obtained. Eclipse warrants that the product itself does not infringe upon any United States patents. No further warranty is expressed or implied.
Liability & Warranty
We have made every effort to make this manual as accurate and complete as possible. Should you find errors or omissions, please bring them to our attention so that we may correct them. In this way we hope to improve our product documentation for the benefit of our customers. Please send your corrections and comments to our Technical Documentation Specialist.
It must be understood that Eclipse’s liability for its product, whether due to breach of warranty, negligence, strict liability, or otherwise is limited to the furnishing of replacement parts and Eclipse will not be liable for any other injury, loss, damage or expenses, whether direct or consequential, including but not limited to loss of use,
income, or damage to material arising in connection with the sale, installation, use of, inability to use, or the repair or replacement of Eclipse’s products.
Any operation expressly prohibited in this manual, any adjustment, or assembly procedures not recommended or authorized in these instructions shall void the warranty.
Document Conventions
There are several special symbols in this document. You must know their meaning and importance.
The explanation of these symbols follows below. Please read it thoroughly.
How To Get Help
If you need help, contact your local Eclipse representative. You can also contact Eclipse at:
1665 Elmwood Rd. Rockford, Illinois 61103 U.S.A. Phone: 815-877-3031 Fax: 815-877-3336 http://www.eclipsenet.com
Please have the information on the product label available when contacting the factory so we may better serve you.
www.eclipsenet.com
Product Name Item # S/N DD MMM YYYY
This is the safety alert symbol. It is used to alert you to potential personal injurt hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
CAUTION
NOTICE
NOTE
2
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Is used to address practices not related to personal injury.
Indicates an important part of text. Read thoroughly.
Table of Contents
Introduction...................................................................................................5
Product Description ..................................................................................5
Audience ..................................................................................................5
Veri-Flame Documents.............................................................................4
Safety .............................................................................................................5
Safety Warnings .......................................................................................5
Capabilities...............................................................................................5
Operator Training .....................................................................................5
Replacement Parts...................................................................................5
DIP Switch Selection ....................................................................................6
Introduction...............................................................................................6
Handling & Storage ..................................................................................6
Approvals of Components ........................................................................6
DIP Switch Location .................................................................................7
DIP Switch Access ...................................................................................7
No Purge DIP Switch Settings..................................................................7
Modulation and Purge DIP Switch Settings..............................................7
Function Summary .......................................................................................9
Introduction...............................................................................................9
Standard Features....................................................................................9
Optional Features.....................................................................................11
System Installation .......................................................................................12
Introduction...............................................................................................12
Interlocks and Limit Switch Input..............................................................12
Combustion Air Switch Input ....................................................................12
Ignition Wiring...........................................................................................12
Low Fire Input...........................................................................................12
Main Valve Closed Switch........................................................................12
High Purge Input ......................................................................................13
Remote Reset ..........................................................................................13
Remote Display and Power Supply..........................................................13
Sensor Installation........................................................................................18
Introduction...............................................................................................18
Sensor Wiring...........................................................................................18
Flame Rods ..............................................................................................18
Scanners ..................................................................................................19
Scanner Sighting Considerations .............................................................19
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015 3
Test Procedures............................................................................................20
Introduction...............................................................................................20
Flame Signal Strength..............................................................................20
Minimum Pilot Test...................................................................................20
Pilot Flame Failure Test ...........................................................................20
Main Flame Failure Test (For Interrupted Pilot Systems).........................20
Spark Sighting Test ..................................................................................20
Limits and Interlocks Test.........................................................................21
Maintenance and Troubleshooting .............................................................22
Introduction...............................................................................................22
Monthly Checklist .....................................................................................22
Yearly Checklist........................................................................................22
Troubleshooting........................................................................................23
LED Status ...............................................................................................24
Remote Display Messages...........................................................................27
Introduction...............................................................................................27
Veri-Flame Operating Sequence..............................................................27
Remote Display Diagnostic Messages.....................................................31
Appendix .......................................................................................................i
4
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
Introduction
Product Description
The Eclipse Veri-Flame Single Burner Monitoring System controls the start-up sequence and monitors the flame of single gas, oil, or combination gas/oil burners. There are three different models of the Veri-Flame line: no purge, purge and modulation models. Each model features field selectable trial for ignition (TFI). Each model is also available for use with three types of flame sensor: ultraviolet (UV), self-check UV and flame rod
Required components are the Veri-Flame, matching wiring base and a flame sensor. Optional components include a remote display and cable, tester, and various scanner accessories.
The Veri-Flame No Purge and Purge models are available in three different series - 5602, 5603 and 5605. The 5602 Series is UL listed for the USA and Canada and FM approved; the 5605 Series is UL listed and FM approved. The 5603 Series is for 240 VAC applications and is FM approved.
1
Figure 1.1 Veri-Flame Single Burner Monitoring
System (Purge Unit Shown)
The Veri-Flame Modulation model is available in two different series: 5602 and 5603. Both series are capable of modulation (high purging and low fire start). The 5602 Series is UL recognized for the USA and Canada and FM approved. The 5603 Series is for 240 VAC and is FM approved.
Audience
This manual has been written for people who are already familiar with all aspects of a nozzle-mix burner and its add­on components, also referred to as “the burner system”.
These aspects are:
• Design / Selection
• Use
• Maintenance
The audience is expected to have previous experience with this type of equipment.
Veri-Flame Documents
Installation Guide 818
• This document
Datasheet 818
• Required to complete design and selection
Spare Parts List Series 818
• Recommended replacement part information
Related Documents
• EFE 825 (Combustion Engineering Guide)
• Eclipse Bulletins and Info Guides: 684, 710, 732, 756, 760, 902, 930
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015 5
Safety
Important notices which help provide safe burner operation will be found in this section. To avoid personal injury and damage to the property or facility, the following warnings must be observed. All involved personnel should read this entire manual carefully before attempting to start or operate this system. If any part of the information in this manual is not understood, contact Eclipse before continuing.
Safety Warnings
DANGER
The burners, described herein, are designed to mix fuel with air and burn the resulting mixture. All fuel burning devices are capable of producing fires and explosions if improperly applied, installed, adjusted, controlled or maintained.
Do not bypass any safety feature; fire or explosion could result.
Never try to light a burner if it shows signs of damage or malfunction.
WARNING
The burner and duct sections are likely to have HOT surfaces. Always wear the appropriate protective equipment when approaching the burner.
2
NOTICE
This manual provides information regarding the use of these burners for their specific design purpose. Do not deviate from any instructions or application limits described herein without written approval from Eclipse.
Capabilities
Only qualified personnel, with sufficient mechanical aptitude and experience with combustion equipment, should adjust, maintain or troubleshoot any mechanical or electrical part of this system. Contact Eclipse for any needed commissioning assistance.
Operator Training
The best safety precaution is an alert and trained operator. Train new operators thoroughly and have them demonstrate an adequate understanding of the equipment and its operation. A regular retraining schedule should be administered to ensure operators maintain a high degree of proficiency. Contact Eclipse for any needed site-specific training.
Replacement Parts
Order replacement parts from Eclipse only. All Eclipse approved valves or switches should carry UL, FM, CSA, CGA and/or CE approval where applicable.
