Ebac DD700 460V User Manual

Drawing : - TPC 401 Issue : - 5 Date : - 28/04/14
DD700
10551GR-US – 460V / 3PH / 60HZ
INDUSTRIAL DEHUMIDIFIER
OWNER’S MANUAL
www.eipl.co.uk
Drawing : - TPC 401 Issue : - 5 Date : - 28/04/14
DD700
PACKAGE CONTENTS
Item Description Quantity
10551GR-US Dehumidifier 1
TPC401 Manual 1
Drawing : - TPC 401 Issue : - 5 Date : - 28/04/14
UNPACKING
Carefully remove the DD700 dehumidifier unit from its transit box and visually check for signs of transit damage. If there is evidence of damage DO NOT attempt to operate the unit, call your supplier for advice. Do not discard the packing, it will be useful when transporting the dehumidifier unit in the future.
INTRODUCTION
Dehumidifiers remove moisture from the air that is circulating through the unit. The resulting reduction of relative humidity helps prevent rust, rot, mould, mildew and condensation within the room, or other enclosed spaces where the dehumidifier is used. The DD700 is of the desiccant wheel type designed to dry air by passing a large volume of air, the “process” air through a slowly rotating Silica gel rotor. Silica gel is a hygroscopic material that absorbs moisture direct from the air. As the air passes through the rotor the humidity of the air is reduced, whilst the moisture content of the rotor is increased. A smaller volume of air, the reactivation air, is heated by an internal heater and passes through a portion of the rotor in the opposite direction. As this heated air passes through the rotor it will “reactivate” it by removing the moisture content from the silica gel material. The reactivation air will leave the humidifier as warm, moist air and must be vented to outside of the building.
Continuous circulation of the room air through the dehumidifier unit gradually reduces the relative humidity in the room.
The DD700 dehumidifier is a robust, compact unit designed to control the humidity in the enclosed space in which it is placed. The casing is fabricated from Steel then painted and has been designed for the exacting conditions which can prevail in offices, shops, houses, restaurants, public houses etc. It combines lightness and compactness with high reliability and strength.
The unit is thermally protected and will automatically switch off in excessive or abnormal conditions.
The dehumidifier has two separate filters. One in the “process” air inlet and one in the “reactivation” air inlet, used to clean the air entering the dehumidifier.
Drawing : - TPC 401 Issue : - 5 Date : - 28/04/14
SPECIFICATIONS
MODEL: DD700
HEIGHT: 1020mm (40”)
WIDTH: 711mm (28”)
DEPTH: 584mm (23”)
WEIGHT: 85Kg (187.4lbs)
POWER SUPPLY: 460V, 3 ph, 60Hz
POWER 7.5 kW (max)
F1 CONTROLS FUSE 2A 250V 5x20 Cartridge fuse
PROCESS AIRFLOW MAXIMUM: 1500m3/hr (883 cfm)
PROCESS AIRFLOW NOMINAL: 700m3/hr (412 cfm)
REGENERATION AIRFLOW NOMINAL: 160m3/hr (94 cfm)
PROCESS AIR OUTLET DIA: 200mm (8”)
REGENERATION AIR OUTLET DIA: 150mm (6”)
ROTOR WHEEL SPEED: 13.6
ROTOR SIZE DIA X DEPTH: 350mm (13.8”) x 100mm (4”)
HIGH EXTRACTION SETTING
109 l/day (231 ppd)
@ 27°C 60% RH:
HIGH EFFICIENCY SETTING
87 l/day (184 ppd)
@ 27°C 60% RH:
DEEP DRYING SETTING
97 l/day (205 ppd)
@ 27°C 60% RH:
TYPICAL DRY AIR OFF
18
HIGH EXTRACTION SETTING (%RH)
TYPICAL DRY AIR OFF
18
HIGH EFFICIENCY SETTING (%RH)
TYPICAL DRY AIR OFF
8
DEEP DRYING SETTING (%RH)
MINIMUM OPERATING TEMPERATURE: -20°C (-4°F)
MAXIMUM OPERATING TEMPERATURE 40°C (104°F)
Drawing : - TPC 401 Issue : - 5 Date : - 28/04/14
UNIT CAPACITY
The ambient conditions of the area to be dehumidified will determine the amount of water extraction the unit is cable of. Measure the ambient conditions of the area to be determined and then use that information with the following capacity diagram to determine the unit capacity.
