Ebac PD120 User Manual

PD120
OWNERS MANUAL
Date :-
10/12/13
Drawing No. :- TPC325 Issue :- 8
EBAC MODEL PD120
INDUSTRIAL DEHUMIDIFIER
OWNER’S MANUAL
Ebac Industrial Products, Inc.
700 Thimble Shoals Blvd, Suite 109
Newport News, VA. 23606-2575
Tel: (757) 873 6800 Fax: (757) 873 3632
Website www.ebacusa.com
PD120
OWNERS MANUAL
Date :-
10/12/13
PD120
PD120
PD120PD120
PACKAGE CONTENTS
PACKAGE CONTENTS
PACKAGE CONTENTSPACKAGE CONTENTS
Item Description Quantity
1028200 Dehumidifier 1
3014338 PVC tube – 12mm I/D 3M
3086101 Jubilee clip 1
Drawing No. :- TPC325 Issue :- 8
3035157 Humidistat 1
TPC325 Manual 1
PD120
OWNERS MANUAL
Date :-
10/12/13
Drawing No. :- TPC325 Issue :- 8
UNPACKING
Carefully remove the PD120 dehumidifier unit from its transit box and visually check for signs of transit damage. If there is evidence of damage DO NOT attempt to operate the unit, call your supplier for advice. Do not discard the packing, it will be useful when transporting the dehumidifier unit in the future.
INTRODUCTION
The Ebac PD120 industrial dehumidifier removes moisture from the air through the refrigeration process.
The Ebac PD120 is basically comprised of:
1) A compressor
2) A refrigerant evaporator coil
3) A refrigerant condenser coil
4) One circulation fan
5) A remote humidistat
6) A cabinet to house the above components
The fan draws the moist air through the cold evaporator coil which cools the air below its dew point. Moisture forms on the evaporator coil and is collected in the condensate tray which is equipped with a permanent drain. The cooled air then passes through the hot condenser coil where it is reheated using the same energy removed during the cooling phase, plus the additional heat generated by the compressor. The air is therefore discharged from the dehumidifier at a slightly higher temperature with a lower absolute humidity than with which it entered. Continuous circulation of air through the dehumidifier gradually reduces the relative humidity within the area. The PD120 dehumidifier is a rugged, reliable drying unit designed to operate effectively over a broad range of temperature and humidity conditions. The PD120 dehumidifier uses a remotely mounted adjustable humidistat to enable you to select the level of dryness.
PD120
OWNERS MANUAL
Date :-
10/12/13
MMMM
ODEL
ODEL
ODELODEL
HHHH
EIGHT
EIGHT
EIGHTEIGHT
WWWW
DDDD
EPTH
EPTH
EPTHEPTH
SPECIFICATIONS
::::
::::
IDTH
IDTH
::::
IDTHIDTH
::::
Drawing No. :- TPC325 Issue :- 8
Ebac PD120
17.5” (445mm)
27” (690mm)
26” (660mm)
WWWW
AAAA
IRFLOW
IRFLOW
IRFLOWIRFLOW
PPPP
PPPP
OWER
OWER
OWER OWER
FFFF
RRRR
EFRIGERANT
EFRIGERANT
EFRIGERANT EFRIGERANT
EIGHT
EIGHT
EIGHTEIGHT
OWER
OWER
OWEROWER
SSSS
UPPLY
UPPLY
UPPLYUPPLY
INISH
INISH
INISHINISH
TTTT
::::
::::
::::
::::
YPE
YPE
YPEYPE
::::
/Q
/Q
/Q/Q
TY
TY
TYTY
176 lbs (80Kg)
Low 261 CFM (445 M3/hr)
High 491 CFM (835 M3/hr)
1000 W
110V–115V/60Hz/1ph
Powder-coated Epoxy
::::
R407c
PD120
OWNERS MANUAL
Date :-
10/12/13
Drawing No. :- TPC325 Issue :- 8
INSTALLATION
POSITIONING:
Position the dehumidifier unit in the center of the room to be conditioned if at all possible. However if a damp patch is particularly apparent the outlet grille should be pointed towards it if possible.
This unit can also be used in a duct system where applicable, please see the diagrams on the following pages which identify the overall sizes of the unit and also the mounting points.
NOTE: Both inlet grille and outlet grille of the dehumidifier unit must have clear space around them and not be obstructed in anyway.
Before connecting this unit to the relevant power supply the following must be carried out.
Selecting the correct fan speed – The PD120 has a low fan speed and a high fan speed and the required speed must be chosen before installation. To select the correct fan speed firstly remove the air inlet cover via the 10off M4 hex head bolts, then remove the electrical box cover via the 4off M4 hex head bolts. Once the electrical box cover is removed the supplied link wire must be wired between either the ‘C’ and ‘L’ or the ‘C’ and ‘H’ terminals on the terminal block. This is shown below.
Before the unit will switch on it must have a low voltage humidistat wired into it with the NC contacts wired to the terminal block inside the electrical box as shown below.
