This manual contains important instructions that you should follow during installation and maintenance of
the UPS and batteries. Please read all instructions before operating the equipment and save this manual for
future reference.
CONSIGNES DE SÉCURITÉ IMPORTANTES
CONSERVER CES INSTRUCTIONS
Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de toute procédure
d’installation et de maintenance des batteries et de l’onduleur. Veuillez consulter entièrement ces
instructions avant de faire fonctionner l’équipement et conserver ce manuel afin de pouvoir vous y reporter
ultérieurement.
Eaton and Power Xpert are registered trademarks of Eaton Corporation. Powerware, X-Slot, ABM, and Powerware Hot Sync are registered
trademarks and ConnectUPS and PowerTrust are trademarks of Eaton Electrical Inc. IBM and AS/400 are registered trademarks of International
Business Machines Corp. Modbus is a registered trademark of Modicon.
ECopyright 2007 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the
express written approval of Eaton Corporation.
Special Symbols
The following are examples of symbols u sed on the UPS or accessories to alert you to important information:
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should
be observed.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional information, such
as important operating and maintenance instructions.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This product
contains sealed, lead-acid batteries and must be disposed of properly. For more information, contact your
local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the
trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
ON – Indicates that the switch is in the ON position.
OFF – Indicates that the switch is in the OFF position.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
Chapter 1Introduction
Figure 1Table 1
The Eaton®Powerware®9315 (500–750 kVA) uninterruptible power supply (UPS) is an
online power protection system that prevents loss of valuable electronic information,
minimizes equipment downtime, and minimizes the adverse effect on equipment
production because of unexpected power problems.
The Powerware 9315 UPS system continually monitors incoming electrical power and
removes the surges, spikes, sags, and other irregularities that are inherent in
commercial utility power. Working with your building’s electrical system, the UPS
system supplies clean, consistent power that your sensitive electronic equipment
requires for reliable operation. During brownouts, blackouts, and other power
interruptions, optional battery strings provide emergency power to safeguard
operation.
The UPS system is housed in a free-standing cabinet, divided into three sections to
facilitate shipping. The cabinet sections line up and match in style and color, and have
safety shields behind the doors for hazardous voltage protection. Figure 1-1 shows a
typical Powerware 9315 (500–750 kVA) UPS system.
Module Bypass
Cabinet (MBC)
Output/Inverter
Cabinet
Input/Rectifier
Cabinet
Figure 1-1. Typical Powerware 9315 (500–750 kVA) UPS System
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
1-1
INTRODUCTION
1.1UPS Features
The UPS has many standard features that provide cost-effective and consistently
reliable power protection. The descriptions in this section provide a brief overview of
the UPS standard features.
1.1.1Installation Features
Power wiring can be routed through the top of each cabinet. External sensing
and monitoring control wire must be installed according to UL Class I requirements.
Class I wiring can be routed through the top of each cabinet.
1.1.2Customer Interface
The UPS has the following communication features:
S Building Alarm Monitoring – The facility’s alarm system contacts can be connected
to four inputs in the UPS. The UPS uses these inputs to monitor the building
alarms in addition to the UPS status. See Chapter 10, “Using Features and
Options,” for additional information.
S Summary Alarm Contacts – Summary alarm contacts are provided for connection to
equipment at the facility, such as a light, an audible alarm, or a computer terminal.
The equipment connected to this contact alerts you to a UPS alarm. See
Chapter 10, “Using Features and Options,” for additional information.
S Computer Interface – Two serial communication ports are standard on all units, and
are electrically isolated from the UPS. You can use these ports to link the UPS to
the features described in Chapter 12, “Communication.”
S X-Slot
®
Communication Bay – One communication bay is available on the UPS to
install an optional X-Slot card. See Chapter 12, “Communication,” for additional
information.
1.1.3Customer Convenience Outlet
An uninterruptible 120 Vac, 0.2A, fuse-protected convenience outlet is provided to
supply power to the optional modem. It is located on the customer interface panel.
1.1.4ABM®Technology
A three-stage charging system increases battery service life by optimizing recharge
time, and protects batteries from damage due to high current charging and inverter
ripple currents. Charging at high currents can overheat and damage batteries.
1.1.5Automatic Battery Charge Current Limit
A preset limit restricts battery charging current to protect batteries from damage due
to high current charging. Charging at high currents can overheat and damage
batteries.
1-2
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
1.2Options and Accessories
Contact your Eaton sales representative for information about the following options:
1.2.15% Input Filter
The UPS can be equipped with an input filter. An input filter yields power factor
correction that allows you to save on your initial installation and operating costs. The
filter also reduces input harmonic current distortion and minimizes upstream
interference that can damage sensitive hardware components.
1.2.2Battery Racks
You can enhance the protection time provided by the UPS system by adding one or
more battery racks. The battery racks should be equipped with sealed,
maintenance-free, lead-acid batteries. An external battery disconnect switch must be
used. See Chapter 4, “Installing a Remote Battery Disconnect,” for additional
information.
INTRODUCTION
1.2.3External Fused Battery Disconnect
An optional external DC disconnect provides an automatic or manual means of
disconnecting a battery string from the UPS. The disconnect is enclosed in a
floor-mounted, free-standing box. You can install it anywhere between the remote DC
supply and the UPS, according to national and local codes.
The breaker switch on the remote battery disconnect is set according to the operation
procedures in Chapter 9, “UPS Operating Instructions.” When service personnel are
performing maintenance on the UPS or battery string, the switch should be set to the
OFF position. See Chapter 4, “Installing a Remote Battery Disconnect,” for battery
disconnect requirements and installation instructions.
1.2.4Upgrade Capability
The UPS is available in various output power ratings in both 50 and 60 Hz models. If
your power requirements increase, you can upgrade the UPS system to provide more
output power with a minimum impact on your facility.
1.2.5Parallel Capacity/Redundant System
With Powerware Hot Sync technology and a System Bypass Module (SBM), the
Parallel Capacity/Redundant System allows two to eight uninterruptible power
modules (UPMs) to operate in parallel to provide more capacity than a single UPM
and as backup for each other. The parallel capacity/redundant system can supply up to
4000A, depending on the SBM used. In addition, when one UPM is taken out of
service for maintenance or is not operating properly, the redundant UPM continues to
supply uninterrupted power to the critical load.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
1-3
INTRODUCTION
1.2.6Monitoring and Communication
The following monitoring and communication options are available:
S Remote Monitor Panel (RMP) – An optional RMP contains backlit status indicators and
a local horn, allowing you to monitor the UPS operational status and alarm
condition from virtually any location within your facility. This option is described
further in Chapter 10, “Using Features and Options.”
S Relay Interface Module (RIM) – An optional RIM uses relay contact closures to
indicate the UPS operating status and alarm condition. The module uses a serial
interface line and may support up t o eight critical loads. This option is described
further in Chapter 10, “Using Features and Options.”
S Supervisory Contact Module (SCM) – An optional SCM establishes an interface
between the Parallel Capacity/Redundant system manufacturer’s equipment and
the customer’s monitor. This interface allows the customer to monitor operational
status of the Parallel Capacity/Redundant system equipment. This option is
described further in Chapter 10, “Using Features and Options.”
S X-Slot Cards – Optional X-Slot cards support several protocols, such as SNMP,
®
AS/400
, and Modbus®. See Chapter 12, “Communication,” for additional
information.
S eNotify Remote Monitoring and Diagnostic Service – An optional service that provides
7x24 remote monitoring of 43 alarms, t emperature/humidity and battery charge
information, daily heartbeat check, and monthly report. The eNotify Service also
provides customer notification of significant alarms, remote diagnostics, and
dispatch of technicians. A ConnectUPS –X Web/SNMP Card is required in the
X-Slot communication bay. An optional Powerware Environmental Monitoring
Probe (EMP) is required for temperature/humidity monitoring. See Chapter 12,
“Communication,” for additional information.
S Modem – An optional modem is available for use with the Remote Notification
feature described in Chapter 12, “Communication.” Refer to the modem
manufacturer’s manual for modem operating instructions.
t
1.3Basic System Configurations
The following basic UPS system configurations are possible:
S Single module UPS and one battery string
S Multi-module (parallel for capacity/redundancy) UPS system consisting of two or
more UPS modules, with one battery string for each module, and a Powerware
Hot Sync Capacity module
S Multi-module (parallel for capacity/redundancy) UPS system consisting of two or
more UPS modules, with one common battery string, and a Powerware Hot Sync
Capacity module
You can enhance the UPS system configuration by adding optional accessories, such
as an RMP, RIM, SCM, or remote emergency power-off (REPO) control.
1-4
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
®
1.4Safety Warnings
INTRODUCTION
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
S This manual contains important instructions that should be followed during installation and maintenance
of the UPS and batteries. Please read all instructions before operating the equipment and save this
manual for future reference.
S The UPS cabinet is designed for industrial or computer room applications and contains safety shields
behind the front doors. However, the UPS system is a sophisticated power system and should be handled
with appropriate care.
DANGER
This UPS contains LETHAL VOLTAGES. All maintenance and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY.
WARNING
S Installation and maintenance should be performed only by qualified personnel.
S The UPS system contains its own energy source (batteries). The output terminals may carry live voltage
even when the UPS is disconnected from an AC source.
S To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled,
indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C
(104°F). Do not operate near water or excessive humidity (95% maximum). The system is not intended for
outdoor use.
S Ensure all power is disconnected before performing installation or service.
S ELECTRIC ENERGY HAZARD. Do not attempt to a lter any battery wiring or connectors. Attempting to alter
wiring can cause injury.
CAUTION
S Batteries can present a risk of electrical shock or burn from high short-circuit current. Observe proper
precautions. Servicing should be performed by qualified service personnel knowledgeable of batteries
and required precautions. Keep unauthorized personnel away from batteries.
S Replace batteries with the same number and type of batteries as originally installed in the UPS.
S Proper disposal of batteries is required. Refer to local codes for disposal requirements.
S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
S Keep the cabinet doors on and secured to ensure proper cooling airflow and to protect personnel from
dangerous voltages inside the unit.
S Disconnect the charging source prior to connecting or disconnecting terminals.
S Determine if the battery is inadvertently grounded. If it is, remove the source of the ground. Contacting
any part of a grounded battery can cause a risk of electric shock. An electric shock is less likely if you
disconnect the grounding connection before you work on the batteries.
S Do not operate the UPS system close to gas or electric heat sources.
S The operating environment should be maintained within the parameters stated in this manual.
S Keep surroundings uncluttered, clean, and free from excess moisture.
S Do not use this equipment for other than intended use.
S The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
S Observe all DANGER, WARNING, and CAUTION notices affixed to the inside and outside of the
equipment.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
1-5
INTRODUCTION
S Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par des courts-circuits de
haute intensité. Prendre les précautions nécessaires.
S Pour le remplacement, utiliser le même nombre et modéle des batteries.
S Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans
votre localité.
S Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire exploser.
1.5Conventions Used in This Manual
This manual uses these type conventions:
S Italic type represents variable information that you must replace with an actual
value, or a directory or file name.
S Screen type represents information that appears on your screen.
S Bold type represents a command or option that you type or enter at a prompt.
AVERTISSEMENT!
ATTENTION!
1.6For More Information
IconDescription
Information notes call attention to important features or instructions.
[Keys]Brackets are used when referring to a specific key, such as [Enter] or [Ctrl].
In this manual, the term UPS refers only to the UPS cabinet and its internal elements.
The term UPS system refers to the entire power protection system – the UPS
modules, battery strings, and options or accessories installed.
Refer to the Powerware 9315 Parallel Capacity/Redundant UPS Installation andOperation Manual for the following additional information:
S SBM cabinet and optional accessories installation instructions, including site
preparation, planning for installation, wiring and safety information, and detailed
illustrations of the cabinet and optional accessories with dimensional and
connection point drawings.
S Parallel operation, including procedures for using the SBM cabinet with the UPS,
responding to system events, and information about maintenance.
S Describes the SBM control panel and explains the SBM functions; discusses the
SBM standard features and optional accessories; provides procedures for starting
and stopping the parallel for capacity/redundancy system, and information about
maintenance and responding to system events.
S SBM RS-485 and RS-232 serial communication, including connecting optional
remote accessories to the SBM and enabling, disabling, and customizing building
alarms.
1-6
Visit www.powerware.com or contact your Eaton service representative for
information on how to obtain copies of this manual.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
1.7Getting Help
INTRODUCTION
If you need help with any of the following:
S Scheduling initial startup
S Regional locations and telephone numbers
S A question about any of the information in this manual
S A question this manual does not answer
Please call the Eaton Help Desk for Powerware products at:
United States:
Canada:1-800-461-9166 ext 260
All other countries:Call your local service representative
1-800-843-9433 or 1-919-870-3028
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
1-7
INTRODUCTION
This page intentionally left blank.
1-8
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
Use the following basic sequence of steps to install the UPS:
1. Create an installation plan for the UPS system (Chapter 2).
2. Prepare your site for the UPS system (Chapter 2).
3. Inspect, unpack, and unload the UPS cabinets (Chapters 2 and 3).
4. Wire the system (Chapter 3).
5. Install features, accessories, and/or options, as applicable (Chapters 4 through 6).
6. Complete the installation checklist (Chapter 3).
7. Have authorized service personnel perform preliminary operational checks and
startup.
