Ebac DD1200 220V User Manual

Page 1
Drawing : - TPC 392 Issue : - 5 Date : - 28/04/14
10540GR-US – 220V / 3PH / 60HZ
INDUSTRIAL DEHUMIDIFIER
OWNER’S MANUAL
www.eipl.co.uk
Page 2
Drawing : - TPC 392 Issue : - 5 Date : - 28/04/14
DD1200
PACKAGE CONTENTS
Item Description Quantity
10540GR-US Dehumidifier 1
TPC392 Manual 1
Page 3
Drawing : - TPC 392 Issue : - 5 Date : - 28/04/14
UNPACKING
Carefully remove the DD1200 dehumidifier unit from its transit box and visually check for signs of transit damage. If there is evidence of damage DO NOT attempt to operate the unit, call your supplier for advice. Do not discard the packing, it will be useful when transporting the dehumidifier unit in the future.
INTRODUCTION
Dehumidifiers remove moisture from the air that is circulating through the unit. The resulting reduction of relative humidity helps prevent rust, rot, mould, mildew and condensation within the room, or other enclosed spaces where the dehumidifier is used. The DD1200 is of the desiccant wheel type designed to dry air by passing a large volume of air, the “process” air through a slowly rotating Silica gel rotor. Silica gel is a hygroscopic material that absorbs moisture direct from the air. As the air passes through the rotor the humidity of the air is reduced, whilst the moisture content of the rotor is increased. A smaller volume of air, the reactivation air, is heated by an internal heater and passes through a portion of the rotor in the opposite direction. As this heated air passes through the rotor it will “reactivate” it by removing the moisture content from the silica gel material. The reactivation air will leave the humidifier as warm, moist air and must be vented to outside of the building.
Continuous circulation of the room air through the dehumidifier unit gradually reduces the relative humidity in the room.
The DD1200 dehumidifier is a robust, compact unit designed to control the humidity in the enclosed space in which it is placed. The casing is fabricated from Steel then painted and has been designed for the exacting conditions which can prevail in offices, shops, houses, restaurants, public houses etc. It combines compactness with high reliability and strength
The unit is thermally protected and will automatically switch off in excessive or abnormal conditions.
The dehumidifier has two separate filters. One in the “process” air inlet and one in the “reactivation” air inlet, used to clean the air entering the dehumidifier.
Page 4
SPECIFICATIONS
M
ODEL
H
EIGHT
W
D
W
EIGHT
P
OWER SUPPLY
P
F1 C
ONTROLS FUSE
P
ROCESS AIRFLOW MAXIMUM
P
ROCESS AIRFLOW NOMINAL
: DD1200
: 1420mm (56”)
IDTH
: 711mm (28”)
EPTH
: 584mm (23”)
: 100Kg (220.5lbs)
: 220V, 3 ph, 60Hz
OWER
11.8 kW (max)
2A 250V 5x20 Cartridge fuse
: 1500m3/hr (883 cfm)
: 1200m3/hr (705cfm)
Drawing : - TPC 392 Issue : - 5 Date : - 28/04/14
R
EGENERATION AIRFLOW NOMINAL
P
ROCESS AIR OUTLET DIA
R
EGENERATION AIR OUTLET DIA
R
OTOR WHEEL SPEED
R
OTOR SIZE DIA X DEPTH
H
IGH EXTRACTION SETTING
@ 27°C 60% RH:
H
IGH EFFICIENCY SETTING
@ 27°C 60% RH:
D
EEP DRYING SETTING
@ 27°C 60% RH:
T
YPICAL DRY AIR OFF
H
IGH EXTRACTION SETTING
T
YPICAL DRY AIR OFF
H
IGH EFFICIENCY SETTING
T
YPICAL DRY AIR OFF
D
EEP DRYING SETTING
(%RH)
(%RH)
(%RH)
: 330m3/hr (195 cfm)
: 200mm (8”)
: 150mm (6”)
: 13.6 (RPH)
: 450mm (17.7”) x 200mm (7.9”)
266 l/day (562 ppd)
190 l/day (402 ppd)
241 l/day (508 ppd)
9
12
5
M
INIMUM OPERATING TEMPERATURE
M
AXIMUM OPERATING TEMPERATURE
: -20°C (-4°F)
40°C (104°F)
Page 5
Drawing : - TPC 392 Issue : - 5 Date : - 28/04/14
UNIT CAPACITY
The ambient conditions of the area to be dehumidified will determine the amount of water extraction the unit is capable of. Measure the ambient conditions of the area to be determined and then use that information with the following capacity diagram to determine the unit capacity.