Eclipse products are designed to minimize the use of materials that contain crystalline silica. Examples of these chemicals are: respirable crystalline silica from bricks, cement or other masonry products and respirable refractory ceramic fibers from insulating blankets, boards, or gaskets. Despite these efforts, dust created by sanding, sawing, grinding, cutting and other construction activities could release crystalline silica. Crystalline silica is known to cause cancer, and health risks from the exposure to these chemicals vary depending on the frequency and length of exposure to these chemicals. To reduce the risk, limit exposure to these chemicals, work in a well-ventilated area and wear approved personal protective safety equipment for these chemicals.
6
DIP Switch Selection
3
Introduction
This section describes the location, selection and description of the Veri-Flame DIP switches, which allow for sequence and timing functions as well as system configuration.
Handling & Storage
Handling
• Make sure that the area is clean.
• Protect the components from the weather, damage, dirt and moisture.
• Protect the components from excessive temperatures and humidity.
• Take care not to drop or damage components.
Storage
• Make sure that the components are clean and free of damage.
• Store the components in a cool, clean, dry room.
• After you have made sure that everything is present and in good condition, keep the components in the original package as long as possible.
Approval of Components
Gas Piping
All the gas piping must comply with all applicable local codes and/or standards such as:
• NFPA Standard 54
• ANSI Z223
• EN 746-2
Where to Get the Standards:
The NFPA Standards are available from:
National Fire Protection Agency Batterymarch Park Quincy, MA 02269 www.nfpa.org
The ANSI Standards are available from:
American National Standard Institute 1430 Broadway New York, NY 10018 www.ansi.org
The UL Standards are available from:
333 Pfingsten Road Northbrook, IL 60062 www.ul.com
Limit Controls & Safety Equipment
All limit controls and safety equipment must comply with all applicable local codes and/or standards and must be listed for combustion safety by an independent testing agency. Typical application examples include:
• American: NFPA 86 with listing marks from UL, FM, CSA
• European: EN 746-2 with CE mark from TuV, Gastec, Advantica
Electrical Wiring
All the electrical wiring must comply with all applicable local codes and/or standards such as:
• NFPA Standard 70
• IEC60364
• CSA C22
• BS7671
The FM Standards are available from:
1151 Boston-Providence Turnpike PO Box 9102 Norwood, MA 02062 www.fmglobal.com/approvals
Information on the EN standards and where to get them is available from:
Comité Européen de Normalisation
Stassartstraat 36
B-1050 Brussels Phone: +32-25196811
Fax: +32-25196819
www.cen.eu
Comité Européen de Normalisation Electronique
Stassartstraat 36
B-1050 Brussels Phone: +32-25196871
Fax: +32-25196919
www.cenelec.org
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015 7
CAUTION
SW2: Pilot selection (On = Intermittent, where pilot remains on during burner cycle; Off = Interrupted, where pilot valve closes after main burner is established).
To avoid electric shock, shut off the power supply when installing or removing any control device. Flame monitoring systems must be installed by a qualified, licensed technician.
DIP Switch Location
All of the DIP switches are located in the back of each Veri-Flame unit (see Figure 3.1 on page 11, or the photograph on page 7).
DIP Switch Access
To gain access to the DIP switches, the Veri-Flame must be separated from the back box (for visual reference, please refer to “Dimensions” on page 9). This separation will expose the DIP switches on the back of the Veri­Flame unit.
No Purge DIP Switch Settings
No Purge models of the Veri-Flame only use three of the eight DIP switches, as shown in the labels in Figure 3.2 on page 11. They are as follows:
SW1: Recycling mode selection (On = Recycling; Off = Non-recycling)
SW3: Trial-for-ignition (TFI) range selection (For 5602/ 5603 units: On = 10 seconds; Off = 5 seconds. For 5605 units: On = 10 seconds; Off = 15 seconds).
Modulation and Purge DIP Switch Settings
Modulation and purge models of the Veri-Flame use all of the eight DIP switches, as illustrated in Figure 3.2 on page
11. They are as follows:
SW1: Recycling mode selection (On = Recycling; Off = Non-recycling)
SW2: Pilot selection (On = Intermittent, where pilot remains on during burner cycle; Off = Interrupted, where pilot valve closes after main burner is established).
SW3: Trial-for-ignition (TFI) range selection (For 5602/ 5603 units: On = 10 seconds; Off = 5 seconds. For 5605 units: On = 10 seconds; Off = 15 seconds).
SW4 through 7: Purge time selection. Total purge time is the sum of each switch selected. If all are set off, the trial for ignition starts when the air switch input comes on.
SW8: Post purge selection. (On = 15 second post purge).
Close-up of DIP switches on
back side of all Veri-Flame models.
Figure 3.1. DIP Switch Location
8
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
No Purge Models
c us
Purge Models Modulation Models
c us
c us
Figure 3.2. DIP Switch Labels with Selections
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
9
Function Summary
4
Introduction
This section describes the features of the Veri-Flame. It is divided into three categories: standard features, optional features and the LED indicator lights on the front cover. Refer to Figure 5.5 for sequence diagrams.
Standard Features
The following function features are standard on the Veri­Flame models as noted:
Interlocks and Limit Switch Input (Terminal 7)
This input is considered the normal operation control or run input to the Veri-Flame system. Interlocks are generally pressure or temperature switches which, when activated, start the burner. Limit switches are generally pressure, temperature and other switches which, when activated, stop the burner. The interlocks and limit switches are wired in series. A break in this circuit will shut the burner down, but will not produce an alarm.
Combustion Air Switch Input (Terminal 6)
For purge and modulation models: This input is for monitoring the combustion air switch separately from other interlocks and limits. The Veri-Flame checks the air flow switch input is open before start-up, closed during operation, and open again at burner shutdown, thus preventing operation with an air switch that is defective, maladjusted or jumped. This input has about a 2 second delay to filter out and ignore a momentary interruption.
The input will be proven open before start-up and after shutdown.
If the input is improperly powered before the fan output is energized, the system error light will blink. The input must de-energize within 30 seconds or the Veri-Flame will lockout.
After the fan output has energized, the air switch input must be made within 10 seconds. If not proven, then the system will lockout, the alarm output and the air failure light will come on. However, if the unit has the optional air switch input hold feature, the sequence is held indefinitely without causing a lockout. When the air switch input is made, then the sequence continues.
Main Fuel Valve Closed Switch (Terminal V)
For purge and no-purge models: The Veri-Flame can be interlocked with the main valve closed switch. This feature checks the switch position before start-up and after shutdown to insure proper valve operation when the jumper on the base is cut.
Low Fire Start
For modulation models: When wired, the system checks for the low fire start position prior to light-off.
Main Fuel Valve Closed / High Fire Purge Check (Terminal D)
For modulation models: This feature is enabled when the jumper on the base is cut. The system checks that the high fire position switch and the main valve closed switch are both made at the end of the high fire purge.
Recycle Mode
Test Mode
(Button In)
For all models: When selected, the Veri-Flame will restart the sequence after flame or air failure. The recycle mode allows the system to re-initiate the start-up sequence automatically provided the main burner has been operating for at least 35 seconds. If the pilot flame fails to light during recycling, the system will lock out and annunciate a pilot flame fail. If the recycle is successful and the main burner is operational for at least 35 seconds, the system is ready for another recycle. At no time will the system recycle in the event of pilot flame fail.
Run Mode
(Button Out)
If the air switch opens during the main firing cycle, the system will either lockout or recycle, depending on the DIP switch recycle selection.
10
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
Pilot Test Mode
For all models: This mode is entered by depressing the TEST/RESET button on the front cover. In the pilot test mode, the Veri-Flame will hold the sequence once the pilot flame is established (i.e., the main valve is not energized). When in the pilot test mode, the green “Interlocks Closed” light blinks.