NOTE Startup and operational checks must be performed by an authorized Eaton Customer Service
Engineer, or the warranty terms specified on page 15-1 become void. This service is offered as part of t he
sales contract for the UPS. Contact your Eaton service representative in advance (usually a two-week notice is
required) to reserve a preferred startup date.
2.1Creating an Installation Plan
Before installing the UPS system, read and understand how this manual applies to the
system being installed. Use the procedures and illustrations in the following chapters
to create a logical plan for installing the system.
2.1.1Preparing Your Site
For the UPS system to operate at peak efficiency, the installation site should meet
the environmental parameters outlined in this manual. If the UPS is to be operated at
an altitude higher than 1500m (5000 ft), contact your Eaton service representative for
important information about high altitude operation. The operating environment must
meet the weight, clearance, and environmental requirements specified in
paragraph A.1 starting on page A-1.
The UPS cabinets use forced air cooling to regulate internal component temperature.
Air inlets are in the front of the cabinet and outlets are in the top. You must allow
clearance in front of and above each cabinet for proper air circulation (see Table B on
page A-1).
2.1.2Environment Considerations
The life of the UPS system is adversely affected if the installation does not meet the
following guidelines:
1. The system must be installed on a level, sealed concrete pad or floor.
2. The system must be installed in a temperature-controlled indoor area free of
conductive contaminants.
Failure to follow guidelines may void your warranty.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
2-1
UPS INSTALLATION PLAN AND UNPACKING
2.1.3Preparing for Wiring the UPS System
For external wiring requirements, including the minimum AWG size of external wiring,
see Table E through Table G starting on page A-13. The power wiring connections for
this equipment are rated at 90°C. If the ambient temperature is greater than 30°C,
higher temperature wire and/or larger size wire may be necessary. Control wiring for
remote emergency power-off (REPO) and optional accessories (such as building
alarms and monitoring interface) should be connected at the customer interface
terminal blocks located inside the UPS using UL Class 1 wiring methods.
2.2Inspecting and Unpacking Each Cabinet
Each cabinet is shipped bolted to w ooden pallets and protected with outer protective
packaging material and a plastic inner covering (see Figure 2-1).
Outer
Packaging
Wooden Pallet
Figure 2-1. Cabinet as Shipped with Outer Packaging and Pallet
WARNING
The UPS cabinets are extremely heavy (see Table A on page A-1). If unpacking instructions are not closely
followed, the cabinet may tip and cause serious injury.
CAUTION
S Do not install a damaged cabinet. Report any damage to the carrier and contact your Eaton service
representative immediately.
S Do not tilt the UPS cabinets more than 10° from vertical or the cabinet may tip over.
NOTE Verify that the forklift or pallet jack is rated to handle the weight of the cabinets (see Table A on
page A-1 for cabinet weights).
To unpack the cabinet:
1. Carefully inspect the outer packaging for evidence of damage during transit.
2-2
2. Use a forklift or pallet jack to move the packaged cabinet to the installation site,
or as close as possible, before unpacking. Insert the forklift or pallet jack forks
between the skids on the bottom of the unit.
3. Set each pallet on a firm, level surface, allowing a minimum clearance of
4.6m (15 ft) on each side for removing the cabinets from the pallets.
4. If outer packaging is secured with steel bands, cut and remove the bands from
each cabinet.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
UPS INSTALLATION PLAN AND UNPACKING
5. Remove the protective cardboard covering from the cabinets, cutting where
indicated, using a knife blade no longer than 25 mm (1”).
6. Remove the plastic bag and foam packing material, and discard or recycle them
in a responsible manner.
7. Inspect the contents for any evidence of physical damage, and compare each
item with the Bill of Lading. If damage has occurred or shortages are evident,
contact your Eaton service representative immediately to determine the extent of
the damage and its impact upon further installation.
NOTE While waiting for installation, protect the unpacked cabinets from moisture, dust, and other harmful
contaminants. Failure to store and protect the UPS system properly may void your warranty.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
2-3
UPS INSTALLATION PLAN AND UNPACKING
This page intentionally left blank.
2-4
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
Chapter 3Installing the UPS System
Figure 3Table 3
This section describes the UPS system installation for single modules and
multi-modules, including: unloading the cabinets, UPS internal and external wiring,
and interface connections.
3.1Preliminary Installation Information
DANGER
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED
SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
WARNING
Installation should be performed only by qualified personnel.
Refer to the following while installing the UPS system:
S See Appendix A for installation drawings and additional installation notes.
S Dimensions are in millimeters and inches.
S Do not tilt the UPS cabinets more than 10° from vertical or the cabinet may tip
over.
S Remove the conduit landing plates to add conduit landing holes as required. Plate
material is 14 gauge steel (2 mm/0.075” thick).
S The Emergency UPS Off (EPO) and the Remote Emergency Power-off (REPO)
buttons normally open all breakers in the UPS, shut down the UPS, and isolate
power from the critical load. However, the EPO and REPO may be configured to
transfer the UPS to bypass and shut down the UPS. Local electrical codes may
also require tripping protective devices upstream from t he UPS.
S The UPS cabinets must be installed on a level, sealed concrete pad or floor.
S If perforated floor tiles are required for ventilation, place them in front of the UPS.
See Table A on page A-1 for equipment weight.
S Details about control wiring are provided in each procedure for connecting options
and features. Paragraph A.5 starting on page A-28 identifies the control wiring
terminations.
S All circuit breakers provided as part of the UPS system that employ adjustable trip
mechanisms have been set to their maximum settings. Based upon the energy
available and other equipment located on-site, these settings may need to be
adjusted to ensure proper system operation and coordination. It is the customer’s
responsibility to conduct a breaker coordination study, so that these breakers can
be adequately set for the site.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
3-1
INSTALLING THE UPS SYSTEM
3.2Unloading the UPS Cabinets from the Pallet
S The UPS cabinets are heavy (see Table A on page A-1). If unpacking instructions are not closely followed,
the cabinet may tip and cause serious injury.
S Do not install a damaged cabinet. Report any damage to the carrier and contact your Eaton service
representative immediately.
S Do not tilt the UPS or optional cabinets more than 10° from vertical or the cabinet may tip over.
NOTE Verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see Table A on
page A-1 for cabinet weights).
Each UPS cabinet is bolted to a wooden pallet supported by wood skids.
To remove the pallet:
1. If not already moved, use a forklift or pallet jack to move the cabinet to the
installation site, or as close as possible, before unloading from the pallet. Insert
the forklift or pallet jack forks between the skids on the bottom of the unit.
WARNING
2. Remove the hardware securing each UPS cabinet to the pallet.
3. Using a forklift, raise the UPS cabinet until the cabinet bottom clears the pallet by
approximately 3 mm (1/8”).
4. When the UPS cabinet is clear of the pallet, pull the pallet from under the
cabinet. Discard or recycle the pallets in a responsible manner.
5. Carefully lower the UPS cabinet until the cabinet base touches the floor.
6. Repeat Steps 3 through 5 for the remaining UPS cabinets.
3.3Single Module Installation
To install a single module UPS system, perform the procedures in the following
paragraphs. If a multi-module system is being installed, proceed to “Multi-Module
Installation” on page 3-4.
3.3.1Installing UPS Internal Power and Control Wiring
NOTE The cables used in Steps 2 through 4 are coiled inside the Input/Rectifier cabinet and are attached
at the factory to the rectifier output. The cables used in Steps 7 and 8 are coiled inside the Module Bypass
Cabinet (MBC) and are attached at the factory to the input of the MBC.
To install the UPS internal power and control wiring (see Table H on page A-16 for
tightening torques and paragraph A.4 starting on page A-22 for terminal locations):
3-2
1. Remove the plastic shield covering the inverter input section of the
Output/Inverter cabinet.
2. Route the DC Link cables from the rectifier output (Input/Rectifier cabinet) to the
inverter input (Output/Inverter cabinet) through the knockouts in the cabinet
sides.
3. Connect the positive DC Link power wiring to the inverter input. Connect two
cables to each inverter.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
INSTALLING THE UPS SYSTEM
4. Connect the negative DC Link power wiring to the inverter input. Connect two
cables to each inverter.
5. Reinstall the plastic shield to the inverter input section.
6. Remove the plastic shield covering the inverter output section of the
Output/Inverter cabinet.
7. Route the MBC input cables from the MBC to the inverter output
(Output/Inverter cabinet) through the knockouts in the cabinet sides.
8. Connect phase A, B, and C and Neutral power wiring from the MBC to the
respective inverter output.
9. Route the ground braid from t he top of the Output/Inverter cabinet to the
Input/Rectifier cabinet through the cabinet knockouts. The ground braid is
secured at the factory to the Output/Inverter cabinet mounting stud.
10. Connect the ground braid to the Input/Rectifier cabinet mounting stud and
secure.
11. Route the ground braid from the top of the MBC to the Output/Inverter cabinet
through the cabinet knockouts. The ground braid is secured at the factory to the
MBC mounting stud.
12. Connect the ground braid to the Output/Inverter cabinet mounting stud and
secure.
13. Reinstall the plastic shield to the inverter output section.
14. Connect the Output/Inverter 15-pin control wiring harness connector to the
Input/Rectifier 15-pin control wiring harness connector. See Figure A-12 on
page A-22 for connector locations.
15. Connect the MBC 15-pin control wiring harness connector to the Output/Inverter
15-pin control wiring harness connector. See Appendix A for connector locations.
16. Connect the 3-pin control wiring harness connector P6 from the MBC to
connector J6 on the Inverter Number 2 control board in the Output/Inverter
cabinet.SeeFigureA-14onpageA-24andFigureA-16onpageA-26for
connector locations.
3.3.2Installing UPS External Power and Control Wiring
To install the UPS external power and control wiring (see Appendix A for wiring and
termination requirements and wiring access information):
1. Remove the sheet-metal shield covering the input terminal area in the
Input/Rectifier cabinet to gain access to the Battery I/O customer interface
and CB2TB. See Figure A-12 page A-22 for the shield location.
NOTE Remove the Input/Rectifier cabinet conduit landing plate to punch conduit holes.
2. Connect phase A, B, and C power wiring from the source to the respective
rectifier inputs in the Input/Rectifier cabinet.
3. Connect the positive and negative DC power wiring from the batteries to the
respective DC inputs in the Input/Rectifier cabinet.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
3-3
INSTALLING THE UPS SYSTEM
NOTE Remove the entire MBC top panel to punch conduit holes.
4. Connect phase A, B, and C power wiring from the bypass source to the
respective bypass inputs in the MBC.
5. Connect phase A, B, and C and Neutral power wiring from the MBC output to
the critical load.
6. Connect the control wiring (battery breaker open and close signals and shunt DC
disconnect) between the external battery disconnect and the UPS.
7. After wiring the UPS system to the facility power and critical load, be sure to
ground the system according to local and/or national electrical wiring codes.
8. Install the batteries according to the battery and battery rack manufacturer’s
instructions and all applicable codes and regulations, including the National
Electrical Code (NEC), Article 480.
NOTE There is no DC disconnect device within the UPS.
NOTE The DC input to the UPS is protected by internal fuses F30 and F31.
3.4Multi-Module Installation
To install a multi-module system using a System Bypass Module (SBM), perform the
procedures in the following paragraphs.
3.4.1Installing UPS Internal Power and Control Wiring
NOTE The cables used in Steps 2 through 4 are coiled inside the Input/Rectifier cabinet and are attached
at the factory to the rectifier output.
To install the UPS internal power and control wiring in a multi-module system (see
Appendix A for terminal locations and wiring access information):
1. Remove the plastic shield covering the inverter input section of the
2. Route the DC Link cables from the rectifier output (Input/Rectifier cabinet) to the
3. Connect the positive DC Link power wiring to the inverter input. Connect two
4. Connect the negative DC Link power wiring to the inverter input. Connect two
5. Reinstall the plastic shield to inverter input section.
Output/Inverter cabinet.
inverter input (Output/Inverter cabinet) through the knockouts in the cabinet
sides.
cables to each inverter. For tightening torque, see Table H on page A-16.
cables to each inverter. For tightening torque, see Table H on page A-16.
3-4
6. Route the ground braid from t he top of the Output/Inverter cabinet to the
Input/Rectifier cabinet through the cabinet knockouts. The ground braid is
secured at the factory to the Output/Inverter cabinet mounting stud.
7. Connect the ground braid to the Input/Rectifier cabinet mounting stud and
secure.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
INSTALLING THE UPS SYSTEM
8. Connect the Output/Inverter 15-pin control wiring harness connector to the
Input/Rectifier 15-pin control wiring harness connector. See Figure A-12 on
page A-22 and Figure A -14 on page A-24 for connector locations.
9. Remove the plastic shield covering the inverter output section of the
Output/Inverter cabinet.
10. Refer to the Powerware 9315 Parallel Capacity/Redundant UPS Installation and
Operation Manual for SBM input wiring procedures.