Page 6
Drawing : - TPC 392
-
WARNING
Issue : - 5 Date : - 28/04/14
INSTALLATION
The DD1200 is designed for indoor use. The unit should be placed on a level surface and a space of 1 meter free around all faces to allow access for any duct work and servicing.
Connecting duct work:
The regeneration outlet must be ducted to outside the area being dehumidified. The outlet duct spigot is 6” diameter and only 6” ducting or greater should be attached.
The process outlet can be ducted to a specific area or another room. The outlet duct spigot is 8” diameter and only 8” ducting or greater should be attached.
Power Supply & Humidistat Control:
The unit must be connected to a suitable 220V, 3 phase, 60Hz supply.
THIS APPLIANCE MUST BE EARTHED
Feed power cables through the gland provided and then wire the unit as shown below.
An external humidistat can also be used to control the relative humidity in the dehumidified area. If a humidistat is used then the wires should pass through the gland provided and then wired as below.
-
Page 7
Drawing : - TPC 392
PROCESS AIR
REGEN AIR
TEMPERATURE
STANDARD
HIGH
DEEP DRYING
Issue : - 5 Date : - 28/04/14
Control Settings
Once the unit is positioned correctly, required duct work attached and the power supply connected, the fan speeds and temperature control need to be set correctly.
The fan speed controls are located behind a removable cover, to the right of the main controls. The controls are numbered 1 to 10, with 10 being the maximum speed.
The temperature control regulates the temperature of the reactivation airflow onto the desiccant wheel. The control can be set up to a maximum of 145°C To adjust the temperature control simply press and hold the UP or DOWN arrows until the required temperature is selected. Once the required set point is reached release the buttons and the value is stored.
For normal (efficient) operation the process airflow should be set to 705cfm, and the regeneration airflow set to 195cfm. Measurements should be taken at the duct outlets using a suitable instrument. The temperature setting should be set to 90°C above the ambient temperature of the area being dehumidified
If high moisture extraction is required it will be necessary to increase both the process and regeneration airflows. The temperature control setting should also be increased.
If very low humidity levels are required then the process airflow should be reduced.
The following table should be used as a guide:
FLOW (CFM)
FLOW (CFM)
RISE
(K)
(EFFICIENT)
EXTRACTION
(LOW RH)
705 195 90
824 235 110
589 235 110
Page 8
Drawing : - TPC 392 Issue : - 5 Date : - 28/04/14
FAN PERFORMANCE CURVES
For example: If the total system resistance is 600pa then the process fan selector would have to be set to No 10 to achieve the required airflow of 705cfm
For example: If the total system resistance is 400pa then the regen fan selector would have to be set to No 8 to achieve the required airflow of 195cfm
Page 9
Drawing : - TPC 392
M
0
Issue : - 5 Date : - 28/04/14
OPERATION
The electrical controls are located on the front of the unit. They are:
On / Off Switch
Dehumidifier in continuous operation
A
Dehumidifier operation by means of an external humidistat
Dehumidifier OFF
An hour counter is provided to display the total time the unit has been in operation
DRYING lamp – unit is in drying mode.
HEATING lamp – indicates heating elements are on. Cycle on/off when
in drying mode.
FAULT lamp – unit has a fault
To start the dehumidifier, turn the On / Off switch to position M. After a slight delay the fans will operate – air can be felt blowing from the air outlets and the heater will come on. The unit will operate continuously at this setting.
If an external humidistat control is fitted, turn the unit to switch to position A. Depending on the setting of the humidistat, the dehumidifier may switch off as the relative humidity in the room decreases. As the humidity increase the unit will automatically switch back on.
High Temperature Cut-Out:
The DD1200 dehumidifier has been designed to work in ambient conditions of
-4ºF to +104ºF. Should the temperature in the room become excessive an overheat protector will operate, switching off the heaters. The fans and drive motor will continue to operate but the fault lamp will illuminate. Prior to resetting the protector, check that the dehumidifier is installed correctly and the ambient temperature does not exceed 104°F.
See repairs section for details on resetting device.
Page 10
Drawing : - TPC 392 Issue : - 5 Date : - 28/04/14
SAFETY
-WARNING-
DO NOT ALLOW CHILDREN TO PLAY WITH OR AROUND THE
UNIT. ENSURE THE UNIT IS INACCESIBLE TO CHILDREN WHEN NOT ATTENDED.