PD120
OWNERS MANUAL
Date :-
10/12/13
Drawing No. :- TPC325 Issue :- 8
OPERATION
The following procedures should be followed to test the PD120 for correct operation:
1) After unpacking, examine all external features to confirm damage-free shipment. Report all
defects and damage at once. Connect the power cable to a grounded power source.
2) Install drain tubing as required.
Caution: Do not operate the machine without the covers for any longer than necessary. Do not remove/ replace the covers when the unit is in operation.
Check dehumidification process as follows:
A. Place unit on a level surface. B. Start up unit as follows:
i.Ensure fan speed selection has been chosen as mentioned in previous pages and also
that the humidistat has been wired in.
ii.Rotate humidistat control knob to fully counter clockwise, minimum setting.
iii.Plug unit into power supply and rotate humidistat knob clockwise to desired setting.
C. Check that the compressor is running. D. Leave the machine running for 15 minutes. E. Observe the evaporator coils behind the filter on the air inlet end of the unit to confirm
frost formation.
i.If the air temperature is below 70ºF, an even coating of frost should cover the entire
evaporator coil, except for the last one or two coils.
ii.If the air temperature is about 70ºF, frost and/or droplets of condensed water should
cover the entire evaporator coil.
F. As the drain tray fills, the condensate will automatically drain by gravity.
If after carrying out the above procedures, the unit does not appear to function properly, refer to the Trouble Shooting section or contact the Factory Service Center.
WARNING:
Due to the high pressures within the refrigeration circuit, under no circumstances must direct
heat be applied to the evaporator coil in an attempt to remove the build up of ice.
No attempt should be made to cut open any part of the refrigeration circuit due to high
pressures and gas involved. If the unit is switched off at the mains power supply for any reason, the unit must be allowed to stand at rest for at least five minutes before restarting. Failure to do so may cause the unit to blow the fuses owing to the compressor due to there being a refrigerant imbalance.
ROUTINE MAINTENANCE
PD120
OWNERS MANUAL
Date :-
10/12/13
Drawing No. :- TPC325 Issue :- 8
WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE
HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE MAINTENANCE ON ITEMS 1, 2, 4, 5, AND 6.
To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows:
1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air. Hold the nozzle of the air hose away from the coil (approx 6”) to avoid damaging the fins. Alternatively, vacuum clean the coils.
WARNING: DO NOT STEAM CLEAN REFRIGERATION COILS.
2. Check that the fan is firmly secured to the motor shaft and that the fan rotates freely. The fan motor is sealed for life and therefore does not need oiling.
3. To check the refrigerant charge, run the unit for 15 minutes and briefly remove the cover. The evaporator coil should be evenly frost coated across its surface. At temperatures above 70°F, the coil may be covered with droplets of water rather than frost. Partial frosting accompanied by frosting of the thin capillary tubes, indicates loss of refrigerant gas or low charge.
4. Check all wiring connections.
I
F ANY OF THE PRECEDING PROBLEMS OCCUR, CONTACT THE EBAC SERVICE CENTER PRIOR TO
CONTINUED OPERATION OF THE UNIT TO PREVENT PERMANENT DAMAGE
.
PD120
OWNERS MANUAL
Date :-
10/12/13
Drawing No. :- TPC325 Issue :- 8
REPAIRS
1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part.
2. If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action.
Any competent refrigeration technician will be able to service the equipment. The
following procedure must be used:
a. The source of the leak must be determined and corrected.
b. The machine should be thoroughly evacuated before recharging.
c. The unit must be recharged with refrigerant measured accurately by weight.
d. For evacuation and recharging of the machine, use the crimped and brazed
charging stub attached to the side of the refrigerant compressor.
The charging stub should be crimped and rebrazed after servicing. N
permanent service valves to be fitted to any part of the circuit. Service valves may leak causing further loss of refrigerant gas.
3. The refrigerant compressor fitted to the dehumidifier is a durable unit that should give many years of service. Compressor failure can result from the machine losing its refrigerant gas. The compressor can be replaced by a competent refrigeration technician.
Failure of the compressor can be confirmed by the following procedure:
a. Establish that power is present at the compressor terminals using a voltmeter.
b. With the power disconnected, check the continuity of the internal winding by
using meter across the compressor terminals. An open circuit indicates that the compressor should be replaced.
c. Check that the compressor is not grounded by establishing that a circuit does not
exist between the compressor terminals and the shell of the compressor.