11. Reinstall the plastic shield to the inverter output section.
3.4.2Installing UPS External Power and Control Wiring
To install the UPS external power and control wiring (see Appendix A for wiring and
termination requirements and wiring access information):
1. Remove the sheet-metal shield covering the input terminal area in the
Input/Rectifier cabinet to gain access to the Battery I/O customer interface
and CB2TB. See Figure A-12 on page A-22 for the shield location.
NOTE Remove the Input/Rectifier cabinet conduit landing plate to punch conduit holes.
2. Connect phase A, B, and C power wiring from the source to the respective
rectifier inputs in the Input/Rectifier cabinet.
3. Connect positive and negative DC power wiring from the batteries to the
respective DC inputs in the Input/Rectifier cabinet.
4. Connect the control wiring (battery breaker open and close signals and shunt DC
disconnect) between the external battery disconnect and the UPS.
5. Refer to the Powerware 9315 Parallel Capacity/Redundant UPS Installation and
Operation Manual for SBM output wiring procedures.
6. After wiring the UPS system to the facility power and critical load, be sure to
ground the system according to local and/or national electrical wiring codes.
7. Install the batteries according to the battery and battery rack manufacturer’s
instructions and all applicable codes and regulations, including NEC, Article 480.
NOTE There is no DC disconnect device within the UPS.
NOTE The DC input to the UPS is protected by internal fuses F30 and F31.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
NOTE If you are installing connections to the Battery I/O terminal connections and terminal board CB2TB,
install conduit between each device and the UPS cabinet for wiring these options.
See paragraph A.5 on page A-28 for the interface point locations within the UPS
cabinet.
To prepare the UPS for wiring t o customer connections:
1. Verify that the UPS system is turned off and all power sources are removed. See
“Shutting Down the UPS and Critical Load” on page 9-6 for shutdown
instructions.
2. Remove the sheet-metal shield covering the input terminal area in the
Input/Rectifier cabinet to gain access to the Battery I/O customer interface
and CB2TB. See Figure A-12 on page A-22 for the shield location.
3. See paragraph A.5 on page A-28 for terminal assignments, and wiring and
NOTE If you are installing connections to a REPO device, building alarm, or relay contacts, install conduit
between each device and the UPS cabinet.
See paragraph A.5 on page A-28 for the interface point locations within the UPS
cabinet.
To prepare the UPS for wiring t o customer connections:
1. Verify that the UPS system is turned off and all power sources are removed. See
“Shutting Down the UPS and Critical Load” on page 9-6 for shutdown
instructions.
2. See paragraph A.5 on page A-28 for terminal assignments, and wiring and
termination requirements.
3.7Installing Accessories
To install an optional REPO switch, see Chapter 5, “Installing a Remote Emergency
Power-off Control.” To install optional accessories [such as the Remote Monitor Panel
(RMP) or X-Slot connections], see Chapter 6, “Installing Optional Accessories.” When
accessory installation is complete, proceed to paragraph 3.8.
3.8Initial Startup
Startup and operational checks must be performed by an authorized Eaton Customer
Service Engineer, or the warranty terms specified on page 15-1 become void. This
service is offered as part of the sales contract for the UPS. Contact your Eaton service
representative in advance (usually a two week notice is required) to reserve a
preferred startup date.
3-6
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
3.9Completing the Installation Checklist
The final step in installing the UPS system is completing the following installation
checklist. This checklist ensures that you have completely installed all hardware,
cables, and other equipment. Completing all items listed on the checklist will ensure a
smooth installation. You should make a copy of the installation checklist before filling
it out, and retain the original.
After the installation is complete, a service representative will be able to verify the
UPS system operation and commission it to support the critical load. The service
representative cannot perform any installation tasks other than verifying software and
operating setup parameters. Service personnel may request a copy of the completed
installation checklist to be sure you have completed all applicable equipment
installation.
NOTE The installation checklist MUST be completed prior to starting the UPS system for the first time.
INSTALLING THE UPS SYSTEM
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
3-7
INSTALLING THE UPS SYSTEM
Installation Checklist
- All packing materials and restraints have been removed from each cabinet.
- Each cabinet in the UPS system is placed in its final installation location.
- A ground bond is installed between any cabinets that are bolted together.
- All switchboards, conduits, and cables are properly routed to the UPS and auxiliary cabinets.
- All power cables are properly sized and terminated.
- A ground conductor is properly installed.
- If a bypass input neutral connection is used, no other N-G bonds exist downstream from the UPS.
- Battery cables and harnesses are terminated on E4 and E5.
- Internal battery cabinet connections have been completed (bus bars, plugs, etc.).
- Shunt trip signal wiring is connected from UPS to battery breaker(s).
- Air conditioning equipment is installed and operating correctly.
- The area around the UPS system is clean and dust-free. (It is recommended that the UPS be installed on a level,
sealed concrete pad or floor.)
- Adequate workspace exists around the UPS and other cabinets.
- Adequate lighting is provided around all UPS equipment.
- A 120V service outlet is located within 7.6m (25 ft) of the UPS equipment.
- Each Remote Monitor Panel (RMP) is mounted in its installed location. (OPTIONAL)
- The control wiring for each RMP is t erminated inside the UPS cabinet. (OPTIONAL)
- The remote emergency power-off (REPO) device is mounted in its installed location and its wiring terminated inside
the UPS cabinet. (OPTIONAL)
- Summary alarms and/or building alarms are wired appropriately. (OPTIONAL)
- A Relay Interface Module (RIM) is mounted in its installed location and its wiring is terminated inside the UPS cabinet.
(OPTIONAL)
- A remote battery disconnect control is mounted in its installed location and its wiring is terminated inside the UPS and
battery cabinets. (OPTIONAL)
- Circuit breakers with adjustable trip mechanisms adjusted to match site requirements.
- Debris shields covering ventilation grills are removed from all cabinets.
- Startup and operational checks are performed by an authorized Eaton Customer Service Engineer.
3-8
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
3-9
INSTALLING THE UPS SYSTEM
This page intentionally left blank.
3-10
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
Chapter 4Installing a Remote Battery Disconnect
Figure 4Table 4
The remote battery disconnect is crated separately for shipping. The enclosure is
designed to be free-standing. You can install a remote battery disconnect anywhere
between the remote DC supply and the UPS, according to national and local codes.
Figure 4-1 shows a typical remote battery disconnect enclosure.
The remote battery disconnect is set according to the operation procedures in
Chapter 9, “UPS Operating Instructions.” When service personnel are performing
maintenance on the UPS or battery string, the disconnect should be set to the OFF
position.
Operating Handle
ON Position
Operating Handle
OFF Position
Figure 4-1. Remote Battery Disconnect Enclosure
Consider the following general notes before beginning installation:
S There is no DC disconnect device within the UPS.
S The DC input to the UPS is only protected by internal fuses F30 and F31.
S The UPS DC disconnect trip signal from CB2TB, terminals 9 and 10 (shunt trip)
must be connected to the DC source disconnect device.
S See Figure A-30 on page A-42 for battery disconnect dimensions.
S See paragraph A.3 on page A-12 for specific ratings and wiring requirements.
S The material and labor for external wiring requirements is to be supplied by others.
S The knockout pattern for the disconnect is determined by others at the time of
installation.
S Power cables and control wiring must be installed in separate conduit.
S The ground conductor is to be sized per National Electrical Code (NEC), Article 250
and local electrical code requirements.
S The maximum current listed is at the minimum DC operating voltage.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
4-1
INSTALLING A REMOTE BATTERY DISCONNECT
S Nominal voltages listed in this chapter are for a lead-acid batteries rated per NEC at
2.00 Vdc per cell.
S Battery strings must be installed according to all applicable codes and regulations,
including NEC, Article 480.
S The UPS to battery cable should be sized for a total maximum voltage drop
of 1% nominal DC Link voltage at maximum current.
S Table 4-1 details the power cable terminations.
S The remote battery disconnect weighs approximately 60.3 kg (133 lb).
It has an ampere interrupting capacity (AIC) of 100,000 at 500 Vdc.
Table 4-1. Remote Battery Disconnect Power Terminations
Number and Type of Accessories Permitted
TerminalTerminal FunctionSize of Termination
E4 (+)UPS Battery Input (+)See Table H on page A-16
E5 (–)UPS Battery Input (–)See Table H on page A-16
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
Chapter 5Installing a Remote Emergency Power-off Control
)
TwistedWires(2)
Figure 5Table 5
A latching-type REPO switch can be used in an emergency to shut down the UPS and
remove power to the critical load from a location away from where the UPS is
installed. Figure 5-1 shows a REPO switch.
To UPMTo Other Equipment
Figure 5-1. Remote Emergency Power-off (REPO) Control
NOTE Before installing a REPO, verify that the UPS was installed according to the instructions in Chapter 3,
“Installing the UPS System.”
To install a REPO station:
1. Verify that the UPS system is turned off and all power sources are removed. See
Chapter 9, “UPS Operating Instructions,” for shutdown instructions.
UNINTERRUPTIBLE POWER SYSTEM
EMERGENCY OFF
2. Securely mount the REPO station. Recommended locations include operator’s
consoles or near exit doors. See Figure A-25 page A-37 for enclosure dimensions
and wiring knockouts.
3. Install wiring from the REPO station using ½” conduit through the cable entry
knockout in the top of the UPS Output/Inverter cabinet. See Appendix A for
conduit landing area, terminal board location, and terminal wiring assignments.
4. Connect the REPO wiring as shown in Table 5-1 and Figure 5-2:
Table 5-1. REPO Wire Terminations
From REPO Station(s)To Customer Interface
TB1-4CUSTTB-9
TB1-5CUSTTB-10
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
Terminal Board CUSTTB in UPS
Output/Inverter Cabinet
Remarks
Twisted Wires(2
14–18 Gauge
5-1
INSTALLING A REMOTE EMERGENCY POWER-OFF CONTROL
NOTE REPO switch rating is 24 Vdc, 1A minimum if supplied by the customer. The REPO switch must be a
latching-type switch with a dedicated circuit.
5. If you are installing multiple REPO stations, wire additional stations in parallel
with the first REPO.
6. If required, install ½” conduit and wiring from the REPO station to trip circuitry of
upstream protective devices. A normally open contact is provided, as shown in
Figure 5-2. REPO switch wiring must be according to UL Class I requirements.
REPO
Switch
Twisted
Wires (2)
Figure 5-2. REPO Wiring
9
CUSTTB
10
7. Secure the UPS by reversing all steps taken to prepare it for REPO installation.
5-2
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
Chapter 6Installing Optional Accessories
Figure 6Table 6
This chapter contains installation information for the following options:
S Monitoring accessories: Remote Monitor Panel (RMP), Relay Interface Module
(RIM), and Supervisory Contact Module (SCM)
S X-Slot cards
NOTE When installing interface connections (such as an RMP, RIM, or SCM), install conduit between each
device and the UPS cabinet.
A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be installed.
An X-Slot card can also be installed with the monitoring accessories. See Table 6-1 for
the number of accessories permitted.
Table 6-1. Optional Monitoring Accessories
Number and Type of Accessories Permitted
RMPRIMSCMX-Slot
2——1
—2—1
——21
11—1
1—11
—111
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
6-1
INSTALLING OPTIONAL ACCESSORIES
6.1Installing an RMP
As an option, you can install an RMP to monitor the UPS system operation from
virtually any location within your facility, up to 152.4m (500 ft) from the UPS. You can
flush-mount or surface-mount an RMP on a desktop or on a wall, wherever you have
a serial interface line. Figure 6-1 shows an RMP. Figure A-26 on page A-38 shows the
enclosure dimensions and cable exit openings.
Flush Mount
Surface Mount
(for hanging)
Wires Must be
Twisted
Figure 6-1. RMP
6-2
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
INSTALLING OPTIONAL ACCESSORIES
To install an RMP:
1. Verify that the UPS system is turned off and all power sources are removed. See
Chapter 9, “UPS Operating Instructions,” for shutdown instructions.
2. Remove the access plate on top of the UPS Input/Rectifier cabinet to gain access
to the customer interface panel (see Figure A-13 on page A-23).
3. Securely mount the RMP.
4. Install wiring from the RMP using ½” conduit through the cable entry knockout in
the top of the UPS Input/Rectifier cabinet. See Figure A-13 on page A-23 for the
conduit landing area location.
5. In the spare parts kit, locate the RMP adapter cable assembly (see Figure 6-2).
Mate the DB-9 connector on the back of the terminal block to the DB-9
connector (Port 1) on the UPS customer interface panel (see Figure A-19 on
page A-30). Use two screws from the spare parts kit to secure the terminal block
bracket to the customer interface panel.
Connect to
Port 1 (DB-9) on
Customer Interface Panel
Fuse
Terminal
Block
(TB3)
Figure 6-2. Terminal Block Bracket
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
6-3
INSTALLING OPTIONAL ACCESSORIES
)
Twistedwires(4)
)
Twistedwires(4)
6. Connect the RMP wiring to the terminal block using terminations shown in
Table 6-2.
Table 6-2. RMP Wire Terminations
From RMP ATo UPSRemarks
TB1-4TB3-1
TB1-5TB3-2
TB1-6TB3-3
TB1-7
From RMP B (If Used)To UPSRemarks
TB1-4TB3-5
TB1-5TB3-6
TB1-6TB3-7
TB1-7
TB3-4
TB3-8
Twisted wires(4
1–2 turns per 3”
Twisted wires(4
1–2 turns per 3”
7. To check the RMP operation, ensure that the UPS system is supplying the load
via the inverter or bypass. If the RMP indicators show the appropriate status,
then it is operating correctly.