To exit the pilot test mode, push the TEST/RESET button three times (the green “Interlocks Closed” light stops blinking but remains lit) and the Veri-Flame will restart the sequence.
Interrupted or Intermittent Pilot
For all models: Pilot mode is selected using the DIP switch SW2. An interrupted pilot shuts off 10 seconds after the main valve opens. An intermittent pilot continues during the entire main flame firing cycle.
Post Purge
For purge and modulation models: Post purge is enabled by DIP switch SW8. A post purge maintains the combustion air fan output for 15 seconds after the interlocks and limit switch input have opened.
Spark, Pilot, Flame and Main Flame Separation
For all models: During the trial for ignition period (TFI), the pilot valve and ignition coil remains energized. If a flame signal is present at the end of the TFI, the pilot output remains on and the ignition coil is de-energized. After a five second delay to prove the pilot flame, the main gas valve is energized.
System Errors and Lockout Conditions
A system error (illuminated by the red “System Error” LED
on the front cover) prevents gas ignition. The unit will continue its sequence after the error is cleared. A lockout condition energizes the alarm output and de-energizes the gas valve and ignition outputs. The unit must be reset to clear the alarm and start the sequence. To reset, the button must be pressed twice so that the button is in the out position.
The following system errors result in immediate lockout conditions:
5. High fire fail (for modulating model)–high fire switch is not closed at the end of high fire purge.
6. Air failure (for purge and modulation models) – loss of combustion air anytime during the operational cycle. The Air Failure LED will be on for this condition. (See “Recycle Mode” on page 13.)
7. Pilot flame fail (for all models) loss of flame during the trial for pilot ignition period. The Flame Failure LED will be on for this condition.
8. Main flame fail (for all models) loss of flame during the main burner trial for ignition or run period (recycling not selected). The Flame Failure LED will be on for this condition.
The following result in lockout conditions after 30 seconds, the system error light blinks about 14 times and then remains on:
9. If a flame is detected out of sequence, which may be caused by:
a. A faulty scanner (for all models)
b. Electrical interference on the sensor wiring (for
all models)
c. A flame exists in the burner or in the line of sight
of a scanner, due to a gas leak, product fire or other conditions (for all models)
10. Air flow switch closed before start-up (for purge and modulation models).
High to Low Fire Purge Modulation Capability with High to Low Fire Position Switch Interlocks
For modulation models: The modulation feature incorporates a high fire purge time and a low fire purge time into the purge sequence. This feature allows the Veri­Flame to sequence internal dry contacts which can be used by the customer requiring a high fire purge of the combustion chamber before ignition.
The high fire and low fire purge times are selectable by means of DIP switches (see Section 3, “DIP Switch Settings” on page 10):
SW4 15 seconds SW6 60 seconds SW5 30 seconds SW7 120 seconds
1. Wiring error which puts external voltage on the output terminals (for all models).
2. Welded internal contacts or other malfunctions in the Veri-Flame (for all models).
3. Main fuel valve (for all models)–open after cycle shut down or before start-up. The system error light blinks twice and then remains on. The fan output terminal 8 will energize.
4. Low fire fail (for modulating model)–low fire switch open prior to trial for ignition.
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
The selected times are additive and apply to both the high fire and low fire purge times (that is, high and low fire times are always identical).
11
The modulation terminals will sequence as follows:
Sequence Step Internal Contact Connections
Power Off Terminal 10 (Common) Terminal 12 (Low Fire)
Power On, Limits Open Terminal 10 (Common) Terminal 12 (Low Fire)
Purge to High Fire Terminal 10 (Common) Terminal 13 (High Fire)
Purge to Low Fire Terminal 10 (Common) Terminal 12 (Low Fire)
Automatic Modulation Terminal 10 (Common) Terminal 11 (Auto)
Alarm & Lockout Terminal 10 (Common) Terminal 12 (Low Fire)
The purge to high fire sequence does not start until the air switch input is on. The Automatic step occurs when the burners are operating and allows the burner firing rate to be controlled by an automatic temperature controller.
Optional Features
The following features are available on select models, or when optional equipment is purchased.
Air Switch Input Hold
For purge models: Holds the sequence indefinitely until air switch input is confirmed without affecting the air failure function and causing a lockout.
Remote Display and Power Supply
The model 5602DBP operates on 120 VAC and has a keypad for reset function. The display is door panel mounted and features a liquid crystal display in a 1/4 DIN housing. The unit connects to the Veri-Flame by a cable to the flame signal test jack, and receives a serial communication on each sequence state change. The display incorporates the following functions:
1. Provides status messages for the Veri-Flame sequence (see section 9).
2. Indicates lockout conditions when they occur, as well as the amount of time into the sequence when the lockout occurred (see section 9).
3. Provides continuous monitoring of the burner’s flame signal strength and run time during main burner operation.
Status Lights and Pushbutton
All of the status lights and the TEST/RESET push-button are located on the front cover of the Veri-Flame. This section describes their respective functions.
• Air Failure
For purge and modulation models: This red LED illuminates whenever combustion air is lost during the operational cycle of the Veri-Flame.
• System Error
For all models: This red LED illuminates when a system error is detected (see “System Errors & Lockout Conditions” on pages 13).
• Flame Failure
For all models: This red LED illuminates when a pilot or main flame fails.
• Low Fire
For modulation models: This yellow LED illuminates during the low fire period of the purge cycle.
• High Fire
For modulation models: This red LED illuminates during the high fire period of the purge cycle.
• Auto
For modulation models: This green LED illuminates during the automatic period which occurs 20 seconds after the main valve is energized.
• Test/Reset
For all models: This push-button is used to activate the pilot test mode or to reset the Veri-Flame unit.
• Flame Signal
For all models: This red LED is located behind the signal test port and illuminates when a flame signal is present.
• Interlocks Closed
For all models: This green LED illuminates when the operation limits are made. These limits are wired in series to terminal 7. This input becomes energized to begin the burner sequence. When in the test mode, this LED blinks (see “Pilot Test Mode” on page 13).
12
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
r
r
System Installation
5
Introduction
This section describes the necessary procedures to integrate a Veri-Flame into a burner system. Figures 5.1 and 5.2 illustrate the various terminal strips mentioned.
NOTE: Shut off the power supply before the Veri-Flame is removed or replaced from the base.
CAUTION
Installation and maintenance must conform with the National Electrical Code and all other national and local codes and authorities having jurisdiction. Flame monitoring systems must be installed by a qualified licensed technician.
Interlocks and Limit Switch Input
Wire external interlock, control, and limit switches in series to this input. Guard against induced voltage levels to wiring connected to this input. In some extreme wiring runs, reduction of induced voltages may require a load (relay or light) connected to terminal 7 to avoid system error lockouts. This input is the power source for the valve and ignition output terminals. Be sure all switches wired to this input can handle the current required by the total of all loads connected to terminals 3, 4, and 5.
Combustion Air Switch Input
To Fan Ouput
Terminal
For purge and modulation models: Wire any switches and contacts in series to this terminal for proving air flow function and relating to the air failure light. Power must not be immediately present at terminal 6 when power is first applied to terminals 1 or 7.
If this terminal is not used, place a jumper between the combustion blower output (terminal 8) and the air switch input (terminal 6).
If the combustion air blower is controlled outside of the Veri-Flame system, then a three way solenoid valve must be connected between the air switch port and the blower sensing port. The valve de-energized state should vent the switch to ambient pressure. The energized state then connects the air switch to the blower sensing port. Power the valve from the blower output terminal 8. If accepted by local codes, the air switch could be wired between the combustion blower output and the air switch input. Connecting the air switch in this manner will satisfy the open contact (air short) check on the switch.
