Technical Data
Effective March 1, 2018
Room Controller QuicKit
Catalog# Prepared by
Project Date
Comments Type
Overview
The Room Controller QuicKits provide a complete, all-in-one package
solution. Easy to order, QuicKits are designed and packaged for
immediate in-room installation.
The Room Controller includes three relays and up to three 0-10
VDC dimming outputs to control compatible dimmable ballasts. The
switching relays and 0-10 VDC outputs are controlled separately,
allowing flexibility in wiring and control. The Room Controller is
shipped preconfigured to work out-of-the-box when connected
to Room Controller devices, allowing quick and easy daylighting
controls, occupancy/vacancy sensing and manual switching.
Features
Packages for Conference Rooms, Offices, Classrooms, and
Healthcare
Click & Go ready, RJ45 connections
Preconfigured for automatic functionality upon power-up
Manual or Automatic On, bi-level, tri-level and dimming control
strategies
Integral Demand Response input with four levels of preconfigured
energy reduction
Built in tubular lighting control with preconfigured wallstation
controls
Integral pillow speaker connections for GPCS (RC3DEHC)
Integral Solatube® connection for classrooms
Guaranteed compatibility with Eaton LED and 0-10V fluorescent
fixtures
Ladderless UL 924 Emergency Mode testing (RC3DE &
RC3DEHC)
March 2018
Room Controller QuicKit
Specifications
QuicKit Size 8.5”H x14”W x11”D
Input/Output
Voltage
Emergency
Output (RC3DE/
RC3DEHC only)
UL 924
Class 2 Dimming
Output
LED Drivers Requires isolated LED drivers for optimal
Operating
Environment
Standards UL Approved
120/277 VAC, 60Hz
Maximum 20A combined load per Room Controller
Ballast load: 20A @ 120/277 VAC (LED)
Incandescent load: 15A @ 120 VAC
Motor load: 1HP @ 120 VAC
LED, Ballast or Incandescent load: 3A
0-10 VDC, sinks up to 100mA per (40 µA max per
circuit leakage to line)
Each 0-10V output supports up to 50 ballasts/
drivers that draw the standard 2mA each
performance
Temperature: 32°F to 104°F (0°C to 40°C)
For indoor use
UL 508 Listed
UL 924 Listed
Description/Operation
The Room Controllers are connected to a 120 VAC or 277 VAC 20
Amp circuit to provide unit power and input power to the individual
relays. The wallstations, occupancy/vacancy sensors, daylight
sensors and receptacle control devices connect via QuickConnect
cables providing a Class 2 connection. Upon power up the preengraved wallstation automatically controls the On/Off relays
and/or adjust the dimming outputs. The daylight sensor will
immediately adjust the lighting levels based on natural light.
Installation
The line voltage section of the Room Controller provides the
installing contractor space to make all line voltage connections and
direct conduit access, reducing the need for additional junction
boxes, while providing easy access to line voltage circuits. Low
voltage devices are connected using Cat5 cables (See page 4 for
included cables).
UL 924 relay is provided on some units for automatic emergency
lighting control. The UL 924 relay automatically tracks with output 1
and can be connected to any of the three 0-10V dimmers. The
UL 924 relay automatically closes and disconnects the 0-10V control
upon loss of normal power providing adequate egress lighting
control. Ladderless maintenance testing of the UL 924 relay can be
acheived by pressing the ALL OFF button four times.