If the communication link between the UPS and the RMP is not present, the
RMP conducts a self-test (all indicators f lash and the horn beeps at one-second
intervals); check all harness connectors and the fuse for proper seating. If all
connections are secure but the RMP continues to self-test, replace the fuse with
the spare included in the hardware kit. If this does not correct the problem,
contact your Eaton service representative for verification that the RMP is working
correctly.
8. To test the light emitting diode (LED) lamps behind the indicators, press and hold
the horn silence button for three seconds. All the indicators illuminate and the
horn sounds continuously until you release the button. If any indicator does not
illuminate, its LED lamp may need to be replaced. Contact your Eaton service
representative if you have a problem with the LEDs.
9. Repeat Steps 1 through 8 if you are installing another RMP.
10. If you are installing an RIM or SCM in addition to an RMP, proceed to
paragraph 6.2 or 6.3, respectively; otherwise, secure the access plate on top of
the UPS Input/Rectifier cabinet.
6-4
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
6.2Installing an RIM
INSTALLING OPTIONAL ACCESSORIES
The optional RIM uses relay contact closures to indicate the UPS system operating
status and alarm condition. The module uses an RS-422 serial interface line and may
support up to eight critical loads. Figure 6-3 shows the RIM with its four 15-pin D-sub
connectors labeled J1 through J4. See Figure A-27 and Figure A-28, starting on
page A-39, for enclosure dimensions and wiring knockouts.
Flush Mount
Surface Mount
(for hanging)
RIM
J2J1J4J3
15-Pin D-Sub
Connectors
Figure 6-3. RIM
Continues
at UPS
1. Verify that the UPS system is turned off and all power sources are removed. See
Chapter 9, “UPS Operating Instructions,” for shutdown instructions.
2. Remove the access plate on top of the UPS Input/Rectifier cabinet to gain access
to the customer interface panel (see Figure A-13 on page A-23).
3. Securely mount the RIM.
4. Install wiring from the RIM using ½” conduit through the cable entry knockout in
the top of the UPS Input/Rectifier cabinet. See Figure A-13 on page A-23 for the
conduit landing area location.
5. If not already installed, locate the RMP adapter cable assembly in the spare parts
kit (see Figure 6-4). Mate the DB-9 connector on the back of the terminal block to
the DB-9 connector (Port 1) on the UPS customer interface panel (see
Figure A-19 on page A-30). Use two screws from the spare parts kit to secure
the terminal block bracket to the customer interface panel.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
6-5
INSTALLING OPTIONAL ACCESSORIES
)
Twistedwires(4)
)
Twistedwires(4)
Connect to
Port 1 (DB-9) on
Customer Interface Panel
Fuse
Terminal
Block
(TB3)
Figure 6-4. Terminal Block Bracket
6. Connect RIM wiring to the terminal block using the terminations shown in
Table 6-3.
Table 6-3. RIM Wire Terminations
From RIM ATo UPSRemarks
TB1-4TB3-1
TB1-5TB3-2
TB1-6TB3-3
TB1-7
From RIM B (If Used)To UPSRemarks
TB1-4TB3-5
TB1-5TB3-6
TB1-6TB3-7
TB1-7
TB3-4
TB3-8
Twisted wires(4
1–2 turns per 3”
Twisted wires(4
1–2 turns per 3”
7. Contact your Eaton service representative for verification and testing of the RIM
and its connections prior to making connections to J1 through J4.
You can order interface cables separately for connecting to the 15-pin D-sub
connectors.
8. Repeat Steps 1 through 7 if you are installing another RIM.
9. If you are installing an SCM in addition to an RIM, proceed to paragraph 6.3;
otherwise, secure the access plate on top of the UPS Input/Rectifier cabinet.
6-6
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
6.3Installing an SCM
INSTALLING OPTIONAL ACCESSORIES
The optional SCM shown in Figure 6-5 provides contacts for monitoring UPS system
status. See Figure A-29 page A-41 for enclosure dimensions and knockout patterns.
Flush Mount
Surface Mount
(for hanging)
TB2
Wires Must be Twisted
Figure 6-5. SCM
1. Verify that the UPS system is turned off and all power sources are removed. See
Chapter 9, “UPS Operating Instructions,” for shutdown instructions.
2. Remove the access plate on top of the UPS Input/Rectifier cabinet to gain access
to the customer interface panel (see Figure A-13 on page A-23).
3. Securely mount the SCM.
4. Install wiring from the SCM using ½” conduit through the cable entry knockout in
the top of the UPS Input/Rectifier cabinet. See Figure A-13 on page A-23 for the
conduit landing area location.
5. If not already installed, locate the RMP adapter cable assembly in the spare parts
kit (see Figure 6-6). Mate the DB-9 connector on the back of the terminal block to
the DB-9 connector (Port 1) on the UPS customer interface panel (see
Figure A-19 on page A-30). Use two screws from the spare parts kit to secure
the terminal block bracket to the customer interface panel.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
6-7
INSTALLING OPTIONAL ACCESSORIES
)
Twistedwires(4)
)
Twistedwires(4)
Connect to
Port 1 (DB-9) on
Customer Interface Panel
Fuse
Terminal
Block
(TB3)
Figure 6-6. Terminal Block Bracket
6. Connect the SCM wiring to the terminal block using the terminations shown in
Table 6-4.
Table 6-4. SCM Wire Terminations
From SCM ATo UPSRemarks
TB1-4TB3-1
TB1-5TB3-2
TB1-6TB3-3
TB1-7
From SCM B (If Used)To UPSRemarks
TB1-4TB3-5
TB1-5TB3-6
TB1-6TB3-7
TB1-7
TB3-4
TB3-8
Twisted wires(4
1–2 turns per 3”
Twisted wires(4
1–2 turns per 3”
7. Contact your Eaton service representative for verification and testing of the SCM
and its connections prior to making connections to terminal strip TB2 shown in
Figure 6-7.
8. Repeat Steps 1 through 7 if you are installing another SCM.
9. Secure the access plate on top of the UPS Input/Rectifier cabinet.
6-8
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
System Normal
No Redundancy
On Generator
Bypass Not Available
INSTALLING OPTIONAL ACCESSORIES
On Battery
UPS Alarm
On Bypass
Shutdown Imminent
Figure 6-7. SCM TB2
NOTE Supervisory contacts are rated at 2.0A at 28 Vdc or 120 Vac and 0.15A at 115 Vdc.
NOTE Supervisory contacts require external power supply. Internal 24 Vdc is not capable of supplying
contact current.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
6-9
INSTALLING OPTIONAL ACCESSORIES
6.4Installing X-Slot Cards
NOTE LAN and telephone drops for use with X-Slot cards must be provided by facility planners or the
customer.
NOTE For setup of an X-Slot card, please contact Eaton (see page 1-7).
To install the X-Slot cards:
1. If not already installed, install the LAN, telephone, or other cables.
2. Remove the access plate on top of the UPS Input/Rectifier cabinet to gain access
to the customer interface panel (see Figure A-13 on page A-23).
3. Remove the X-Slot cover plate to gain access to the X-Slot communication bay
(see Figure A-19 on page A-30).
4. Install the X-Slot card into the communication bay.
5. Route and install the LAN, telephone, and other cables to the appropriate X-Slot
card.
6. Refer to the manual supplied with the X-Slot card for operator instructions.
6-10
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
The Powerware 9315 is a continuous duty, solid-state UPS that supports the
following equipment: process control, data processing, telecommunications/PBX,
research, and medical. The Powerware 9315 maintains power to the critical loads
during commercial electrical power brownout, blackout, overvoltage, undervoltage,
and out-of-tolerance frequency conditions.
In this manual, the power required by your equipment is called the critical load. The UPS
supplies the critical load with conditioned power that is synchronized with your utility
power. Figure 7-1 shows the main elements of the UPS system.
Battery
Breaker
CB2
F30
F31
Battery String
Output/InverterInput/Rectifier
AC Input to
Rectifier/
Charger
AC Input to
Bypass
Input
Breaker
CB1
Input
Transformer
Input
Filter
Rectifier/
Charger
Inverter
Power
Processing Unit
Digital
Output
Transformer
Output
Breaker
CB3
Input
Filter
Metering
Static
Backfeed
Protection
Breaker FBP
Module Bypass Cabinet (MBC)
Switch
Bypass
Breaker
CB4
Figure 7-1. Main Elements of the UPS System
The emergency bypass consists of a static switch, a wraparound bypass breaker
(CB4) and a Backfeed Protection Breaker (FBP). The FBP is located in series with the
static switch and opens so that the UPS cannot backfeed the bypass source.
AC Output
to Critical
Load
For manual transfers to bypass, the static switch is not used. During the transfer, CB4
is closed and verified and then inverter output breaker CB3 is opened. For transfers of
the load from bypass to the UPS, CB3 is closed and verified and then CB4 is opened.
The static switch is armed and ready during both types of transfers.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
7-1
UNDERSTANDING UPS OPERATION
7.1Operating Modes
If utility power is interrupted or falls outside the parameters specified in Chapter 14,
“Product Specifications,” the UPS uses a backup battery supply to maintain power to
the critical load for a specified period of time or until the utility power returns. For
extended power outages, the backup battery supply allows you to either transfer to
an alternative power system (such as a generator) or shut down your critical load in an
orderly manner.
The UPS system supports the critical load with the following operating modes:
S Normal mode – The critical load is supplied by the inverter, which derives its power
from rectified utility AC power. In this mode, the rectifier also provides charging
power to the battery.
S Bypass mode – Utility power directly supplies the critical load.
S Battery mode – The battery cabinet provides DC power, which maintains inverter
operation. The battery supports the critical load.
The UPS continually monitors itself and the incoming utility power, and automatically
switches between these modes as required, with no operator intervention. The
sophisticated detection and switching logic inside the UPS ensures that operating
mode changes are automatic and transparent to the critical load. The UPS changes
operating modes in response to:
S A command is an intervention that is externally initiated by an operator or by some
site action. A command causes the UPS to switch operating modes; it usually does
not require any further action.
S A notice is a minor system event that may or may not require your attention.
S An alarm is a system event that requires immediate operator intervention.
System events, horns, and indicators are described in Chapter 11, “Responding to
System Events.”
The following paragraphs describe the differences in UPS operating modes, using
block diagrams to show the power flow during each mode of operation.
7-2
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
7.1.1Normal Mode
In Normal mode, utility AC power is supplied to the rectifier. The rectifier supplies DC
power to the inverter, which then supplies the critical load with AC power. The
rectifier also provides charging power to the battery. The battery charge condition is
monitored by the UPS and reported by a status indicator on the control panel. The
message System Normal appears in the status area of the control panel LCD
screen.
Figure 7-2 shows the path of electrical power through the UPS system when the UPS
is operating in Normal mode.
UNDERSTANDING UPS OPERATION
CB4
(open)
Bypass
Static Switch
Rectifier
Input
Bypass
Input
CB1
(closed)
Path of Electrical Power
FBP
(closed)
InverterRectifier
DC
CB3
(closed)
Output
Input
Transformer
Link
Output
Transformer
CB2
(closed)
Battery
Figure 7-2. Path of Current Through the UPS in Normal Mode
If the utility AC power is interrupted or is out of specification, the UPS automatically
switches to Battery mode to support the critical load with no interruption. When utility
power returns, the UPS returns to Normal mode.
If the UPS becomes overloaded or unavailable, the UPS switches to Bypass mode.
The UPS automatically returns to Normal mode when the error condition is cleared
and system operation is restored within specified limits.
If the UPS suffers an internal failure, it switches automatically to Bypass mode and
remains in that mode until the failure is corrected and the UPS is back in service.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
7-3
UNDERSTANDING UPS OPERATION
7.1.2Bypass Mode
The UPS automatically switches to Bypass mode if it detects an overload, load fault,
or internal failure. The bypass source supplies the commercial AC power to the load
directly.
Figure 7-3 shows the path of electrical power through the UPS system when the UPS
is operating in Bypass mode.
CAUTION
The critical load is not protected while the UPS is in Bypass mode.
CB4
(closed)
Bypass
Static Switch
Rectifier
Input
Bypass
Input
CB1
(open)
Path of Electrical Power
FBP
(closed)
InverterRectifier
Input
Transformer
DC
Link
Output
Transformer
CB2
(open)
CB3
(open)
Output
Battery
Figure 7-3. Path of Current Through the UPS in Bypass Mode
The UPS can be transfered from Normal mode to Bypass mode manually. However,
the UPS switches automatically to Bypass mode whenever the inverter can no longer
supply the critical load. Initially, the static switch fires and conducts power from
breaker FBP to the load. When breaker CB4 closes, the static switch stops
conducting and breaker FBP opens. If the UPS transfers to Bypass mode from Normal
mode due to any reason other than operator intervention, the UPS automatically
attempts to transfer back to Normal mode (up to three times within a ten minute
period). The fourth transfer locks the critical load to the bypass source and requires
operator intervention to transfer.