Ignition Wiring
Route ignition wiring a sufficient distance from all sensors and other low voltage wiring to avoid electrical interference, which may cause erratic operation of the Veri-Flame system. Keep the high voltage wire run from the ignition transformer as short as possible. The best condition is to mount the ignition transformer close to the burner and keep a low impedance path from the burner ground to the case of the transformer. Make sure the high voltage lead and ground return paths do not create a loop antenna around the Veri-Flame and sensor wiring.
Low Fire Input
FAN
To Burne
3-Way Solenoid Valve
De-energized
To Fan Ouput
Terminal
FAN
3-Way Solenoid Valve
Energized
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015 13
Air
Switch
Closed
To Burne
For modulation models: It is possible to wire the system for checking low fire start position prior to pilot ignition. To use this feature, the low fire start switch must be connected between terminal 3 and the pilot valve (see Figure 5.2). On direct spark burners, a by-pass contact must be wired around the low fire switch, see relay and contact CR in Figure 5.3.
Main Valve Closed Switch
The system can be wired to check for the main valve closed switch on the main gas valve prior to start-up and after the end of the burner cycle.
For purge and no purge models: The main valve closed switch must be connected to Terminal V and the jumper in the base must be cut (see Figure 5.4).
For modulation models: The main valve closed switch must be wired in series between the air flow switch and the high purge damper switch (see Figure 5.1). To use this feature, the jumper in the base must be cut.
High Purge Input
For modulation models: The system can be wired to check for high purge position during the high fire purge portion of the sequence. To use this feature, the red jumper in the base must be cut and the high purge position switch must be connected from terminal 6 to D. If this feature is not used, the jumper in the base remains intact or a jumper must be installed between terminals 1 and D. Please note that the yellow jumper on the base has no effect whether cut or intact.
Remote Reset
This feature permits remote mounting of a switch to reset the Veri-Flame. To use this feature, a normally closed remote reset switch must be wired so power is interrupted to terminal 1. When it is depressed or actuated, the connection to terminal 1 is momentarily interrupted and resets the Veri-Flame.
Remote Display and Power Supply
Wire the display according to Figure 5.3. Mount through a 1/4 DIN cutout using the two supplied brackets in either the top and bottom or the side slots. Locate the display and wiring to minimize electrical interference. Applying and disconnecting the display power supply should coincide with power to terminal 1 of the Veri-Flame. Use
the appropriate cable (Eclipse part number 20318) to connect to the test jack and to the S2 terminal of the Veri­Flame wiring base. Do not attempt to parallel the test jack signal to other devices when using a remote display. The LCD display contrast can be adjusted on the back with a small blade screwdriver.
NOTE: Power for terminal 7 of the Veri-Flame must not flow through the R1-R2 contact of the remote display when load currents exceed 5 amps.
Notes for Figures 5.1, 5.2 and 5.3 below:
1. Ground, shielding and conduit must not be connected to terminal S2.
2. Control circuit wires must meet 90°C (194°F) specification minimum and must be number 16 AWG or larger and in accordance with all applicable codes.
3. Flame sensor wires must be individually run in their own separate conduit; flame sensor wires CANNOT be run together in a common conduit or wireway (See Section 6).
4. Flame signal should read between 4 and 10 VDC with a digital volt meter. Drop off is approximately
4.0 VDC. Positive test jack point is on the cover marked “Flame Signal” with negative point being the S2 or ground.
5. Purge time, TFI, intermittent/interrupted pilot, and recycle/non-recycle selections are made with a DIP switch located on the rear plate of the control unit.
6. Neutral must be grounded.
14
15 A
Fuse
On/Off
Interlocks & Limits
No Purge Models Purge Models
5602/5605:
120 VAC
50/60 HZ
Proof of Closure
240 VAC 50/60 HZ
1
Piloted Burner
2
3
4
5
7
A
V
S1
S2
5603:
Pilot
Ignition
Main
Alarm
15 A Fuse
5602/5605:
120 VAC
50/60 HZ
On/Off
Air Flow Switch
Interlocks
& Limits
Proof of Closure
S1
S2
Figure 5.1. No Purge and Purge Wiring Diagram
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
5603:
240 VAC 50/60 HZ
1
2
3
4
5
6
7
8
A
V
Piloted Burner
Pilot
Ignition
Main
Fan
Alarm
5602/5605:
120 VAC 50/60 HZ
5603: 240 VAC 50/60 HZ
15 A. Fuse
Air Flow
To Activate Terminal D.
Interlocks
& Limits
Proof of Closure
On/Off
Cut Red
Jumper
High Purge
Damper
Switch
1
2
3
4
5
6
7
8
A
D
S2
S1
10
11
12
13
G
Flame Sensor Terminals
Common
Automatic
Low Fire
High Fire
Low Fire Proving
Pilot
Ignition
Main
Fan
Alarm
See the
chart below
for contact
connections.
Figure 5.2. Modulation Wiring Diagram
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
15
Self Check UV 5602-91
(Requires 5602-91-7 cable)
Model 5602 DBP
120 VAC Remote Display
2 1
S1
S2
A
B C
D
Self-Check UV 5602-91
(Requires 5602-91-7 cable)
for 240 VAC Veri-Flame
2 1
S1
S2
T1
Third party transformer required. Must be at least 25 VA.
T1
240V
120V
A B C
D
No Purge & Purge
Direct Spark
3
4
IGNITION
S1
Blue (Signal)
S2
Yellow (Neutral)
UV
UV
Scanner
5
NOTE:
Intermittent pilot must be selected, DIP-SW2 = ON
12V
MAIN
12V
Tx Rx
-
+
Cable
#20318
NOTE:
Power for terminal 7 must not flow through the R1-R2 contact when load currents exceed 5 amps.
120V
120V
N
to 120 VAC
L
R1 R2
G
PLUG
To 1
Flame Signal Test Jack
To S2
Veri-Flame
Flame Rod
S1
Blue
Flame Rod
S2
Modulation
Direct Spark with
Low Fire Start
Neutral
Low Fire Proving
3
CR
4
5
NOTE:
Intermittent pilot must be selected, DIP-SW2 = ON CR is a control relay used to bypass the low fire switch after the burner is lit.
CR
MAIN
IGNITION
Neutral
16
Figure 5.3. Typical Connections for All Models
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
Model Number 5602-10P Model Number 5602-10-1P
P3
3
6
2 1 1
3 2 1
4
6
4
P3
P2
P1
Jumper
P2
5
6 S2 S1
7
8
P1
3 4
Jumper
V 2 1 A
Internal Diagram
Purge & No-purge
P1 P1
5
P1
P3
P3
P2
6
3
J1
Fan
Alarm
Fault
P1
Pilot
P3
Ign
P3
Main
P3
Supervisor
1
7
V
6
2
1
8
2
A
4
6
3
4
5
3
5
Model Number 5602-40
3
2
1
1
3 2
1
Gnd
12345678AD 11121310S2 S1
6
P3
4
P2
6
P1
4
Jumper
5
6S2S17 8 A 1 2 V 4 3
Modulating Base
1
1
J2J1
S2
P2
1
S1
NOTE: No-purge models do not use 6 & 8.