Drawing : - TPC 401
-
WARNING
Issue : - 5 Date : - 28/04/14
INSTALLATION
The DD700 is designed for indoor use. The unit should be placed on a level surface and a space of 3 ft free around all faces to allow access for any duct work and servicing.
Connecting duct work:
The regeneration outlet must be ducted to outside the area being dehumidified. The outlet duct spigot is 6” diameter and only 6” ducting or greater should be attached.
The process outlet can be ducted to a specific area or another room. The outlet duct spigot is 8” diameter and only 8” ducting or greater should be attached.
Power Supply & Humidistat Control:
The unit must be connected to a suitable 460V, 3 phase, 60Hz supply.
THIS APPLIANCE MUST BE EARTHED
Feed power cables through the gland provided and then wire the unit as shown below.
An external humidistat can also be used to control the relative humidity in the dehumidified area. If a humidistat is used then the wires should pass through the gland provided and then wired as below.
-
Drawing : - TPC 401
PROCESS AIR
REGEN AIR
TEMPERATURE
STANDARD
HIGH
DEEP DRYING
Issue : - 5 Date : - 28/04/14
Control Settings
Once the unit is positioned correctly, required duct work attached and the power supply connected, the fan speeds and temperature control need to be set correctly.
The fan speed controls are located behind a removable cover, to the right of the main controls. The controls are numbered 1 to 10, with 10 being the maximum speed.
The temperature control regulates the temperature of the reactivation airflow onto the desiccant wheel. The control can be set up to a maximum of 145°C To adjust the temperature control simply press and hold the UP or DOWN arrows until the required temperature is selected. Once the required set point is reached release the buttons and the value is stored.
For normal (efficient) operation the process airflow should be set to 412cfm, and the regeneration airflow set to 94. Measurements should be taken at the duct outlets using a suitable instrument. The temperature setting should be set to 90°C above the ambient temperature of the area being dehumidified
If high moisture extraction is required it will be necessary to increase both the process and regeneration airflows. The temperature control setting should also be increased.
If very low humidity levels are required then the process airflow should be reduced.
The following table should be used as a guide:
FLOW (M³/H)
FLOW (M³/H)
RISE
(K)
(EFFICIENT)
EXTRACTION
(LOW RH)
412 94 90
530 147 110
294 147 110
Drawing : - TPC 401 Issue : - 5 Date : - 28/04/14
FAN PERFORMANCE CURVES
For example: If the total system resistance is 500pa then the process fan selector would have to be set to No 7 to achieve the required airflow of 412 cfm
For example: If the total system resistance is 300pa then the regen fan selector would have to be set to No 8 to achieve the required airflow of 94 cfm
Drawing : - TPC 401
M
0
Issue : - 5 Date : - 28/04/14
OPERATION
The electrical controls are located on the front of the unit. They are:
On / Off Switch
Dehumidifier in continuous operation
A
Dehumidifier operation by means of an external humidistat
Dehumidifier OFF
An hour counter is provided to display the total time the unit has been in operation
DRYING lamp – unit is in drying mode.
HEATING lamp – indicates heating elements are on. Cycle on/off when
in drying mode.
FAULT lamp – unit has a fault
To start the dehumidifier, turn the On / Off switch to position M. After a slight delay the fans will operate – air can be felt blowing from the air outlets and the heater will come on. The unit will operate continuously at this setting.
If an external humidistat control is fitted, turn the unit to switch to position A. Depending on the setting of the humidistat, the dehumidifier may switch off as the relative humidity in the room decreases. As the humidity increase the unit will automatically switch back on.
High Temperature Cut-Out:
The DD700 dehumidifier has been designed to work in ambient conditions of
-4ºF to +104ºF. Should the temperature in the room become excessive a manual overheat protector will operate, switching off the heaters. The fans and drive motor will continue to operate but the fault lamp will illuminate. Prior to resetting the protector, check that the dehumidifier is installed correctly and the ambient temperature does not exceed 104°F.
See repairs section for details on resetting device.
Drawing : - TPC 401 Issue : - 5 Date : - 28/04/14
SAFETY
-WARNING-
DO NOT ALLOW CHILDREN TO PLAY WITH OR AROUND THE
UNIT. ENSURE THE UNIT IS INACCESIBLE TO CHILDREN WHEN NOT ATTENDED.