7-4
Bypass mode is a normal operating mode, not an alarm condition. However, if the
UPS is unable to return to Normal mode following an automatic transfer to Bypass
mode, an alarm condition is recorded.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
7.1.3Battery Mode
The UPS transfers to Battery mode automatically if a utility power outage occurs, or if
the utility power does not conform to specified parameters. In Battery mode, the
battery provides emergency DC power that the inverter converts to AC power. When
the UPS switches to Battery mode, the alarm indications depend on the cause and
condition of the battery charge. The length of time the system can operate in Battery
mode depends on load configuration and battery charge.
Figure 7-4 shows the path of electrical power through the UPS system when the UPS
is operating in Battery mode.
Bypass
Input
UNDERSTANDING UPS OPERATION
CB4
(open)
Bypass
Static Switch
FBP
(open)
Rectifier
Input
InverterRectifier
CB1
(closed)
Transformer
Path of Electrical Power
Input
DC
Link
Output
Transformer
CB2
(closed)
Battery
CB3
(closed)
Figure 7-4. Path of Current Through the UPS in Battery Mode
When the discharging battery voltage reaches the lower limit of UPS operation capability,
the critical load transfers to Bypass mode if it is available. If Bypass input is not available, a
Shutdown Imminent warning occurs. The warning time before critical load loss occurs is
approximately two minutes, depending on load configuration and battery charge.
If incoming power returns to within specified parameters, the UPS automatically returns
to Normal mode and alarm indications clear. However, the process of returning to Normal
mode is not instantaneous. The rectifier gradually draws increasing power from the
incoming utility until Normal mode is achieved.
Output
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
7-5
UNDERSTANDING UPS OPERATION
This page intentionally left blank.
7-6
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
Chapter 8Using the Control Panel
Figure 8Table 8
This chapter describes the UPS control panel, including controls and indicators, and
how to monitor UPS operation. The control panel is a black square area on the front of
the UPS (see Figure 8-1).
Emergency UPM OFF
Pushbutton Switch
LCD Screen
Pushbutton Switches
Backlit Status
Indicators
Mode Key Switch
Push In To Reset
Pushbutton Switch
Battery Switch
Figure 8-1. UPS Control Panel
The following sections describe using the UPS control panel to monitor the UPS.
See Chapter 9, “UPS Operating Instructions,” for use of the operational controls.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
8-1
USING THE CONTROL PANEL
8.1Using the LCD Screen
System Normal
A
ALARM: NONE
NOTICES: NONE
The LCD screen at the top of the control panel provides an operator interface with the
UPS system. Figure 8-2 identifies the display fields discussed in the following
sections.
Uninterruptible Power System
4 MAY 199909:25:42
F
B
C
D
E
Battery
Minutes
Meters
System
Load Amps
Versions
Meters
InputOutput
48.6
Events Statistics Graphics Setup
VAB
VBCVCA
nnn
nnnnnn
IAIBIC
nnn
KVA
nnn
VAB
nnn
KW
nnn
BypassBattery
VBCVCA
nnnnnn
FREQ
nn.n
nnnnnn
PF
0.nn
VAB
VBCVCA
nnn
nnnnnn
IAIBIC
nnnnnnnnn
KVA
nnnKWnnnPF0.nn
V
nnn
G
FREQ
nn.n
IN
nnn
I
+
nn
Figure 8-2. LCD Screen
AThe UPS status area contains three lines that display the current UPS state. The first line shows the present
UPS operational mode. The second line shows the highest level of the current active alarms, and the third line
shows any notices the UPS has posted. (For more information about alarms and notices, see Chapter 11,
“Responding to System Events.”)
BThe battery charge box shows the minutes of battery capacity available.
CThe menu box shows the currently selected menu and lists the options available on that menu. The title at the
top of the menu box is also shown below on the menu bar (E). Press the
andpushbuttons to scroll up and
down through the options in the menu box.
DThe currently selected option is highlighted in the menu box (C). Press the
andpushbuttons to move the
highlight up or down. The data in the information area (G) changes accordingly.
EThe menu bar lists the titles of the menus. The menu title currently displayed in the menu box (C)is
highlighted. When you press the
andpushbuttons to move the highlight left or right, the data in the menu
box (C) and the information area (G) change accordingly.
FThe time stamp shows the current date and time. This date and time are recorded in the Event Log when an
alarm or notice is activated.
GThe information area contains data about UPS status and operation. Select a menu option to display statistics
or graphics.
8-2
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
8.2Using the Pushbuttons
USING THE CONTROL PANEL
Use the LCD screen and the pushbuttons beneath it to:
S Monitor UPS operation
S Look at a log of UPS events (alarms, notices, and commands)
The pushbuttons below the LCD screen are labeled with arrows indicating their
functions:
8.3Adjusting the Contrast
Figure 8-3. LCD Pushbuttons
S Press theandpushbuttons to move through the options in a menu, or to
scroll through the list of alarms and notices in the Event History Log.
S Press theandpushbuttons to move through the menu titles on the menu bar.
Press them simultaneously to silence the horn, or to test the LED lamps behind
the status indicators.
S Press thepushbutton to toggle the use of theandpushbuttons between
the menu box and the information area.
Use the pushbuttons to adjust the contrast on the LCD screen. Hold down the
pushbutton, then press thepushbutton to increase the contrast or the
pushbutton to decrease the contrast.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
8-3
USING THE CONTROL PANEL
8.4Reading the Status Indicators
The six symbols on the left side of the control panel are status indicators. They are
backlit by colored LED lamps, and they work in conjunction with the horn to let you
know the UPS operating status.
NormalThis green symbol illuminates when the UPS is operating in Normal
BatteryThis yellow symbol illuminates when the UPS is operating in Battery
BypassThis yellow symbol illuminates when the UPS is operating in Bypass
NoticeThis yellow symbol illuminates when the system needs attention. The
mode. The power processing unit (PPU) is supplying power to the
critical load.
mode. Because Battery mode is a normal condition of the UPS, the
Normal indicator also remains illuminated.
mode. The critical load is supported by the bypass source. The Normal
indicator is not illuminated when the system is in Bypass mode.
LCD screen shows all active notices. Some notices may be
accompanied by a horn. To silence the horn, press theand
thepushbuttons simultaneously. The Notice indicator may be
illuminated along with other indicators.
AlarmThis red symbol illuminates when a situation requires immediate
StandbyThis yellow symbol illuminates when electricity is present in the PPU of
For more information about horns, see “System Event Horns” on page 11-1.
To test the LED lamps behind the status indicators, press and hold the
pushbuttons simultaneously for three seconds. All the indicators should illuminate
until you release the pushbuttons. If any indicator does not illuminate, its LED lamp
may need to be replaced. Contact your Eaton service representative if you have a
problem with the indicator lamps.
8.5Using the Menu Options
The UPS menus allow you to display data in the information area to help you monitor
and control UPS operation. The following menus and options are available:
S Meters – Displays performance meters for the system or critical load.
S Events – Displays the list of Active System Events and a historical log of
S Statistics – Displays statistical information about UPS operation for the battery,
S Graphics – Displays a real-time graphic representation of the flow of current
S Setup – Allows you to configure the UPS communication port and set the date and
attention. The LCD screen shows the highest priority active alarms. All
alarms are accompanied by a horn. To silence the horn, press the
and thepushbuttons simultaneously. The Alarm indicator may be
illuminated along with other indicators.
the UPS and the Normal indicator is not illuminated. During normal
startup, this indicator illuminates until the the UPS transfers to Normal
mode, at which point the Normal indicator illuminates. During normal
shutdown, the Standby indicator illuminates until all energy in the UPS
is dissipated and shutdown is complete.
and
system events.
load, or line.
through the internal UPS components.
time for the time stamp.
8-4
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
8.5.1System Meters Screen
Figure 8-4 shows the LCD screen as it appears when you first start the UPS. The
Meters menu is displayed in the menu box, with the System option highlighted. In the
information area, the system meters show their current readings.
Uninterruptible Power System
System Normal
ALARM: NONE
NOTICES: NONE
USING THE CONTROL PANEL
4 MAY 199909:25:42
Battery
Minutes
Meters
System
Load Amps
Versions
Meters
48.5
Events Statistics Graphics Setup
VAB
nnn
InputOutput
VBCVCA
nnnnnn
IAIBIC
nnn
KVA
nnn
VAB
nnn
KW
nnn
BypassBattery
VBCVCA
nnnnnn
nnnnnn
PF
0.nn
FREQ
nn.n
VAB
nnn
IAIBIC
nnnnnnnnn
VBCVCA
nnnnnn
KVA
nnnKWnnnPF0.nn
V
nnn
I
nn
+
FREQ
nn.n
IN
nnn
Figure 8-4. System Meters Screen
The Input area shows the phase-to-phase voltage, frequency, and phase current
of the incoming utility, followed by t he kVA, kW, and power factor measurements.
The output area shows the same information for the power being output by the UPS.
The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery
area displays the DC voltage (V) and the DC current (I).
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
8-5
USING THE CONTROL PANEL
8.5.2Load Amps Meters Screen
Select Load Amps from the Meters menu to view a real-time bar graph of the output
current of the UPS. The graph shows the current for each phase.
Figure 8-5 shows the Load Amps Meters screen.
Uninterruptible Power System
System Normal
ALARM: NONE
NOTICES: NONE
4 MAY 199909:25:42
Battery
Minutes
48.5
Meters
System
Load Amps
Versions
Events Statistics Graphics SetupMeters
Output Current
125%
100%
75%
50%
25%
0%
Phase APhase BPhase C
Figure 8-5. Load Amps Meters Screen
8-6
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
8.5.3Software Versions Screen
Select Versions from the Meters menu to view the software versions installed on
the UPS.
Figure 8-6 shows the Software Versions screen.
Uninterruptible Power System
System Normal
ALARM: NONE
NOTICES: NONE
USING THE CONTROL PANEL
4 MAY 199909:25:42
Battery
Minutes
48.5
Meters
System
History
Load Amps
Versions
EventsMeters
Software Versions
Version
Monitor
Rectifier
Inverter
01.17
*****
*****
Statistics Graphics Setup
Figure 8-6. Software Versions Screen
Part Number
143650369
143650347
143650348
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
8-7
USING THE CONTROL PANEL
8.5.4Event History Log Screen
Select History from the Events menu to display the Event History Log. The Event
History Log lists up to 400 system events in chronological order, with the most recent
event listed last. The end of the log (the most recent events) appears when you
display the screen; scroll upward to view older event listings.
Figure 8-7 shows the Event History Log screen.
Uninterruptible Power System
System Normal
ALARM: NONE
NOTICES: NONE
4 MAY 199909:25:42
Battery
Minutes
48.5
Events
History
Active
EventsMeters
Date / Time
May
03
16:41:19.3
03
16:41:20.1
03
16:41:22.4
03
16:41:25.5
03
16:41:26.8
03
16:41:27.8
03
16:41:30.4
16:41:29.1
03
Statistics Graphics Setup
Event History Log
Event Description
COMMAND: Keyswitch On
STATUS: Auto Mode
COMMAND: Rectifier Commanded On
STATUS: Inverter On
STATUS: Rectifier On
STATUS: Output Breaker (CB3) Closed
STATUS: Bypass Breaker (CB4) Open
STATUS: Inverter Normal
Figure 8-7. Event History Log Screen
A small return arrow () appears in the upper right corner of the information area of
the Event History Log screen. This arrow is a reminder that you can press the
pushbutton on the control panel to toggle the scroll bar between the menu box and
the information area. When the scroll bar is in the information area, the return arrow is
in the menu box. When the scroll bar is in the menu box, the return arrow is in the
information area.
8-8
When the scroll bar is in the information area, you can press the
pushbuttons to scroll through the Event History Log.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
and
8.5.5Active System Events Screen
Select Active from the Events menu to display a listing of all system events that are
currently active. The most recent system event is listed first. As events clear, they are
removed from the Active System Events listing.
Figure 8-8 shows the Active System Events screen.
Uninterruptible Power System
System Normal
ALARM: ON BATTERY SHUTDOWN IMMINENT
NOTICES: NONE
USING THE CONTROL PANEL
4 MAY 199909:25:42
Battery
Minutes
48.5
Events
History
Active
Events Statistics Graphics SetupMeters
Active System Events
NOTICE: Input power unavailable
NOTICE: Bypass Not Available
ALARM:Shutdown Imminent
Figure 8-8. Active System Events Screen
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
8-9
USING THE CONTROL PANEL
8.5.6Unit Statistics Screen
Select Unit from the Statistics menu to display a listing of statistics about UPS
operation.
Figure 8-9 shows the Unit Statistics screen.
UPS System Normal
ALARM: NONE
NOTICES: NONE
Uninterruptible Power System
4 MAY 199909:25:42
Battery
Minutes
48.5
Statistics
Unit
Events Statistics Graphics SetupMeters
Number of Incidents:
On Battery < 1 Min.
On Battery 1-4 Min.
On Battery > 4 Min.