Flame Signal
Amplifier
Jack
Internal Diagram
Modulation Model
P1 P1
5
1
6
Alarm
Fault
P1
3
7
22K
22K
D
P3
6
2
P2
2
2
S2
P2
1
S1
J2
10
4
Fan
P3
4
Flame Signal
1 2
Red
P1
4
Pilot
P3
6
Ign
P3
5
Main
P3
3
Supervisor
Amplifier
J2
2
J2
1
J2
3
Auto
Low
High
8
A
3
4
5
Jack
11
12
13
Figure 5.4. Purge and No Purge Base
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
17
Outputs
Inputs
Terminal
1
3
4
5
7
V
Function
Control Power
Pilot Valve
Ignition
Main Valve
Interlocks
POVC
Start
TFI
Pilot Trial
Flame Check
Pilot Off (Interrupted)
35 Seconds
Main
Trial
10 Sec
Recycle
Permitted
Firing Cycle
Pilot Off
(Intermittent)
End
Outputs
Inputs
Outputs
Inputs
Continuity
Between
Modulation
Terminals
Terminal
1
3
4
5
8
6
7
V
Terminal
1
3
4
5
8
6
7
D
3
10 to 12
10 to 13
10 to 11
Function
Control Power
Pilot Valve
Ignition
Main Valve
Fan
Air Switch
Interlocks
POVC
Function
Control Power
Pilot Valve
Ignition
Main Valve
Fan
Air Switch
Interlocks
High Fire & POVC
Low Fire Switch
Low Fire Purge
High Fire Purge
Automatic
Start
10
Sec
Start
10
Sec
Air Proven
Purge
Air Proven
High Fire
Purge
TFI
Pilot Trial
Flame
Check
5 Sec
Low Fire
Purge
35 Seconds
Main
Trial
10 Sec
Pilot Off (Interrupted)
Recycle
Permitted
Firing Cycle
Flame Check
TFI
5 Sec
Pilot Trial
Pilot Off
(Intermittent)
Post
Purge
15 Sec
Main
Trial
10 Sec
20 Seconds
35 Seconds
End
Pilot Off (Interrupted)
Firing Cycle
Recycle
Permitted
Pilot Off
End
(Intermittent)
Post
Purge
15 Sec
18
Figure 5.5. Sequence Diagrams
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
Sensor Installation
6
Introduction
This section describes the proper wiring, installation and sighting considerations for all sensors that can be used with a Veri-Flame.
WARNING
Incorrect sensor installation may cause the sensor to generate a false flame signal, possibly resulting in the collection of unburned fuel in the combustion chamber. This unburned fuel creates the potential for explosions which can result in injuries, death and property damage. Be certain that the flame sensor detects acceptable pilot and main flames only.
Sensor Wiring
Route sensor wiring a sufficient distance from ignition and other high voltage or high current wiring to avoid electrical interference. Interference from ground currents, nearby conductors, radio-frequency emitters (wireless devices), and inverter drives can induce false flame signals. Shielded cables can help reduce interference with the shield connected to ground at the control end only. The wire type and its capacitance (picofarads or microfarads) to ground may cause low signal problems, so a grounded shield may decrease the signal due to the cable’s internal capacitance. Multiple UV tube-type sensor leads run together without shielding may interfere or “cross talk”, so the shield or flexible armor must be grounded to prevent this situation. For flame rod sensor running approximately 30 meters (100 feet) or greater, use Eclipse part number 21741 coax cable. To achieve the maximum wiring distance, the shield should not be grounded (keep in mind that an ungrounded shield provides less protection against electrical interference).
NOTE: Unshielded sensor wiring must not be run in common with other wires; it must be run in separate conduit. Multiple unshielded flame sensor wiring must not be run together for long lengths in a common conduit or wireway. Use number 14 to number 18 AWG wire suitable for 90°C (194°F) and 600 volt insulation, or a better grade if required by the application. Multiple shielded flame sensor cables can be run in a common conduit.
Flame Rods
WRONG
Rod Detects
Weak Pilot
PILOT
Figure 6.1. Flamerod Position
Flame rods should be used only on gas burners. They accumulate soot from oil burners, causing nuisance shutdowns and unsafe operating conditions.
See the burner manufacturer’s literature for flamerod mounting location. When installing flame rods, please consider the following:
1. Keep the flamerod as short as possible and at least 13 mm (1/2 inch) away from any refractory.
2. Position the rod into the side of both the pilot and main flames, preferably at a descending angle to minimize drooping of the flamerod against burner parts, see Figure 6.1. Flamerod position must adequately detect the pilot flame at all burner draft conditions. Extend the rod 13 mm (1/2 inch) into non-luminous flames, such as blue flames from burning an air/gas mixture. For partially luminous flames, such as atmospheric air/gas mixtures, place the rod at the edge of the flame.
3. Provide a burner/flame grounding area that is at least four times greater than the flamerod area contacting the flame. The flamerod/burner ground ratio and position of the rod in the flame may need adjustment to yield maximum flame signal strength.
4. Ignition interference from the spark plug may increase or decrease the flame signal strength. Reversing the ignition transformer primary leads may reduce this effect. Changing the spark gap or adding grounding area between the flamerod and spark plug may eliminate the interference.
CORRECT
Rod Detects
Only Strong
Pilot Flame
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015 19
WARNING
Use only Eclipse scanner models as listed in the Illustrated Parts List at the end of this document.
Scanners
When installing scanners, please consider the following:
1. Position the scanner within 457 mm (18 inches) of the flame. Consult factory for longer distances.
2. Bushing threads are 1/2" FNPT for all scanner models except 5602-91 which has 1" FNPT bushing threads.
3. The ambient temperature limits of each scanner varies; check the literature for the specific scanner model. For higher temperatures, use Eclipse heat block seal 23 HBS for 1/2" NPT. scanners and if necessary, add cooling purge air.
4. An optional magnifying lens may also be used to increase the flame signal strength in difficult sighting situations.
Scanner Sighting Considerations
MAIN
BURNER
Scanner
Sight
Line
SCANNER
1/3 of
Flame Length
Figure 6.2.
Aim scanners at the third of the flame closest to the burner nozzle, see Figure 6.2 (oil flames typically have less UV radiation in the outer flame). The scanner should view the intersection of the pilot and main flames. When sighting scanners, please consider the following:
1. If possible, sight the scanner away from the ignition spark. Sighting the spark or its reflections from burner internals may lead to a misdiagnosis of shutdowns during burner ignition. If necessary, use a scanner orifice to reduce spark pickup.
2. Do not allow the scanner to detect a pilot flame that is too small to ignite the main burner.
3. Perform a minimum pilot test when installing or adjusting any pilot or main burner system; see “Minimum Pilot Test”.
20
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
Test Procedures
7
Introduction
This section describes the test procedures that must be performed after installation to insure that the Veri-Flame is operating properly; these procedures are mandatory.
Flame Signal Strength
Insert the positive probe of a 0-15 VDC, digital volt meter into the test point on the front cover of the Veri-Flame; connect the negative probe to S2 or ground. A good flame signal strength will read between 6 and 11 VDC; anything below 4 VDC is inadequate. Also, the red LED inside the test point illuminates when a flame signal is indicated.
Minimum Pilot Test
Run the following test procedures to ensure that the sensor will not detect a pilot flame too small to reliably light the main flame:
1. Manually shut off the fuel supply to the burner, but not to the pilot.
2. Start the system normally.
3. To enter the pilot test mode, depress the test/reset button located in the lower right corner on the front cover.
4. The control will hold the operating sequence at the pilot flame step. Measure signal strength as described above.
5. Reduce pilot fuel until the flame relay drops out. Increase pilot fuel until the flame signal is greater than 4 VDC, and flame relay just manages to pull in. This is the minimum pilot. If you don’t think this flame will be able to safely light the main burner, realign the sensor so that it requires a larger pilot flame and repeat steps 2 through 5.