DO NOT USE THIS UNIT IN AN ENVIRONMENT CONTAINING
FLAMMABLE FUMES
DO NOT USE THIS UNIT IF THE CABINET OR POWER CORD IS
DAMAGED
DO NOT INSERT OBJECTS INTO ANY OF THE GRILLES ON
THE MACHINE
DO NOT COVER OR OBSTRUCT AIRFLOW FROM THE
GRILLES
DO NOT OPERATE THE UNIT WITH THE COVERS REMOVED
DO NOT ATTEMPT ANY REPAIRS SHOULD THE UNIT FAIL TO
OPERATE
DO NOT STAND ON THE UNIT
DO NOT LIFT THE UNIT WHEN SWITCHED ON
DO CHECK THE PLUG ON THE EQUIPMENT MATCHES THE
SUPPLY
DO USE THE UNIT FOR THE PURPOSE FOR WHICH IT WAS
DESIGNED
DO ENSURE THE POWER CORD AND SUPPLY IS EARTHED
CORRECTLY
DO USE A RESIDUAL CURRENT DEVICE “RCD” WHERE
POSSIBLE
DO KEEP THE UNIT DRY. NEVER USE A HOSE OR PRESSURE
WASHER TO CLEAN THE UNIT.
Drawing : - TPC 401
WARNING:
Issue : - 5 Date : - 28/04/14
ROUTINE MAINTENANCE & REPAIR
To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows:
ENSURE THAT THE POWER CORD TO THE MACHINE HAS
BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE
MAINTENACE.
SWITCH OFF THE DEHUMIDIFIER APPROXIMATELY 15
MINUTES PRIOR TO REMOVING ANY PANELS, ALLOWING
THE HEATER TO COOL DOWN
We recommend that the filters are checked at least once a month. Intervals for cleaning or replacement of filters will depend on the installation
Never operate the dehumidifier without the filters, as the rotor can be damaged by dust.
To carryout the following, it is necessary to remove the side panels.
This machine should be serviced by qualified Ebac Industrial Products Ltd personnel or other persons having technical competence in servicing electrical equipment following the instructions in this Service Manual.
The rotor is maintenance free. However, should it be necessary to clean the rotor, compressed air should be used to carefully blow dirt from the rotor.
The heaters are maintenance free. However should it be necessary to clean the heaters, compressed air should be used to carefully blow dirt from the heaters.
Check that the fans are firmly secured and that the fan rotates freely.
Check all wiring connections.
Check the belt tensioning at regular intervals.
The overheat protector is located inside the unit, below the desiccant
wheel. To reset this device press the red button.
Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part.
Drawing : - TPC 401 Issue : - 5 Date : - 28/04/14
F ANY OF THE PRECEDING PROBLEMS OCCUR, CONTACT THE EBAC
INDUSTRIAL PRODUCTS LTD SERVICE CENTER PRIOR TO CONTINUED
OPERATION OF THE UNIT TO PREVENT PERMANENT DAMAGE
TROUBLESHOOTING
SYMPTOM
CAUSE
REMEDY
.
Little or no
dehumidification
capacity
Dehumidifier does
not start
Rotor does not
rotate
No Dry or Wet Air
Airflow
Filter clogged
No regeneration heat Check Heaters / OHP
Reduced airflow Check fans / duct
No rotation of Rotor Check belt tension / drive motor
Air leakage Check sealing
No power Check fuse
Correct switch setting Check Auto / Manual switch
Loose electrical wiring
Drive belt slipping Check belt tension
Drive belt broken Replace drive belt
Rotor jammed Check centre shaft, rim of rotor
Drive motor faulty Check supply /Replace motor
Filter clogged Clean or replace filters
Fan faulty Check supply / fan
Ducts blocked Check duct for obstruction
Clean or replace filters
Check wiring diagram - fault
find & repair
Fan loose Check fans secured firmly
Noisy
Loose fastenings Tighten all fastenings
Drawing : - TPC 401 Issue : - 5 Date : - 28/04/14
1
3
OF
SHEET
1/10
1
W DAGLISH
1
DD700
DRG.NO.
DRAWN :
CAD SCALE :
N/A
GENERAL ASSEMBLY / OVERVIEW
1003.
2
PROCESS
AIR INLET
1 12/02/13 ORIGINAL
ISS. DATE COMMENTS
4
REGENERATION
AIR INLET
TITLE
MATERIAL
DD
D NN
ND AA
AN LL
LA KK
KL CC
CK
MM
M
UU
UC
AA
AM
AA
AU
HH
HA
DD
D
A
RR
RH
NN
ND
PP
P
UU
UR
AA
AN
OO
OP
DD
DU
LL
LA
HH
HO
D
GG
GL
..