Full Batt. Discharge
Building Alarm 1
Building Alarm 2
Building Alarm 3
Building Alarm 4
Building Alarm 5
Building Alarm 6
The left column shows the number of UPS incidents for the current month and since
the start date shown at the top of the information area. The top right column shows
the time that the UPS was on bypass, battery, or generator, and the amount of time
the UPS logic has been functioning since the start date. The lower right column
shows the percent of availability of the UPS and the bypass source.
8-10
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
8.5.7Mimic Screen
Select Mimic from the Graphics menu to display a real-time graphical representation
of the flow of current through the UPS.
Figure 8-10 shows the Mimic screen.
UPS System Normal
Alarm: None
Notice: None
Battery
Percent
100%
USING THE CONTROL PANEL
Uninterruptible Power System
4 MAY 199909:25:42
Bypass
CB1CB3
RectifierInverter
Graphics
Mimic
Events Statistics Graphics SetupMeters
CB2
Battery
Figure 8-10. Mimic Screen
The Mimic screen shows the internal components of the UPS cabinet. The flow of
current through the components is highlighted.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
8-11
USING THE CONTROL PANEL
8.5.8Time Setup Screen
Select Time from the Setup menu to display the Time Setup screen. The Time Setup
screen allows you to set the internal time stamp of the UPS. The time stamp is used
for logging events in the Event History Log. Figure 8-11 shows the Time Setup
screen.
UPS System Normal
ALARM: NONE
NOTICES: NONE
Battery
Minutes
48.5
Uninterruptible Power System
Set Time & Date
DAY DT
MON 07
MON
APRYR99
HR:MN
15:06
4 MAY 199909:25:42
SAVE
YES
Setup
Port 1
Port 2
Time
Language
EventsMeters
Statistics Graphics Setup
Figure 8-11. Time Setup Screen
A small return arrow () appears in the upper right corner of the information area of
the Time Setup screen. This arrow is a reminder that you can press the
pushbutton on the control panel to toggle the scroll bar between the menu box and
the information area. When the scroll bar is in the information area, the return arrow is
in the menu box. When the scroll bar is in the menu box, the return arrow is in the
information area.
When the scroll bar appears in the information area, you can use the pushbuttons to
change the time stamp settings. To change a setting, press the
andpushbuttons
to highlight the setting you want to change. To increase the setting (make it a higher
value), press the
the
pushbutton. To save the settings upon exit from this screen, be sure the Save
pushbutton. To decrease the setting (make it a lower value), press
field is set to YES.
8-12
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
8.5.9Port Setup Screen
Select Port 1 or Port 2 from the Setup menu to display one of the Port Setup screens.
The Port Setup screens allow you to specify settings for the two serial
communication ports on the UPS.
Figure 8-12 shows the Setup Serial Port 1 screen.
UPS System Normal
Alarm: None
Notice: None
Battery
Minutes
48.5
Uninterruptible Power System
Setup Serial Port 1
RATE
MODE
TERMINAL
9600
DATA/STOP
81
USING THE CONTROL PANEL
4 MAY 199909:25:42
HANDSHAKING
XON / XOFF
SAVE
NO
Setup
Port 1
Port 2
Time
Language
EventsMeters
Statistics Graphics Setup
Figure 8-12. Port Setup Screen
A small return arrow () appears in the upper right corner of the information area of
the Port Setup screen. This arrow is a reminder that you can press the
pushbutton on the control panel to toggle the scroll bar between the menu box and
the information area. When the scroll bar is in the information area, the return arrow is
in the menu box. When the scroll bar is in the menu box, the return arrow is in the
information area.
When the scroll bar appears in the information area, you can use the pushbuttons to
change the port configuration. To change a setting, press the
andpushbuttons
to highlight the setting you want to change. To scroll through the available options for
that setting, press the
orpushbutton. To save the settings upon exit from this
screen, be sure the Save field is set to YES.
The setup screens for Port 1 and Port 2 are identical. For detailed information about
configuring the serial ports, see Chapter 12, “Communication.”
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
8-13
USING THE CONTROL PANEL
This page intentionally left blank.
8-14
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
Chapter 9UPS Operating Instructions
Figure 9Table 9
This chapter describes the UPS controls and instructions for operating the UPS
system.
NOTE Before starting the UPS, ensure all installation tasks are complete and an authorized Eaton Customer
Service Engineer has performed a preliminary startup. The preliminary startup verifies all electrical
interconnections to ensure the installation was successful and the system operates properly.
NOTE The following procedures are applicable for systems with the optional internally installed rectifier
input breaker CB1 and inverter output breaker CB3.
NOTE For System Bypass Module (SBM) operation in a multi-module system, refer to the Powerware 9315
Parallel Capacity/Redundant UPS Installation and Operation Manual.
9.1UPS Controls and Indicators
The controls and indicators identified and described in this section are used to control
and monitor UPS operation. Figure 9-1 shows the UPS controls and indicators.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
9-1
UPS OPERATING INSTRUCTIONS
9.1.1Control Panel
9.1.2UPS Circuit Breakers
The UPS control panel contains an LCD screen to display the current UPS system
status. You can view a statistical history and log of system events and display a
real-time graphic representation of power flowing through the system components.
Backlit status indicators show the UPS operating mode and alert you to system
events.
The control panel is described in Chapter 8, “Using the Control Panel.” The Battery
switch controls the application of battery power to the UPS. The Mode key switch,
also located on this panel, is used to start and stop the system and transfer the load
between normal UPS operation and bypass operation. The Emergency UPM Off
pushbutton is located at the top of the control panel, and the Push In To Reset button
for the Emergency UPM Off is located between the Battery switch and the Mode key
switch.
The UPS can contain as many as four circuit breakers:
S UPS Input Breaker (CB1)
S UPS Output Breaker (CB3)
S UPS Bypass Breaker (CB4)
S Backfeed Protection Breaker (FBP)
CB1 controls the input to the UPS rectifier, while CB3 controls the output of the UPS
inverter. CB1 is optional and may be either motor operated or manually controlled.
CB4 and FBP are used in single module applications and are contained in the MBC of
the UPS. CB4 is used as the bypass supply in the event the output of the UPS is not
available and to supply the critical load during maintenance. The FBP is used to
prevent power feedback to the UPS input supply when the UPS is operating in the
Battery mode. These breakers are electrically controlled by the UPS and are automatic
in operation.
Multi-module systems replace the MBC of the UPS with an SBM. Refer to “SBM
Circuit Breakers” in the Powerware 9315 Parallel Capacity/Redundant UPS Installationand Operation Manual.
In addition, a remote mounted external battery disconnect is used to connect the
battery string to the UPS. This disconnect is manually controlled.
9.1.3Emergency UPM Off
An Emergency UPM Off pushbutton is provided for situations where you must
instantaneously control the UPS output. The pushbutton is located on the front of the
UPS for quick access and is covered with a clear plastic shield to prevent accidental
activation. The shield must be raised before pressing the pushbutton. The Emergency
UPM Off pushbutton is described in Chapter 9, “UPS Operating Instructions.”
9-2
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
9.2Starting the UPS
UPS OPERATING INSTRUCTIONS
To start the UPS system:
NOTE This procedure assumes Automode is enabled.
1. Verify that the UPS circuit breakers are set as follows:
UPS Input Breaker (CB1)OPEN
UPS Battery Breaker or Battery Disconnect (CB2)OPEN
UPS Output Breaker (CB3)OPEN
UPS Bypass Breaker (CB4)OPEN
Backfeed Protection Breaker (FBP)OPEN
NOTE When feeder power is applied in Steps 3 and 5, UPS circuit breakers CB1, CB2, CB3, CB4, and FBP
will charge, if not already charged.
2. Ensure the Push In To Reset pushbutton is pressed in.
5. Close the UPS Bypass input feeder circuit breaker. Breakers CB4 and FBP close
as soon as charged.
The critical load is immediately supplied by the bypass source. The UPS is in
Bypass mode, until the inverter turns on and the UPS transfers to Normal mode.
The status indicator on the UPS control panel indicates the UPS is in Bypass
mode.
6. On the UPS, set the Battery switch to ENABLE.
7. If system is equipped with motor operated breaker CB1, proceed to Step 8;
otherwise, proceed to Step 11.
8. On the UPS, turn the Mode key switch to NORMAL for one second.
NOTE If system is equipped with Inrush Protection Option, the inrush contactor closes before UPS
breaker CB1 closes.
9. Confirm UPS breaker CB1 has closed by viewing the breaker position on the LCD
Mimic screen.
The rectifier and the input/rectifier cooling blowers turn on.
10. Proceed to Step 13.
11. Close UPS breaker CB1.
The input/rectifier cooling blowers turn on.
12. On the UPS, turn the Mode key switch to NORMAL for one second.
The rectifier turns on.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
9-3
UPS OPERATING INSTRUCTIONS
13. If system is equipped with motor operated breaker CB2, proceed to Step 14;
otherwise, proceed to Step 16.
14. Confirm UPS Battery Breaker CB2 has closed by viewing the breaker position on
the LCD Mimic screen.
The inverter and output/inverter cooling blowers turn on. When the inverter
reaches full voltage, UPS breaker CB3 closes and breaker CB4 opens supplying
power to the critical load. It takes less than one minute for the UPS to achieve
Normal mode. If UPS is not in Automode, turn the Mode key switch to NORMAL
for one second to transfer UPS to Normal mode.
15. Proceed to Step 18.
16. When the UPS Battery Disconnected alarm and notification is received, close
UPS Battery Disconnect CB2.
17. On the UPS, turn the Mode key switch to NORMAL for one second.
The inverter and output/inverter cooling blowers turn on. When the inverter
reaches full voltage, UPS breaker CB3 closes and breaker CB4 opens supplying
power to the critical load. It takes less than one minute for the UPS to achieve
Normal mode. If UPS is not in Automode, turn the Mode key switch to NORMAL
for one second to transfer UPS to Normal mode.
18. The UPS system is now operating in Normal mode.
9.3Starting the UPS in Bypass Mode
To start the UPS when the inverter output of the UPS is not available and the critical
load needs to be energized:
1. Verify that the UPS circuit breakers are set as follows:
UPS Input Breaker (CB1)OPEN
UPS Battery Breaker or Battery Disconnect (CB2)OPEN
UPS Output Breaker (CB3)OPEN
UPS Bypass Breaker (CB4)OPEN
Backfeed Protection Breaker (FBP)OPEN
2. Close the UPS Bypass input feeder circuit breaker. Breakers CB4 and FBP close
as soon as charged. If the breakers do not close, turn the Mode key switch to
BYPASS for one second.
The critical load is immediately supplied by the bypass source, in Bypass mode,
until the inverter turns on and the UPS transfers to Normal mode. The status
indicator on the UPS control panel indicates the UPS is in Bypass mode.
3. The UPS system is now operating in Bypass mode. No backup is available.
9-4
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
9.4Transferring to Bypass Mode
NOTE In the following step, holding the Mode key switch in the BYPASS position for three seconds
transfers the load to Bypass and shuts down the UPS.
To transfer the critical load to Bypass mode:
1. On the UPS, turn the Mode key switch to BYPASS for one second.
The UPS switches to Bypass mode. If the bypass source is not available, the
power processor unit remains on and an alarm sounds.
3. On the UPS LCD screen, verify that the On Bypass message appears and the
BYPASS Mode indicator illuminates on the control panel
on bypass.
4. On the UPS, turn the Mode key switch to BYPASS for one second.
5. Observe that UPS breaker CB1 and Battery Disconnect CB2 open.
The bypass source supplies the critical load, the power processor unit
de-energizes and cooling blowers shutdown.
. The UPS system is now
Power is present at the UPS breaker CB1 input, until the upstream UPS input feeder circuit breaker is
opened.
9.7Shutting Down the UPS and Critical Load
To perform maintenance or service on the critical load, shut down power to the load:
1. Transfer the critical load to bypass by performing the procedure in paragraph 9.4.
2. Turn off all equipment that is being powered by the UPS.
3. Press the Emergency UPM Off pushbutton on the control panel.
Power is present at the UPS breaker CB1 input, until the upstream UPS input feeder circuit breaker is
opened.
4. Open the UPS input feeder circuit breaker.
9.8Using the UPS Emergency UPM Off Pushbutton
Initiate a UPS Emergency UPM Off using the covered, red Emergency UPM Off
pushbutton on the UPS control panel. This pushbutton is protected by a clear plastic
shield to prevent accidental activation. In an emergency, you can press this
pushbutton to instantaneously control the UPS output. The UPS Emergency UPM Off
pushbutton functions differently, depending on the Emergency Power-off option
specified when ordered. The options available are as follows:
WARNING
WARNING
9-6
S Power to the critical load is de-energized and the UPS powered down. UPS
breakers CB1, CB3, FBP, and Battery Disconnect CB2 trip, and the UPS is cut off
from utility power.
S The critical load is transferred to bypass and the UPS powered down. UPS
breakers CB1, CB3, and Battery Disconnect CB2 trip, and the UPS is cut off from
utility power.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
UPS OPERATING INSTRUCTIONS
The UPS (including Bypass) remains locked off until you reset the Emergency UPM
Off pushbutton.
To restart the UPS after pressing the Emergency UPM Off pushbutton, follow the
procedure in paragraph 9.8.2, “Resetting the UPS System after an Emergency UPM
Off,” before starting the system.