6. Push the test/reset button located in the lower right corner on the front cover to exit the test mode (reset) and begin the normal start-up sequence again.
7. When the sequence reaches the main flame trial for ignition, smoothly restore the fuel supply to the burner. If the main burner does not light within five seconds, immediately shut off the burner supply to shut down the system. Realign the sensor so that it requires a larger pilot flame. Repeat steps 1 through 6 until the main burner lights off smoothly and reliably.
Pilot Flame Failure Test
1. Manually shut off the fuel supply to the pilot and the main burner.
2. Place system in pilot test mode (please refer to page 13).
3. Start the system normally. The controller should lock out*; if it doesn’t, then the controller is detecting a false flame signal (see Section 6). Find the problem and correct it before resuming normal operation.
Main Flame Failure Test (For Interrupted Pilot Systems)
1. Manually shut off the fuel supply to the main burner but not to the pilot.
2. Start the system normally. This should ignite the pilot and lock out* after pilot interruption. If the system does not lock out, the controller is detecting a false flame signal (see Section 6). Find the problem and correct it before resuming normal operation.
Spark Sighting Test
1. Manually shut off the fuel supply to the pilot and the main burner.
2. Start the system normally.
3. Measure the flame signal as described in “Flame Signal Strength” in this section.
4. If a flame signal greater than 4 VDC is measured for more than three seconds during the trial for ignition, then the sensor is picking up a signal from the spark plug; see “Sensor Wiring”. It is not necessary to correct a spark sighting condition for a Veri-Flame when the ignition transformer is connected to terminal 4.
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015 21
Limits and Interlocks Test
Periodically check all interlock and limit switches by manually tripping them during burner operation to make sure they cause the system to shut down.
WARNING
Never operate a system that is improperly adjusted or has faulty interlocks or limit switches. Always replace faulty equipment with new equipment before resuming operation. Operating a system with defective safety equipment can cause explosions, injuries, and property damage.
*Indicated by the illuminated red “Flame Failure” LED on the Veri-Flame front cover.
22
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
Maintenance and Troubleshooting
8
Introduction
This section is divided into two parts. The first part describes the maintenance procedures, and the second part helps you to identify problems that may occur and gives recommendations on how to solve these problems.
Preventative maintenance is the key to a reliable, safe and efficient system. The following are suggested guidelines for periodic maintenance. Burners in severe environments or operational conditions should be checked more frequently.
NOTE: The monthly and yearly lists are an average interval. If your environment is dirty, then the intervals may be shorter. Check with local authorities having jurisdiction on their recommended maintenance schedules.
CAUTION
Turn off the power to the burner and controls before proceeding with burner inspection.
Monthly Checklist
1. Inspect flame-sensing devices for good condition and cleanliness. Keep scanner lenses clean with a soft, damp cloth, since small amounts of dust will measurably reduce the flame signal strength. Wash the flamerod electrode and insulator with soap and water, then rinse and dry thoroughly.
2. Test all the alarm systems for proper signals.
3. Check ignition spark electrodes and check proper gap.
4. Test interlock sequence of all safety equipment as described on page 25: manually make each interlock fail, noting what related equipment closes or stops as specified by the manufacturer.
5. Test flame safeguard by manually shutting off gas to the burner.
Yearly Checklist
1. Test (leak test) safety shut-off valves for tightness of closure.
2. Test pressure switch settings by checking switch movements against pressure setting and comparing with actual impulse pressure.
3. Visually check ignition cable and connectors.
4. Make sure that the following components are not damaged or distorted:
• the burner nozzle
• the spark plugs
• the flame sensors
• the flame tube or combustion block of the burner
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015 23
Troubleshooting
Problem Possible Cause Solution
Cannot initiate a start sequence
Scrambled messages on the remote display
"Unsafe Air Short" message appears on the display
Burner flame fails but no flame failure indication occurs
Voltage reading is greater than 15 VDC at "Test Point" on Veri-Flame faceplate
Main valve is not closed
Check the main valve closed switch. No voltage on V (or D)
Check the air pressure switch adjustment
Check the air filter
Air pressure switch has not made contact
Check the blower rotation
Check the outlet pressure from the blower.
No voltage on 6 after 8 is on
Check the incoming gas pressure; adjust the gas pressure if necessary
High pressure gas switch has tripped
Check the pressure switch setting and operation
No voltage to 7
Check the incoming gas pressure; adjust the gas pressure if necessary
Low gas pressure switch has tripped
Check the pressure switch setting and operation
No voltage to 7
Malfunction of the flame safeguard system
such as a short-out flame sensor or
Have a qualified electrician troubleshoot and correct the problem
electrical noise in the sensor line
Purge cycle not completed
Main power is off
No power to the control unit
Check the switch setting
Check the air switch
Make sure the power to the control system is on
Have a qualified electrician troubleshoot and correct the problem
Check the grounding in the system.
Electrical interference
Separate the communication cable. Move the ignition circuit.
Improperly adjusted air switch Check the air switch settings
Air switch either shorted or it is wired
Check the wiring to the air switch
incorrectly
A faulty scanner
Improperly connected sensor wires
Electrical interference from other current
carrying wires
Check the scanner as explained in the "Maintenance" section above
Check the wiring diagram in the "System Installation" chapter of this manual
See Figures 5.1, 5.2, 5.3 and their associated notes in the "System Installation" chapter of this manual
Check grounding of neutral at the control
Improper grounding
power transformer
24
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
LED Status
This section describes the status of operating conditions based on the LED or combination of LEDs which are lit on the front cover of each Veri-Flame model.
LED Status and Conditions for Veri-Flame No Purge Models
LED(s) Lit Possible Cause
Interlocks Closed The interlocks are closed (normal operation), power on terminal 7. System Error 1. The flame detected is out of sequence, flame signal light is on.
2. The sensor is “runaway,” flame signal light is on.
3. Inductance is detected on sensor wires, flame signal light is on.
4. Voltage wired into terminals 3, 4, or 5.
5. Internal relay contacts welded.
6. Internal controller failure.
7. Main valve closed switch defective, no power to V.
Flame Failure 1. Pilot flame is not established in selected TFI.
2. Main flame is not established in selected TFI.
3. Main flame fails within 35 seconds of TFI.
4. Flame failed during operation in non-recycle mode.
5. Flame failed 35 seconds after TFI and was not established after try in recycle mode.
No Purge Model
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
25
LED Status and Conditions for Veri-Flame Purge Models
LED(s) Lit Possible Cause
Interlocks Closed The interlocks are closed (normal operation), power on terminal 7. System Error 1. The flame detected is out of sequence, flame signal light is on.
2. The sensor is “runaway”, flame signal light is on.
3. Inductance is detected on sensor wires, flame signal light is on.
4. Voltage wired into terminals 3, 4 or 5.
5. Internal relay contacts welded.
6. Internal controller failure.
7. Air flow switch closed before start-up.
8. Main fuel valve switch opens after shutdown or before start-up, no power to V.
Flame Failure 1. Pilot flame is not established in selected TFI.
2. Main flame is not established in selected TFI.
3. Main flame fails within 35 seconds of TFI.
4. Flame failed during operation in non-recycle mode.
5. Flame failed 35 seconds after TFI and was not established after one try in recycle mode.
Air Failure 1. Air flow switch not closed within ten seconds of start-up.