DO NOT USE THIS UNIT IN AN ENVIRONMENT CONTAINING
FLAMMABLE FUMES
DO NOT USE THIS UNIT IF THE CABINET OR POWER CORD IS
DAMAGED
DO NOT INSERT OBJECTS INTO ANY OF THE GRILLES ON
THE MACHINE
DO NOT COVER OR OBSTRUCT AIRFLOW FROM THE
GRILLES
DO NOT OPERATE THE UNIT WITH THE COVERS REMOVED
DO NOT ATTEMPT ANY REPAIRS SHOULD THE UNIT FAIL TO
OPERATE
DO NOT STAND ON THE UNIT
DO NOT LIFT THE UNIT WHEN SWITCHED ON
DO CHECK THE PLUG ON THE EQUIPMENT MATCHES THE
SUPPLY
DO USE THE UNIT FOR THE PURPOSE FOR WHICH IT WAS
DESIGNED
DO ENSURE THE POWER CORD AND SUPPLY IS EARTHED
CORRECTLY
DO USE A RESIDUAL CURRENT DEVICE “RCD” WHERE
POSSIBLE
DO KEEP THE UNIT DRY. NEVER USE A HOSE OR PRESSURE
WASHER TO CLEAN THE UNIT.
Page 11
Drawing : - TPC 392
WARNING:
Issue : - 5 Date : - 28/04/14
ROUTINE MAINTENANCE & REPAIR
To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows:
ENSURE THAT THE POWER CORD TO THE MACHINE HAS
BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE
MAINTENACE.
SWITCH OFF THE DEHUMIDIFIER APPROXIMATELY 15
MINUTES PRIOR TO REMOVING ANY PANELS, ALLOWING
THE HEATER TO COOL DOWN
We recommend that the filters are checked at least once a month.
Intervals for cleaning or replacement of filters will depend on the installation
Never operate the dehumidifier without the filters, as the rotor can be
damaged by dust.
To carryout the following, it is necessary to remove the side panels.
This machine should be serviced by qualified Ebac Industrial Products Ltd personnel or other persons having technical competence in servicing electrical equipment following the instructions in this Service Manual.
The rotor is maintenance free. However, should it be necessary to
clean the rotor, compressed air should be used to carefully blow dirt from the rotor.
The heaters are maintenance free. However should it be necessary to
clean the heaters, compressed air should be used to carefully blow dirt from the heaters.
Check that the fans are firmly secured and that the fan rotates freely.
Check all wiring connections.
Check the belt tensioning at regular intervals.
The overheat protector is located inside the unit, below the desiccant
wheel. To reset this device press the red button.
Should an electrical component fail, consult the Factory Service Center
to obtain the proper replacement part.
Page 12
Drawing : - TPC 392 Issue : - 5 Date : - 28/04/14
I
F ANY OF THE PRECEDING PROBLEMS OCCUR, CONTACT THE EBAC
I
NDUSTRIAL PRODUCTS LTD SERVICE CENTER PRIOR TO CONTINUED
OPERATION OF THE UNIT TO PREVENT PERMANENT DAMAGE
TROUBLESHOOTING
S
YMPTOM
C
AUSE
R
EMEDY
.
Little or no
dehumidification
capacity
Dehumidifier does
not start
Rotor does not
rotate
No Dry or Wet Air
Airflow
Filter clogged
No regeneration heat Check Heaters / OHP
Reduced airflow Check fans / duct
No rotation of Rotor Check belt tension / drive motor
Air leakage Check sealing
No power Check fuse
Correct switch setting Check Auto / Manual switch
Loose electrical wiring
Drive belt slipping Check belt tension
Drive belt broken Replace drive belt
Rotor jammed Check centre shaft, rim of rotor
Drive motor faulty Check supply /Replace motor
Filter clogged Clean or replace filters
Fan faulty Check supply / fan
Ducts blocked Check duct for obstruction
Clean or replace filters
Check wiring diagram - fault
find & repair
Fan loose Check fans secured firmly
Noisy
Loose fastenings Tighten all fastenings
Page 13
Drawing : - TPC 392 Issue : - 5 Date : - 28/04/14
Page 14
1
3
OF
SHEET
1/10
1
W DAGLISH
1
DD1200
DRG.NO.
DRAWN :
CAD SCALE :
N/A
N/A
DD1200 - GENERAL ASSEMBLY / OVERV IEW
2
AIR INLET
PROCESS
1 12/02/13 ORIGINAL
ISS. DATE COMMENTS
450
3
65
450
4
1
0
3
AIR INLET
REGENERATION
314
133
2
6
8
3
2
3
5
6
TITLE
MATERIAL
DD
D NN
ND AA
AN LL
LA KK
KL CC
CK
MM
M
UU
UC
AA
AM
AA
AU
HH
HA
DD
D
A
RR
RH
NN
ND
PP
P
UU
UR
AA
AN
OO
OP
DD
DU
LL
LA
HH
HO
D
..