NOTE The remote emergency power-off (REPO) option functions the same way as the Emergency UPM Off
pushbutton on the UPS control panel.
9.8.1Using the UPS Emergency UPM Off Pushbutton
1. Raise the clear plastic shield covering the red UPS Emergency UPM Off
pushbutton on the UPS control panel.
2. Press the Emergency UPM Off pushbutton.
The breakers open (you can hear t hem opening) and the Push In To Reset
pushbutton on the UPS control panel pops out.
9.8.2Resetting the UPS System after an Emergency UPM Off
CAUTION
Do not attempt to restart the system after Emergency UPM Off until the cause of the emergency has been
identified and cleared.
The Push In To Reset pushbutton is a small white button on the UPS control panel.
The Push In To Reset pushbutton pops out when the Emergency UPM Off
pushbutton on the UPS control panel is activated.
To reset the UPS system:
1. Press the Push In To Reset pushbutton until it clicks in and remains recessed.
2. Breakers CB4 and FBP charge and close.
3. Reset tripped circuit breakers on UPS systems with manually controlled CB1 and
CB2 breakers.
4. The UPS system is now reset. To restart the UPS system, see “Starting the
UPS” on page 9-3.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
9-7
UPS OPERATING INSTRUCTIONS
This page intentionally left blank.
9-8
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
Chapter 10Using Features and Options
Figure 10Table 10
The many standard features of your UPS system provide consistent, economical, and
dependable power protection. In addition, you can add available options to enhance
the performance of your system. This chapter provides descriptions of some of the
features and options introduced earlier in this manual. For the customer interface
panel and terminal locations and for terminal wiring information, see:
S Paragraph A.3 starting on page A-12
S Paragraph A.4 starting on page A-22
S Paragraph A.5 starting on page A-28
10.1Building Alarm Monitoring
This standard feature lets you connect the UPS to building alarms, such as smoke
detectors or overtemperature alarms. The customer interface terminals for external
connections are located inside the UPS.
Regardless of how you assign the building alarms, the default is to display the alarms
as Building Alarm 1, Building Alarm 2, Building Alarm 3, and so on, on the UPS control
panel. Use twisted-pair wires for each alarm input and common.
10.2General Purpose Relay Contacts
Two general purpose relay contacts are provided as a standard feature on the UPS.
The alarm contacts (one notice and one alarm) are located inside the UPS on the
customer interface terminal board.
You can specify that each contact be either normally-closed (NC) or normally-open
(NO). If the state of the contact changes from the state you specify as normal, a
signal is issued. You can connect these contacts to equipment at your facility (such as
a light or an alarm bell) to let you know when an alarm is active on the UPS. This
feature is useful if the UPS is located in a remote area where the UPS horn may not
be heard immediately.
Contacts should not be operated in excess of 30 Vac or 42.4V peak AC or DC @ 1A maximum.
CAUTION
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
10-1
USING FEATURES AND OPTIONS
10.3Optional Remote Monitor Panel
The optional Remote Monitor Panel (RMP) monitors the UPS system operating status
and alarm condition from virtually any location within your facility, up to
152.4m (500 ft) from the UPS. You can flush-mount or surface-mount an RMP on a
desktop, wall, or wherever you have a serial interface line. Figure 10-1 shows an
RMP.
Figure 10-1. RMP
10-2
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
The RMP contains a local horn and the following backlit status indicators:
SYSTEM NORMAL
The UPS is energized (either with utility power or battery backup) and is
supplying conditioned power to the critical load.
NO REDUNDANCY
This indicator applies only to parallel systems when one cabinet is not
functioning. This feature is not available on this system.
ON GENERATOR
This alarm means that the UPS input and bypass are being supplied by the
power from the generator, instead of from the utility power.
ON BYPASS
The bypass source is supplying the critical load. Usually this means that
the UPS is not energized. The load is not protected in Bypass mode, and a
horn sounds after 30 seconds.
UPS ALARM
The UPS system is issuing an alarm. Conditions that affect the current UPS
mode are indicated by the indicators and horn on the UPS.
USING FEATURES AND OPTIONS
ON BATTERY
The UPS battery backup is supplying the critical load. The utility power is
either interrupted or out of specification. The SYSTEM NORMAL indicator
is also lit.
BYPASS UNAVAILABLE
The UPS system is in Normal mode, but a bypass source is not within
specification. A horn sounds after 30 seconds.
SHUTDOWN IMMINENT
The UPS is preparing to shut down because the UPS is in Battery mode
and the DC voltage is approaching its low limit.
This indicator is accompanied by a horn.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
10-3
USING FEATURES AND OPTIONS
10.4Optional Relay Interface Module
The optional Relay Interface Module (RIM) uses relay contact closures to indicate the
operating status and alarm condition of the Parallel Capacity/Redundant system.
Figure 10-2 shows the RIM with its four 15-pin connectors labeled J1 through J4.
Figure 10-2. RIM
The RIM can provide the following signals:
UPS AVAILABLEPins 1 and 12Contacts are closed when the UPS is offline.
UPS OFF LINEPins 3 and 13Contacts are closed when the UPS is operating in Normal
mode.
BATTERY WEAKPins 5 and 14Contacts are closed when approximately two minutes of
battery time is remaining, before the critical load is lost.
UTILITY FAILUREPins 6 and 15Contacts are closed when Utility Failure is detected.
10-4
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
10.5Optional Supervisory Contact Module
An optional Supervisory Contact Module (SCM) establishes an interface between the
Parallel Capacity/Redundant system manufacturer’s equipment and the customer’s
monitor. This interface allows the customer to monitor operational status of the
Parallel Capacity/Redundant system equipment. Figure 10-3 shows the SCM, input
connections on TB1, and output connections on TB2.
USING FEATURES AND OPTIONS
TB2
Figure 10-3. SCM
The SCM provides signals for the following indications:
SYSTEM NORMALTB2-1 through TB2-3
NO REDUNDANCYTB2-4 through TB2-6
ON GENERATORTB2-7 through TB2-9
BYPASS NOT AVAILABLETB2-10 through TB2-12
ON BATTERYTB2-13 through TB2-15
UPS ALARMTB2-16 through TB2-18
ON BYPASSTB2-19 through TB2-21
SHUTDOWN IMMINENTTB2-22 through TB2-24
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
10-5
USING FEATURES AND OPTIONS
This page intentionally left blank.
10-6
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
Chapter 11Responding to System Events
Figure 11Table 11
When the UPS system is operating in Normal mode, it continually monitors itself and
the incoming utility power. In Battery or Bypass modes, the UPS may issue alarms to
let you know exactly what event caused the change from Normal mode. System
events on the UPS can be indicated by horns, indicators, messages, or all three.
Select Active from the Events menu on the LCD screen to display the Active System
Events screen. This screen shows any currently active alarms, notices, or commands.
11.1System Event Horns
The system event horn beeps according to the type of event it is signifying:
S When the UPS detects an alarm that requires your attention, the horn beeps at
half-second intervals.
S When a notice occurs, the horn beeps at two-second intervals.
11.2System Event Indicators
The status indicators on the UPS control panel work in conjunction with the horn to
let you know when the UPS system is operating in any mode other than Normal
mode. Only the Normal indicator is illuminated during normal UPS system operation.
The others illuminate to indicate alarms or events. When an alarm occurs, first check
these indicators to see what type of event has taken place. For descriptions of the
status indicators, see paragraph 8.4 on page 8-4.
11.3System Event Messages
When a system event occurs, a message is added to the Event History Log. A
message may also appear on the UPS control panel. The Event History Log contains
all system event messages, whether or not they were displayed on the control panel.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
11-1
RESPONDING TO SYSTEM EVENTS
This page intentionally left blank.
11-2
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
Chapter 12Communication
Figure 12Table 12
This chapter describes the communication features of the Powerware 9315 UPS and
provides information about connecting hardware, configuring the ports, changing
settings, and changing modes.
12.1Locating the Customer Interface Panel
The customer interface panel inside the UPS contains:
S Two serial communication ports, one DB-9 and one DB-25.
The ports provide a computer interface to a Remote Monitor Panel (RMP), Relay
Interface Module (RIM), Supervisory Contact Module (SCM), or remote terminal
and/or printer.
S A 120 Vac, 0.2A convenience outlet for powering a modem used for remote
notification.
S An X-Slot communication bay for installing an optional X-Slot card.
See Appendix A for the UPS customer interface panel location.
12.2Connecting Equipment to a Serial Port
The UPS serial communication ports are designed to accept a wide variety of data
communication equipment (DCE), such as terminals, printers, and computers. Use an
appropriate cable for the type of equipment you are connecting to the UPS. Cables
should be no longer than 16m (50 ft) and have a male connector.
Port 1 cable pins are identified in Figure 12-1 and the pin functions are described in
Table 12-1. Port 2 cable pins are identified in Figure 12-2 and the pin functions are
described in Table 12-2.
+24V
RS-232 TXD
RS-232 RXD
NOT USED
RETURN
Figure 12-1. Port 1 (DB-9)
Table 12-1. Pin Assignments for Port 1 (DB-9)
Pin NumberSymbolFunctionComments
1+24V+24 Volts DC
2TXDTransmit DataInput to UPS
3RXDReceive DataOutput from UPS
5RTNReturn
7485+RS-485 + Data
8485–RS-485 – Data
1
2
3
4
5
6
7
8
9
NOT USED
485+
485–
RETURN
9RTNReturn
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
12-1
COMMUNICATION
GND
1
RS-232 TXD
RS-232 RXD
RS-232 RTS
RS-232 CTS
RS-232 DSR
RTN
+12V
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
14
2
15
3
16
4
17
5
18
6
19
7
20
8
21
9
22
10
23
11
24
12
25
13
Figure 12-2. Port 2 (DB-25)
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
RS-232 DTR
NOT USED
–12V
NOT USED
NOT USED
NOT USED
Table 12-2. Pin Assignments for Port 2 (DB-25)
Pin NumberSymbolFunctionComments
1GNDChassis Ground
2TXDTransmit DataInput to UPS
3RXDReceive DataOutput from UPS
4RTSRequest to SendInput to UPS
5CTSClear to SendOutput from UPS
6DSRData Set ReadyOutput from UPS
7RTNReturn
8+12V+12 VoltsOutput from UPS - always true
20DTRData Terminal ReadyInput to UPS - typically not used by UPS
22–12V–12 VoltsOutput from UPS - always true
NOTE Pins 5 and 6 are tied together internally.
12-2
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
12.3Configuring the Serial Ports
Configure the communication port using the LCD screen and pushbuttons on the UPS
control panel.
Select Port 1 or Port 2 from the Setup menu to display one of the Setup Port screens.
The screens for Port 1 and Port 2 are identical, and allow you to specify settings for
the two serial communication ports. Figure 12-3 shows the Setup Serial Port 1
screen.
UPS System Normal
ALARM: NONE
NOTICES: NONE
Battery
Percent
100%
COMMUNICATION
Uninterruptible Power System
15 JUL 1998 09:25:42
Setup Serial Port 1
Setup
Port 1
Port 2
Time
Mode
TERMINAL
EventsMeters
Statistics Graphics Setup
Rate
9600
Data/Stop
81
Handshaking
XON / XOFF
Save
NO
Figure 12-3. Setup Serial Port 1 Screen
A small return arrow () appears in the upper right corner of the Setup Port screen.
This arrow is a reminder that you can press thepushbutton on the control panel
to toggle the pushbuttons between the menu box and the information area.
If the scroll bar is in the menu box, press the
pushbutton to toggle to the
information area. The first setting (Mode) is highlighted. Press theorpushbutton
to move the highlight to the setting you want to change. To scroll through the
available options for that setting, press t he
orpushbutton.
To save the settings upon exit from this screen, be sure the Save field is set to YES.
Table 12-3 shows which options are available for each port. The sections that follow
describe the configuration settings you can change.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
12-3
COMMUNICATION
Table 12-3. Options Available for Each Communication Port
Port 1Port 2Options
XXTerminal Mode
XXSystem Configuration Mode
XCalibration Mode
XComputer Mode
XRemote Monitor Mode
XXBaud rate of 300, 1200, 2400, 4800, 9600, or 19200
XXData size/stop bits of 8/1 or 8/2
XData size/stop bits of 7/1 or 7/2
XXDisabled handshaking
XXXON/XOFF handshaking
12.3.1Modes
Each communication port operates in one of the following modes:
S Terminal Mode – System events are logged immediately as they occur.
S System Configuration Mode – Allows you to set building alarms, battery tests, and
other UPS functions. (Check with your sales or service representative for
availability.)
S Calibration Mode – Used only by service personnel; available for Port 2 only.
S Computer Mode – Provides an Eaton proprietary Binary Computer Mode (BCM)
Interface facility monitoring or network communication via a Powerware
.ConnectUPS Card. Available for Port 2 only.
S Remote Monitor Mode – Sends all system event information to an RMP, RIM, or
SCM; available for Port 1 only.
Port 1 and Port 2 cannot be in the same mode simultaneously; they must always be
operating in different modes. The modes are described later in this chapter.
12.3.2Rate
The baud rate determines the speed of data transferred between the UPS and the
connected equipment. For Remote Monitor mode, the baud rate must be set to 300.