2. Air flow switch is open during timing cycle.
3. Air flow switch is open during firing cycle.
26
Purge Model
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
LED Status and Conditions for Veri-Flame Modulation Models
LED(s) Lit Possible Cause
Interlocks Closed The interlocks are closed (normal operation), power on terminal 7. System Error 1. The flame detected is out of sequence, flame signal light is on.
2. The sensor is “runaway”, flame signal light is on.
3. Inductance is detected on sensor wires, flame signal light is on.
4. Voltage wired into terminals 3, 4 or 5.
5. Internal relay contacts welded.
6. Internal controller failure.
7. Air flow switch closed before start-up.
8. Main fuel valve switch opens after shutdown or before start-up, no power to V.
Flame Failure 1. Pilot flame is not established in selected TFI.
2. Main flame is not established in selected TFI.
3. Main flame fails within 35 seconds of TFI.
4. Flame failed during operation in non-recycle mode.
5. Flame failed 35 seconds after TFI and was not established after one try in recycle mode.
Air Failure 1. Air flow switch not closed within ten seconds of start-up.
2. Air flow switch is open during timing cycle.
3. Air flow switch is open during firing cycle.
Interlocks Closed and Auto
Interlocks Closed and High Fire
Interlocks Closed and Low Fire
Burner in run mode, firing rate determined by automatic controller (normal operation).
Purge high sequence (normal operation).
Purge low sequence (normal operation).
Modulation Model
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
27
Remote Display
9
Messages
Introduction
This section describes how the optional remote display is used with the Veri-Flame. The remote display provides LCD messages which monitor the status of the Veri-Flame’s functions as well as any lockout conditions. This section is divided into two parts or tables:
Veri-Flame Operating Sequence
This section describes the start-up and shutdown monitoring sequences of the Veri-Flame and how the progress (or halt) of the sequence can be monitored by the messages on the remote display.
POWER ON
REMOTE DISPLAY
NORMAL MESSAGE
REVISION X.X
ERROR MESSAGE #1
UNSAFE FLAME ON
Fan is energized. If signal is eliminated within 30 seconds, sequence continues. If not, then . . .
ERROR MESSAGE #2 – 30 SECONDS AFTER #1
UNSAFE FLAME ON XX:XX:XX LOCKOUT
Alarm energized.
FOR PURGE & MODULATING
UNSAFE AIR SHORT
If switch is opened within 30 seconds, sequence continues. If not, then . . .
ERROR MESSAGE #2 – 30 SECONDS AFTER #1
UNSAFE AIR SHORT XX:XX:XX LOCKOUT
SAFE START OK Check_Sum = XX
FAN ENERGIZED
Was internal safe start check successful?
YES NO
EXTERNAL INTERLOCK CHECKS
Is ame signal present?
YES NO
Is voltage present at air ow switch?
ERROR MESSAGE #1
Alarm energized.
NORMAL MESSAGE
NORMAL MESSAGE
YES NO
Is voltage present at interlock switch?
YES NO
LIMITS OPEN TIME = XXXX:XX:XX
Holds until answer is yes.
Various lockout messages
Is main valve closed switch made?*
YES NO
ERROR MESSAGE
MAIN VALVE FAIL XX:XX:XX LOCKOUT
ERROR MESSAGE
28
Fan output is energized; modulator is sent to low re.
BURNER START-UP
(see next page)
* Applies to purge and no purge models only.
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
BURNER START-UP
Is voltage present at air flow switch
within ten seconds?
NO PURGE MODELS
PURGE MODELS
NORMAL MESSAGE
AIR PROVEN
Purge based on selected time.
NORMAL MESSAGE
PILOT TRIAL FOR IGNITION
Spark and pilot valve energized for selected trial for ignition.
Is voltage present at air switch . . .
YES NO
ERROR MESSAGE
AIR NOT PROVEN XX:XX:XX LOCKOUT
MODULATION MODELS
NORMAL MESSAGE
AIR PROVEN
NORMAL MESSAGE
PURGE TO HIGH FIRE
Modulator sent to high fire for selected purge time.
NORMAL MESSAGE
PURGE TO LOW FIRE
Modulator sent to low fire for selected purge time.
Is voltage present at air switch . . .
YES NO
ERROR MESSAGE
AIR NOT PROVEN XX:XX:XX LOCKOUT
Is voltage present
at high purge switch?
YES NO
ERROR MESSAGE
HI DAMPER FAIL XX:XX:XX LOCKOUT
Is low fire switch closed?
YES NO
ERROR MESSAGE
LOW FIRE FAIL XX:XX:XX LOCKOUT
NORMAL MESSAGE
PILOT FLAME ON
Flame signal detected
NORMAL MESSAGE
PILOT FLAME XX.XV TIME = XXXX:XX:XX
Spark turns off at end of TFI; sequence delayed 5 seconds.
Is flame signal present?
YES NO
Is flame signal present?
PILOT FLAME FAIL
ERROR MESSAGE
XX:XX:XX LOCKOUT
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
29
BURNER START-UP (continued)
Is ame signal present?
YES
NORMAL MESSAGE
MAIN FLAME ON
NO
MAIN FLAME FAIL
ERROR MESSAGE
XX:XX:XX LOCKOUT
NORMAL MESSAGE
MAIN FLAME ON PILOT OFF
Pilot will shut o 10 seconds after main ame is energized.
MODULATION MODELS
PURGE & NO PURGE MODELS
IF Interrupted Pilot is selected IF Intermittent Pilot Is Selected
NORMAL MESSAGE
AUTOMATIC MODULATION
Modulator sent to automatic 20 seconds after main valve is energized.
NORMAL MESSAGE
MODULATION MODELS
BURNER ON XX.XV TIME = XXXX:XX:XX
PURGE & NO PURGE MODELS
Main ame of burner is proven. Flame signal = XX.XVolts DC; elapsed time is shown in hours: minutes:seconds.
Is ame signal present?
YES
NO
NORMAL MESSAGE
MAIN FLAME ON
Was the main ame on more than 35 seconds?
YES
NO
ERROR MESSAGE
AIR FAILURE RECYCLING
Unit returns to beginning sequence.
Is air switch signal on?
YES
NO
Is recycle selected?
YES
NO
AIR FAILURE XX:XX:XX LOCKOUT
ERROR MESSAGE
Was the main ame on more than 35 seconds?
YES
NO
ERROR MESSAGE
MAIN FLAME FAIL RECYCLING
Unit returns to beginning sequence.
Is recycle selected?
YES
NO
MAIN FLAME FAIL XX:XX:XX LOCKOUT
ERROR MESSAGE
30
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
BURNER SHUTDOWN
Shutdown is started by opening
the operating interlock circuit.
Is voltage present at interlocks?
Continued operation.
POST PURGE XX
Fuel valves de-energized; fan energized for 15 seconds.
FOR PURGE & MODULATING
ERROR MESSAGE #1
UNSAFE AIR SHORT
If switch is opened within 30 seconds, sequence continues. If not, then ...
ERROR MESSAGE #2 – 30 SECONDS AFTER #1
UNSAFE AIR SHORT XX:XX:XX LOCKOUT
Alarm energized.
NORMAL MESSAGE
YES NO
Is post purge selected?
YES NO
Is main valve closed switch made?*
YES NO
YES NO
ERROR MESSAGE #1
UNSAFE FLAME ON
Fan is energized. If signal is elimi-nated within 30 seconds, sequence continues. If not, then. . .