EVER
allow
PD120
OWNERS MANUAL
Date :-
10/12/13
supply panel
fault and repair
3. Loss of refrigerant gas
3. Contact the Factory Service Center
2. Replace fan
S
YMPTOM
Unit inoperative
C
TROUBLESHOOTING
AUSE
1. no power to unit
Drawing No. :- TPC325 Issue :- 8
R
EMEDY
1. Check the power from the power
Little or no airflow
Little or no water extraction
Unit vibrates excessively
Water flooding inside the machine
1. Loose fan on shaft
2. Fan motor burnt out
3. Dirty refrigeration coils
4. Loose electrical wiring
1. Insufficient air flow
2. Compressor fault
1. Loose compressor mounts
2. Damaged fan
1. Drain pipe blocked/frozen
2. Drain pipe too high
1. Tighten fan
2. Replace the fan motor
3. See Routine Maintenance Section
4. Check the wiring diagram to find
1. Check all of the above
2. Contact the Factory Service Center
1. Tighten the nuts on the compressor mounts
1. Clear the obstruction
2. Ensure that no section of the drain hose is above the level of the water outlet
Ebac Industrial Products, Inc.
700 Thimble Shoals Blvd, Suite 109
Newport News, VA. 23606-2575
Tel: (757) 873 6800 Fax: (757) 873 3632
Website www.ebacusa.com
PD120
OWNERS MANUAL
Date :-
10/12/13
RRRR
::::
VVVV
::::
PPPP
::::
TTTT
DDDD
FFFF
::::
Drawing No. :- TPC325 Issue :- 8
RATING PLATE INFORMATION
MMMM
OISTURE
OISTURE
OISTURE OISTURE
(P
(P
INTS PER
INTS PER
(P(P
INTS PER INTS PER
@@@@
80F
80F
////
60%
60%
80F80F
60%60%
EFRIGERANT
EFRIGERANT
EFRIGERANTEFRIGERANT
OLTAGE
OLTAGE
OLTAGEOLTAGE
OWER
OWER
OWEROWER
PPPP
HASE
HASE
::::
HASEHASE
HHHH
ZZZZ
::::
CCCC
URRENT
URRENT
URRENTURRENT
CCCC
ONTROL
ONTROL
ONTROL ONTROL
IME
IME
ELAY
ELAY
IME IME
ELAY ELAY
PD120
RRRR
EMOVAL
EMOVAL
EMOVALEMOVAL
24
24
HOURS
2424
RH
RH::::
RHRH
HOURS
HOURSHOURS
))))
::::
VVVV
OLTAGE
OLTAGE
OLTAGEOLTAGE
USE
USE
USEUSE
::::
PD120
PD120PD120
107
1300 Grams
115 Volts
1.1 KW Single
60 Hz
10 A
5 V DC
15 A
PD120
OWNERS MANUAL
Date :-
10/12/13
PLEASE NOTE
WARRANTY REGISTRATION
Drawing No. :- TPC325 Issue :- 8
LIMITED WARRANTY
Our products carry a one-year unconditional warranty against any defects in workmanship or material. This warranty will cover all parts and labor required to repair your Ebac product. This warranty is invalid if the unit has been abused, damaged, whether intentional or accidental, or if any modifications have been made to the unit.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IS ISSUED IN LIEU OF ALL OTHER WARRANTIES (WHETHER WRITTEN, ORAL, OR IMPLIED) INCLUDING THE WARRANTY OF MERCHANTABILITY AND THE WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. EBAC INDUSTRIAL PRODUCTS, INC. DISCLAIMS ANY LIABILITY FOR CONSEQUENTIAL DAMAGES, LOST PROFITS, OR INCIDENTAL DAMAGES FOR BREACH OF ANY WRITTEN OR IMPLIED WARRANTY WITH RESPECT TO THE FOREGOING DESCRIBED MERCHANDISE.
For Your Records: Model: ____________________ S/N: ______________________ Date Received: ______________
SAVE THIS SECTION FOR YOUR RECORDS
CLIP AND RETURN THIS CARD
To ensure that your Ebac Dehumidifier is accorded the full coverage provided by this warranty, please complete and mail this card at your earliest convenience.
Thank You
Thank You
Thank YouThank You
DATE
MODEL ___________ S/N ________________ RECEIVED ________________
OWNER __________________________________________________________
ADDRESS ________________________________________________________
CITY __________________________ STATE ________ ZIP _______________
COMMENTS ______________________________________________________
_________________________________________________________________
Ebac Industrial Products.
700 Thimble Shoals Boulevard, Suite 109, Newport News, Virginia. 23606-2575
PD120
OWNERS MANUAL
Date :-
10/12/13
Drawing No. :- TPC325 Issue :- 8
PD120
OWNERS MANUAL
Date :-
10/12/13
Drawing No. :- TPC325 Issue :- 8
PD120
OWNERS MANUAL
Date :-
10/12/13
Drawing No. :- TPC325 Issue :- 8
UK Head Office
Ebac Industrial Products Ltd
St Helens Trading Estate
Bishop Auckland
County Durham
Tel: +44 (0) 1388 664400
Fax: +44 (0) 1388 662590
sales@eipl.co.uk
DL14 9AD
www.eipl.co.uk
American Sales Office
Ebac Industrial Products Inc
700 Thimble Shoals Blvd. Suite 109, Newport News
Virginia, 23606-2575
USA
Tel: +01 757 873 6800
Fax: +01 757 873 3632
www.ebacusa.com