.
GG
GL
SS
SH II
IS
oo
o.
NN
NG
B
C
E
BB
BI
CC
Co
EE
EN
DIMENSIONS IN m.m.
OTHERWISE STATED
TOLERANCES UNLESS
77
7 99
97
3RD ANGLE PROJECTION
99
99 1
11
19
4
2
FINISH
1
0.25
0.5 DEGREE
0.05
ANGULAR
0.0
0.00
0.
DO NOT SCALE
IF IN DOUBT ASK
3
4
CONTROLS
40
5
150
n
AIR OUTLET
6
REGENERATION
40
5
ELECTRICAL
CONNECTIONS
POWER
ISOLATOR
200
n
OUTLET
PROCESS AIR
PANEL
MAINS INLET GLAND
WIRING GLAND
HUMIDISTAT SENSOR
580
290
6
7
4
0
1
7
1
126
.
.
1
7
D D
C C
B B
A A
Page 15
2
3
OF
SHEET
1/14
1
W DAGLISH
1
DD1200
DRG.NO.
DRAWN :
CAD SCALE :
N/A
N/A
DD1200 - GENERAL ASSEBLY / OVERVIEW
2
1 12/02/13 ORIGINAL
ISS. DATE COMMENTS
3
TITLE
MATERIAL
DD
D NN
ND AA
AN LL
LA KK
KL CC
CK
MM
M
UU
UC
AA
AM
AA
AU
HH
HA
DD
D
A
RR
RH
NN
ND
PP
P
UU
UR
AA
AN
OO
OP
DD
DU
LL
LA
HH
HO
D
..
.
GG
GL
SS
SH II
IS
oo
o.
NN
NG
B
C
E
BB
BI
CC
Co
EE
EN
DIMENSIONS IN m.m.
OTHERWISE STATED
TOLERANCES UNLESS
77
7 99
97
3RD ANGLE PROJECTION
99
99 1
11
19
4
2
FINISH
1
0.25
0.5 DEGREE
0.05
ANGULAR
0.0
0.00
0.
DO NOT SCALE
IF IN DOUBT ASK
3
4
5
6
D D
C C
B B
A A
5
6
Page 16
3
3
OF
SHEET
1/10
1
W DAGLISH
1
DD1200
DRG.NO.
DRAWN :
CAD SCALE :
N/A
N/A
DD1200 - GENERAL ASSEMBLY / OVERV IEW
2
1 12/02/13 ORIGINAL
ISS. DATE COMMENTS
DETAIL A
SCALE 1/3
3
TITLE
MATERIAL
DD
D NN
ND AA
AN LL
LA KK
KL CC
CK
MM
M
UU
UC
AA
AM
AA
AU
HH
HA
DD
D
A
RR
RH
NN
ND
PP
P
UU
UR
AA
AN
OO
OP
DD
DU
LL
LA
HH
HO
D
..
.
GG
GL
SS
SH II
IS
oo
o.
NN
NG
B
C
E
BB
BI
CC
Co
EE
EN
DIMENSIONS IN m.m.
OTHERWISE STATED
TOLERANCES UNLESS
77
7 99
97
3RD ANGLE PROJECTION
99
99 1
11
19
4
2
FINISH
1
0.25
0.5 DEGREE
0.05
ANGULAR
0.0
0.00
0.
DO NOT SCALE
IF IN DOUBT ASK
3
4
5
A
6
D D
C C
B B
A A
5
6
Page 17
Page 18
Page 19
Page 20
Drawing : - TPC 392
UK Head Office
America
n Sales Office
German Sales Office
Issue : - 5 Date : - 28/04/14
Ebac Industrial Products Ltd
St Helens Trading Estate
Bishop Auckland
County Durham
DL14 9AD
Tel: +44 (0) 1388 664400
Fax: +44 (0) 1388 662590
www.eipl.co.uk
sales@eipl.co.uk
Ebac Industrial Products Inc
700 Thimble Shoals Blvd. Suite 109, Newport News
Virginia, 23606-2575
Ebac Industrial Products Ltd.
Gartenfelder Str. 29-37
Gebäude 35
D-13599, Berlin
USA
Tel: +01 757 873 6800
Fax: +01 757 873 3632
www.ebacusa.com
sales@ebacusa.com
Tel: +49 3043 557241
Fax: +49 3043 557240
www.eip-ltd.de
sales@eip-ltd.de
Germany
Loading...