.
SS
SH
NN
NG
II
IS
oo
o.
E
B
C
EE
EN
BB
BI
CC
Co
DIMENSIONS IN m.m.
N/A
2
FINISH
1
0.25
0.5 DEGREE
0.05
OTHERWISE STATED
ANGULAR
TOLERANCES UNLESS
0.0
0.00
0.
DO NOT SCALE
77
7 99
3
133 314
4
65 451
301
263
634
3
97
3RD ANGLE PROJECTION
99
99 1
11
19
4
718
1
40
40
7
5
IF IN DOUBT ASK
3
4
5
POWER
ISOLATOR
ELECTRICAL
CONNECTIONS
PANEL
MAINS INLET GLAND
200
150
n
6
D D
AIR OUTLET
REGENERATION
C C
n
580
PROCESS
AIR OUTLET
301.7
851.7
290
1
7
B B
HUMIDITY SENSOR
WIRING GLAND
6
A A
2
3
OF
SHEET
1/10
1
W DAGLISH
1
DD700
DRG.NO.
DRAWN :
CAD SCALE :
N/A
GENERAL ASSEMBLY / OVERVIEW
N/A
2
1 12/02/13 ORIGINAL
ISS. DATE COMMENTS
3
TITLE
MATERIAL
DD
D NN
ND AA
AN LL
LA KK
KL CC
CK
MM
M
UU
UC
AA
AM
AA
AU
HH
HA
DD
D
A
RR
RH
NN
ND
PP
P
UU
UR
AA
AN
OO
OP
DD
DU
LL
LA
HH
HO
D
GG
GL
..
.
SS
SH
NN
NG
II
IS
oo
o.
E
B
C
EE
EN
BB
BI
CC
Co
DIMENSIONS IN m.m.
OTHERWISE STATED
TOLERANCES UNLESS
77
7 99
97
3RD ANGLE PROJECTION
99
99 1
11
19
4
2
FINISH
1
0.25
0.5 DEGREE
0.05
ANGULAR
0.0
0.00
0.
DO NOT SCALE
IF IN DOUBT ASK
3
4
5
6
D D
C C
B B
A A
5
6
3
3
OF
SHEET
1/8
1
W DAGLISH
1
DD700
DRG.NO.
DRAWN :
CAD SCALE :
N/A
GENERAL ASSEMBLY / OVERVIEW
N/A
2
1 12/02/13 ORIGINAL
ISS. DATE COMMENTS
DETAIL A
SCALE 1/3
3
TITLE
MATERIAL
DD
D NN
ND AA
AN LL
LA KK
KL CC
CK
MM
M
UU
UC
AA
AM
AA
AU
HH
HA
DD
D
A
RR
RH
NN
ND
PP
P
UU
UR
AA
AN
OO
OP
DD
DU
LL
LA
HH
HO
D
GG
GL
..
.
SS
SH
NN
NG
II
IS
oo
o.
E
B
C
EE
EN
BB
BI
CC
Co
DIMENSIONS IN m.m.
OTHERWISE STATED
TOLERANCES UNLESS
77
7 99
97
3RD ANGLE PROJECTION
99
99 1
11
19
4
2
FINISH
1
0.25
0.5 DEGREE
0.05
ANGULAR
0.0
0.00
0.
DO NOT SCALE
IF IN DOUBT ASK
3
4
5
A
6
D D
C C
B B
A A
5
6
Drawing : - TPC 401
UK Head Office
American Sales Office
German Sales Office
Issue : - 5 Date : - 28/04/14
Ebac Industrial Products Ltd
St Helens Trading Estate
Bishop Auckland
County Durham
DL14 9AD
Tel: +44 (0) 1388 664400
Fax: +44 (0) 1388 662590
www.eipl.co.uk
sales@eipl.co.uk
Ebac Industrial Products Inc
700 Thimble Shoals Blvd. Suite 109, Newport News
Virginia, 23606-2575
Ebac Industrial Products Ltd.
Gartenfelder Str. 29-37
Gebäude 35
D-13599, Berlin
USA
Tel: +01 757 873 6800
Fax: +01 757 873 3632
www.ebacusa.com
sales@ebacusa.com
Tel: +49 3043 557241
Fax: +49 3043 557240
www.eip-ltd.de
sales@eip-ltd.de
Germany
Loading...