ERROR MESSAGE #2 – 30 SECONDS AFTER #1
UNSAFE FLAME ON XX:XX:XX LOCKOUT
Alarm energized.
MAIN VALVE FAIL
ERROR MESSAGE
XX:XX:XX LOCKOUT
Fan energized; alarm sounds.
YES NO
NORMAL MESSAGE
LIMITS OPEN TIME = XXXX:XX:XX
* Applies to purge and no purge models only.
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
31
Remote Display Diagnostic Messages
This section alphabetically lists and explains the diagnostic messages which can appear on the remote display.
Message Type Explanation
Air Failure XX:XX:XX Lockout
Lockout
Air Failure Recycling
Status
Air Not Proven XX:XX:XX Lockout
Air Proven
Automatic Modulation
Lockout
Status
Status
Burner on XX.XV Time = XXXX:XX:XX Status
D-Internal Fail XX:XX:XX:XX Lockout
Fan Energized
Flame Failure XX:XX:XX Lockout
HI Damper/POVC XX:XX:XX Lockout
K-Internal Fail XX:XX:XX Lockout
L-Internal Fail XX:XX:XX Lockout
Limits Open Time = XXXX:XX:XX
Low Fire Fail XX:XX:XX Lockout
Main Flame Fail XX:XX:XX Lockout
Main Flame Fail Recycling
Main Flame ON
Main Flame ON Pilot OFF
Lockout
Status
Lockout
Lockout
Lockout
Lockout
Status
Lockout
Lockout
Status
Lockout
Status
For purge & modulation models: Combustion air flow limit switch opened for more than two seconds once initially proven.
For purge & modulation models: Combustion air flow limit switch opened; if “recycle” has been selected, the Veri-Flame will restart the sequence after air failure (see “Recycle Mode” on page 13).
For purge & modulation models: Combustion air flow limit switch did not make within ten seconds of fan being energized.
For purge & modulation models: Combustion air flow limit switch closed within ten seconds of fan being energized.
For modulation models only: Modulating motor is sent to automatic operation.
Main flame of burner is proven in the automatic modulation mode; flame strength is XX.XV (volts DC). Elapsed time is shown in hours:minutes:seconds.
For modulation models only: Internal control failure; replace controller.
For purge & modulation models: Blower motor is energized at the start of pre-purge.
Main flame lost during operation in the automatic modulation mode.
For modulation models only: High damper or high purge rate switch did not make at the end of pre-purge to high fire.
Internal control failure; replace controller.
Internal control failure; replace controller.
The controller has completed its internal checks and is standing by for the interlocks to close.
For modulation models only: Low fire switch is open just prior to pilot trial for ignition.
Main flame was not established during the main burner trial for ignition.
Main flame lost during automatic modulation; control will recycle once if “recycle” has been selected.
Main valve has been energized and main flame proven during trial for ignition.
Pilot valve is de-energized and main flame is on.
Main Valve Fail XX:XX:XX Lockout
Pilot Flame Fail XX:XX:XX Lockout
Pilot ON
Pilot Trial for Ignition
32
Lockout
Lockout
Status
Status
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
For purge and no purge models: Main valve closed switch is open before start-up or after burner shutdown.
Pilot flame was not established during the pilot trial for ignition.
Pilot flame is proven; transformer is de-energized; remaining countdown for pilot trial for ignition is.
Pilot valve and ignition transformer are energized; countdown for pilot trial for ignition begins.
Message Type Explanation
Post Purge
Program Switch Error XX:XX:XX Lockout
Status
Lockout
For purge & modulation models: 15 second post purge is started on burner shutdown.
DIP switch improperly set or changed during cycle.
Purge to High Fire Status For modulation models only: Modulating motor is sent to high fire.
Purge to Low Fire Status For modulation models only: Modulating motor is sent to low fire.
Relay Fail XX:XX:XX Lockout
Lockout
Internal relay(s) fail initial check. Check ratings. If lockout still occurs after overload is eliminated, replace control.
Safe Start OK Status Control has completed internal safe-start check.
Unsafe Short
Status
For purge & modulation models: Combustion air switch is closed before start-up or after shutdown; control holds start-up until switch reopens; if interlocks close before switch opens, alarm is energized.
Unsafe Air Short XX:XX:XX Lockout Lockout
For purge & modulation models: Same conditions as above, except the interlocks close before the switch reopens, causing a lockout and the alarm being energized.
Unsafe Flame ON
Hold
Flame signal - actual, induced, or runaway scanner - is detected before start-up or after shutdown. The fan is energized. If the cause is corrected within 30 seconds, as in afterburn, the control will turn off the fan and continue the sequence.
Unsafe Flame ON XX:XX:XX Lockout Lockout
Same conditions as above, except the cause has not been corrected within 30 seconds, refansulting in a lockout and the alarm being energized.
Unsafe Flame Purge
Hold
For purge & modulation models: Flame signal - actual, induced, or runaway scanner - is detected during the selected purge time period. The fan is energized. If the cause is corrected within 30 seconds, as in afterburn, the control will turn off the and continue the sequence.
Unsafe Flame Purge XX:XX:XX Lockout Lockout
For purge & modulation models: Same conditions as above, except the cause has not been corrected within 30 seconds, resulting in a lockout and the alarm being energized.
V-Internal Fault XX:XX:XX Lockout
Watchdog Fail XX:XX:XX Lockout
XXXXXXX XXXXXTESTXX
Lockout
Lockout
Status
Internal control failure; replace controller.
Internal control failure; replace controller.
In combination with other messages, shows the control is in the minimum pilot test mode.
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
33
Appendix
Conversion Factors
Metric to English
From To Multiply By
actual cubic meter/h (am³/h) actual cubic foot/h (acfh) 35.31
normal cubic meter/h (Nm³/h) standard cubic foot /h (scfh) 38.04
degrees Celsius (°C) degrees Fahrenheit (°F) (°C x 9/5) + 32
kilogram (kg) pound (lb) 2.205
kilowatt (kW) Btu/h 3415
meter (m) foot (ft) 3.281
millibar (mbar) inches water column ("w.c.) 0.402
millibar (mbar) pounds/sq in (psi)
millimeter (mm) inch (in) 3.94 x 10
MJ/Nm³ Btu/ft³ (standard) 26.86
Metric to Metric
14.5 x 10
-3
-2
English to Metric
actual cubic foot/h (acfh) actual cubic meter/h (am³/h) 2.832 x 10
standard cubic foot /h (scfh) normal cubic meter/h (Nm³/h) 2.629 x 10
degrees Fahrenheit (°F) degrees Celsius (°C) (°F - 32) x 5/9
inches water column ("w.c.) millibar (mbar) 2.489
From To Multiply By
kiloPascals (kPa) millibar (mbar) 10
meter (m) millimeter (mm) 1000
millibar (mbar) kiloPascals (kPa) 0.1
millimeter (mm) meter (m) 0.001
From To Multiply By
pound (lb) kilogram (kg) 0.454
Btu/h kilowatt (kW) 0.293 x 10
foot (ft) meter (m) 0.3048
pounds/sq in (psi) millibar (mbar) 68.95
inch (in) millimeter (mm) 25.4
Btu/ft³ (standard) MJ/Nm³ 37.2 x 10-3
-2
-2
-3
i
Notes
ii
© Eclipse, Inc. All Rights Reserved
Installation Guide 818, 1/15/2015
Loading...