Ebac CD100E User Manual

Drawing : - TPC262 Issue : - 8 Date : - 10/12/13
CD100E
CD100ECD100E
INDUSTRIAL DEHUMIDIF
INDUSTRIAL DEHUMIDIFIER
INDUSTRIAL DEHUMIDIFINDUSTRIAL DEHUMIDIF
IER
IERIER
OWNER’S MANUAL
www.eipl.co.uk
Page 1 of 18
Drawing : - TPC262 Issue : - 8 Date : - 10/12/13
CD100E
PACKAGE CONTENTS
Item Description Quantity
1027500 Dehumidifier 1
Wall mounting bracket 1
3081315 M8 X 25 Hex head bolt 10 off
3081505 M8 Flat washer 10 off
3081525 M8 Spring washer 10 off
3088546 Red end cap 6 off
3088552 M8 Spring nut 10 off
3035998 Free socket 1 off
3014338 PVC tube – 12mm I/D 3M
3086101 Jubilee clip 1 off
TPC262 Manual 1 off
Page 2 of 18
Drawing : - TPC262 Issue : - 8 Date : - 10/12/13
UNPACKING
Carefully remove the CD100 dehumidifier unit from its transit box and visually check for signs of transit damage. If there is evidence of damage DO NOT attempt to operate the unit, call your supplier for advice. Do not discard the packing; it will be useful when transporting the dehumidifier unit in the future.
INTRODUCTION
Dehumidifiers remove moisture from the air that is circulating through the unit. The resulting reduction of relative humidity helps prevent rust, rot, mould, mildew and condensation within the room, shelter or other enclosed spaces where the dehumidifier is used. A dehumidifier consists of a motor-compressor unit, a refrigerant condenser, an air circulating fan, a refrigerated evaporator, a means for collecting and disposing of the condensed moisture and a cabinet to house these components. The fan draws the moist room air through the cold evaporator coil which cools the air below its dew point. Moisture forms on the evaporator and is collected in the condensate tray then lead away to a permanent drain. The cooled air then passes through the hot condenser, where it is re-heated with the same energy removed during the cooling phase and the addition heat derived from the compressor. The air is therefore discharged into the room at a slightly higher temperature but at a lower relative humidity than that at which it entered the unit. Continuous circulation of room air through the dehumidifier gradually reduces the relative humidity of the room. The CD100 dehumidifier is a rugged reliable drying unit designed to operate effectively over a broad range of temperature and humidity conditions. A powerful and reliable active hot gas defrost system, controlled by an electronic timer, guarantees positive de-icing, thereby optimizing at low temperatures. The unit incorporates a welded steel chassis and is finished in vinyl coated steel covers for resilience to damage caused by rough handling.
Page 3 of 18
Drawing : - TPC262 Issue : - 8 Date : - 10/12/13
SPECIFICATIONS
M
ODEL
H
EIGHT
W
IDTH
D
EPTH
W
EIGHT
A
IRFLOW
P
OWER
P
OWER SUPPLY
F
INISH
M
OBILITY
R
EFRIGERANT
T
YPE/QTY
"This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The
refrigeration system is hermetically sealed.
The Global Warming Potential (GWP) of refrigerants used in products manufactured by Ebac
Industrial Products Ltd is as follows
For type and weight of refrigerant contained in this unit, please refer to the product data label"
CD100E
:
: 406mm (16”)
: 914mm (36”)
: 508mm (20”)
: 61 Kg (135 lbs)
: 1190 M3/hr (700 cfm)
1090 W (max)
110V/120V, 1p,
:
50Hz/60Hz.
: Vinyl Coated Steel
Choice of Mobility Aids
:
– Wheels of Skid Handle
R407c (0.54Kg)
:
R134a – 1300 R407c – 1610
Page 4 of 18
Drawing : - TPC262 Issue : - 8 Date : - 10/12/13
INSTALLATION
POSITIONING:
Position the dehumidifier unit in the center of the room to be conditioned if at all possible. However if a damp patch is particularly apparent the outlet grille should be pointed towards it.
NOTE: Both inlet grille and outlet grille of the dehumidifier unit must have clear space around them and not be obstructed in anyway.
WIRING:
Connect the power cord of the dehumidifier to a suitable single phase, fused power supply. As follows:-
Brown Live
Blue Neutral
Green/Yellow Earth (ground)
ALARM WIRING:
Plug L (Normally Open Contacts)
Plug N (Close on Humidity Rise)
Plug E (Earth)
DRAINAGE:
Connect a 15mm inside diameter hose to the condensate outlet pipe (positioned centrally, beneath the air inlet grille). Secure the hose using a worm drive clip. The hose should at no point be raised higher than the outlet pipe. Failure to observe this requirement will result in flooding of the dehumidifier unit. Ensure the draintube heater tape is inserted the full length of the drain tube.
OPTIONAL:
The CD100 may also be fitted with a water pump capable of discharging the condensate a vertical height of 30ft. The water can, therefore, be discharged into a drain some distance away.
Page 5 of 18
Drawing : - TPC262
WARNING:
Issue : - 8 Date : - 10/12/13
OPERATION
The operation of the dehumidifier is to remove moisture from the air by having it condense on the cool tubes of the evaporator coil. The air then passes over the hot condenser and returns to the conditioned space slightly warmer and at reduced moisture content. To concentrate drying all doors and windows should be kept closed.
AIR MOVING SYSTEM:
Air is drawn in through the inlet grille at the rear of the dehumidifier (below the handle) and over the two heat exchanges (evaporator/condenser coils) under the influence of the axial fan, which is driven by the motor. The operation of the fan motor is to run continuously whenever power is supplied to the dehumidifier. The fan motor used in the dehumidifier unit is induction protected i.e. the motor is able to take stalled current without burning out the motor windings.
TEST FOR CORRECT OPERATION:
DO NOT RUN THE MACHINE WITHOUT THE COVERS IN PLACE FOR ANY
LONGER THAN NECESSARY. DO NOT REMOVE / REPLACE THE
COVERS WITH THE POWER ON
Remove the cover by releasing the retaining bolts and follow the test procedure laid out below.
1. Set the adjustment humidistat to maximum
2. Switch the machine to the on position; this will result in the compressor starting to run and the fan blade to starting to rotate.
3. When the compressor has been running for twenty minutes the coils located above the drain tray will be evenly coated in frost. (If the temperature is above 25ºC the coils will be covered in water).
4. After the machine has been running for approximately fifty minutes the unit will automatically enter defrost. The defrost cycle lasts for approximately three minutes; this will result in the frost on the coils meeting and dripping into the drainage tray.
5. After the defrost cycle has finished the machine will return to normal operation.
6. Ensure the condensate drains away from the machine.
Page 6 of 18