All other modes should operate at t he highest baud rate available with the connected
equipment.
You can select a baud rate of 300, 1200, 2400, 4800, 9600, or 19200.
12-4
NOTE 300 baud is not recommended for any mode except Remote Monitor.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
12.3.3Data/Stop
The data size and stop bits of the equipment connected to this port determine the
number of bits transmitted per ASCII character. The data size and stop bits you
specify depend on the configuration of your equipment.
For Port 1, the data size must be set to 8, with 1 or 2 stop bits. Settings of 7 data
bits/1 stop bit and 7 data bits/2 stop bits are available for Port 2.
NOTE When connecting a computer running a terminal emulation program, set your equipment to NO
PARITY.
12.3.4Handshaking
This setting controls handshaking. You can select XON/XOFF or Disabled for this
setting.
S XON/XOFF – If handshaking is enabled, the UPS uses special characters (XON and
XOFF) to handshake with the host terminal. The XON character is defined to be
ASCII value 11 hex, and the X OFF character is defined to be ASCII value 13 hex.
Upon reception of an XOFF command, the UPS halts transmission until an XON
command is received. In the same way, if the terminal receives an XOFF
command, the UPS expects the terminal t o halt transmission until the UPS
sends an XON command.
S Disabled (No Handshaking) – If handshaking is disabled, the UPS transmits and
receives data via the serial port, ignoring all inputs from handshaking lines.
COMMUNICATION
12.3.5Save
Set to YES to save any changes to configuration settings upon exit from the Setup
screen. Set to NO if you do not want to save any changes.
12.3.6Default Settings
The following are the default configuration settings for the serial communication
ports:
Port 1Remote Monitor300 baud8/1Handshaking Disabled
Port 2Terminal9600 baud8/1Handshaking Disabled
Each communication port on the UPS operates in one of five modes that you select
when configuring the port using the Setup Port screen.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
12-5
COMMUNICATION
12.4Terminal Mode
In this mode, system events are continually logged through the serial port to the
device connected to the port. Port 2 operates by default in Terminal mode.
The Event History Log entries contain a time and date stamp and the alarm text
message. Terminal mode uses this format for printing alarm entries:
MMM DDHH:MM:SS.hhKYWD MESSAGE ::::<CR> <LF>
SymbolDescription
MMMMonth (3 letters)
DDDay (2 digits)
HHHour (2 digits)
MMMinute (2 digits)
SSSecond (2 digits)
hhHundredths of Second (2 digits)
KYWDKeyword (ALARM, NOTICE, COMMAND, or STATUS)
::::System Diagnostic Information
<CR>Carriage Return Character (ASCII 13)
<LF>Line Feed (ASCII 10)
An alarm message is prefixed by the word CLEAR whenever an alarm is entered into
the Event History Log with a cleared status.
12.4.1Printing Selected Information
NOTE To use a key combination, hold down the Control key and press the letter key.
If a port is operating in Terminal mode and is connected to a computer, use the
following key combinations at any time to print selected information:
[Ctrl]+[P]Prints the entire log with a header
[Ctrl]+[M]Prints the current system meters with a header
[Ctrl]+[A]Prints all system information
[Ctrl]+[B]Prints Battery Test Log
12-6
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
12.4.2Entire Log [Ctrl]+[P]
The [Ctrl]+[P] key sequence prints the entire UPS Event History Log at the time the
data is requested. The printout begins with the oldest alarm entry in the queue and
ends with the most recent. Any alarms that occur while the Event History Log is
printing are included in chronological order. The Event History Log lists up
to 400 system events. Figure 12-4 shows a sample Event History Log printout.
Uninterruptible Power System
COMMUNICATION
UPS System Normal
Alarm:None
Notice:None
Event History Log
MAY 12
JUN 04
16:41:19.3
12
16:41:29.1
12
16:41:42.4
12
16:42:05.5
12
16:42:46.8
12
16:43:15.8
12
16:43:42.4
12
16:44:29.1
12:16:35.9
03 NOV 199714:23:45
Event Description
COMMAND: Keyswitch On
STATUS:Auto Mode
COMMAND: Rectifier Commanded On
STATUS:Inverter On
0421
1000
2030
2202
STATUS:Rectifier On
STATUS:Inverter Contactor (3) Closed
STATUS:Bypass Contactor (K4) Open
STATUS:Inverter Normal
324001
NOTICE:Room High Temperature
Figure 12-4. Event History Log
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
12-7
COMMUNICATION
12.4.3Meters Printout [Ctrl]+[M]
The [Ctrl]+[M] key sequence prints the current readings of the UPS system meters.
The Input area shows the phase-to-phase voltage, frequency, and phase current of
the incoming utility, followed by the kVA, kW, and power factor measurements. The
output area shows the same information for the power being output by the UPS. The
Bypass area shows the phase-to-phase voltage of the bypass source. The Battery
area displays the DC voltage (V) and the DC current (I). Figure 12-5 shows a sample
System Meters printout.
Uninterruptible Power System
UPS System Normal
Alarm:None
Notice:None
InputOutput
VAB
VAB
VBC VCA
480
480 480
IAIBIC
640
KVA
530
KW
505
FREQ
60.0
640640
PF
0.95
VBCVCA
480
480480
IAIBIC
480480480
KVA
400KW320PF0.80
BypassBattery
VAB
VBCVCA
480
480480
Figure 12-5. System Meters Screen
540
12.4.4System Information Printout [Ctrl]+[A]
The [Ctrl]+[A] key sequence prints a listing of all available serial data. This printout
contains the information shown on the Event History Log and System Meters screens
of the UPS (see Figure 12-4 and Figure 12-5).
03 NOV 199714:22:45
FREQ
60.0
IN
0
V
+
I
0
12-8
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
12.5System Configuration Mode
The System Configuration mode allows you to modify special functions in your UPS.
These functions include programming of building alarms, customizing building alarm
messages, adjusting the nominal output voltage, and scheduling battery tests. The
menus provided and their function are described in the following sections.
12.5.1System Configuration Mode Main Menu
When the System Configuration mode is selected with a terminal attached, you are
prompted to enter the password for this mode:
Please Enter Password:
The default password is POWER1. You may modify this password using the change
password function in the following menu. When the valid password is entered, the
Main menu is displayed:
Program Mode Main Menu
1. Program Building Alarms
2. Program Unit Name
3. Adjust Output Voltage
4. Change Password
5. Battery Test Setup
6. Modify Low Battery Time
7. Exit Program Mode
Enter Selection:
COMMUNICATION
12.5.2Program Building Alarms
This menu provides access to all the functions available in the System Configuration
mode. If 1 is entered at the prompt, you can program the building alarm functions:
Program Building Alarms
1. Enable/Disable Default Functions
2. Customize Alarm Messages
3. Return to Main Menu
Enter Selection:
12.5.3Enable/Disable Default Functions
From this menu you may either enable the building alarms for general functions or
special functions, such as On Generator, Go To Bypass, and Go To UPS. You may
also customize the alarm messages from this menu. When 1 is selected, the
following menu is displayed:
Enable/Disable Default Functions
1. Enable/Disable Go To Bypass
2. Enable/Disable Go To UPS
3. Enable/Disable On Generator
4. Enable/Disable Building Alarm
5. Return to Program Building Alarms Menu
Enter Selection:
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
12-9
COMMUNICATION
If you select 1, 2,or3 from t his menu, the following menu is displayed:
Enable/Disable (Function)
Enabled Building Alarm Number(s) 1 4
Enter E# to Enable Building Alarm Number #
Enter D# to Disable Building Alarm Number #
Enter <CR> for No Change
Enter Selection:
Where (Function) indicates the function the building alarm is being programmed for.
The text following the “Enabled Building Alarm Number(s)” label indicates which
building alarms are currently enabled for the function. In this example, Building
Alarms 1 and 4 are enabled. A building alarm can only be programmed for one special
function at a time from these menus. Enabling a building alarm for a special function
automatically enables the alarm. If you disable a special function, the building alarm is
also disabled.
If you select entry 4 from this menu, the following menu is displayed:
Enable/Disable Building Alarm
Enabled Building Alarm Number(s) 1 4
Enter E# to Enable Building Alarm Number #
Enter D# to Disable Building Alarm Number #
Enter <CR> for No Change
Enter Selection:
The text following the “Enabled Building Alarm Number(s)” label indicates which
building alarms are currently enabled. In this example, Building Alarms 1 and 4 are
enabled.
12.5.4Customize Alarm Messages
If Customize Alarm Message (option 2) is selected from the Program Building Alarms
menu, you can select a custom message for a building alarm or disable a previously
enabled building alarm custom message. When this entry is selected, the following
menu is displayed:
Customize Alarm Messages
Enabled on Building Alarm Number(s) 2 3
Enter Building Alarm Number:
This example indicates that there are custom messages enabled for Building Alarms 2
and 3. When a building alarm number is entered, the message being used by the
software is displayed (either a custom message or the default message indicated by
the list of enabled custom messages). If 1 was entered at the prompt, the following is
displayed:
12-10
Building Alarm Active Message:Building Alarm 1 (default
message)
Enter New Message or <CR> for No Change:
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
COMMUNICATION
At this level you can enter a custom message, 30 characters maximum, to display
when Building Alarm 1 is activated. If a custom message is entered to activate the
building alarm, a custom message should also be entered to deactivate the building
alarm. After the message or a carriage return is entered, the following is displayed:
Building Alarm Clear Message:Clear Building Alarm 1 (default
message)
Enter New Message or <CR> for No Change:
At this prompt, the user should enter the custom message for the building alarm
deactivation state. When a message or a carriage return is entered, the following is
displayed:
Enter E to Enable Custom Message
Enter D to Disable Custom Message
Enter <CR> for No Change
Enter Selection:
If E is entered at the prompt, the custom messages are used for the building alarm. If
D is entered, the default messages are used for the building alarm.
12.5.5Program Unit Name
If Program Unit Name (option 2) is selected from the Main menu (see page 12-9), the
following is displayed:
Program Unit Name
Unit Name:
Enter New Name or <CR> No Change:
NOTE The Unit Name is 45 characters maximum, including spaces and punctuation.
NOTE If the user wants to center the text portion of the name, the appropriate number of leading spaces
should be included when entered.
The current Unit Name is displayed. This name is displayed on the second line of the
display and in the headers of printouts from Terminal mode. If a change is desired,
the new Unit Name should be entered at the prompt.
12.5.6Change Password
If Change Password (option 4) is selected from the Main menu (see page 12-9), the
following menu is displayed:
Change Password
Enter New Password:
Verify New Password:
<CR> to return with no change.
NOTE The password must be six characters in length.
The password is changed if the user enters and verifies a new password.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
12-11
COMMUNICATION
12.5.7Battery Test Setup
If Battery Test Setup (option 5) is selected from the Main menu (see page 12-9), the
following menu is displayed:
NOTE If a message stating “Battery Test Requires Calibration” appears, please notify your Eaton service
representative for proper calibration.
Battery Test Setup
1. Setup One-time Delayed Battery Test
2. Setup Monthly Battery Test
3. Setup Quarterly Battery Test
4. Cancel Pending Battery Test
5. Display Next Scheduled Battery Test
6. Return to Main Menu
Enter Selection:
This menu allows you to schedule battery tests, review scheduled battery tests, or
cancel pending battery tests. If you select 1, 2,or3 from this menu, the following
menu is displayed:
Enter Starting Month (1–12):
Enter Day of Week, Sunday = 1, (1–7):
Enter Week of Month (1–5):
Enter Hour of Test (0–23):
Enter Minute of Test (0–59):
<CR> with no entry will return to Battery Test Setup Menu.
NOTE Follow each entry with a carriage return <CR>.
Enter the information at the prompt with a carriage return to schedule the battery
test.
If 4 is selected from the Battery Test Setup menu, you are prompted to enter Y to
cancel all pending tests. This selection will only cancel pending tests and will not stop
a test currently in progress.
If 5 is selected from the Battery Test Setup menu when a Battery Test is scheduled,
the following is displayed:
Next Battery Test Scheduled
WK DAY MON HR:MN
4FRI MAR 15:34
Enter <CR> to return to Battery Test Setup Menu
12-12
If 5 is selected from the Battery Test Setup menu when a Battery Test is not
scheduled, the following is displayed:
No Battery Test Scheduled
Enter <CR> to return to Battery Test Setup Menu
NOTE The unit will only perform one battery test in any 24 hour period.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
12.5.8Modify Low Battery Time
12.6Calibration Mode
COMMUNICATION
If Modify Low Battery Time (option 6) is selected from the Main menu (see
page 12-9), the following menu is displayed:
Modify Low Battery Time
Low Battery Time (Minutes):004
Enter New Low Battery Time:
<CR> to return with no change.
NOTE Low Battery Time should be no greater than 999.
To change the Low Battery Time warning level, enter a new time.
Calibration mode is used by factory and field service personnel to calibrate system
meters. Factory test engineers calibrate the UPS meters prior to shipping so the UPS
arrives at your site correctly calibrated. After use, field service personnel may need to
use Calibration mode to recalibrate one or more meter settings.
12.7Computer Mode
12.8Remote Monitor Mode
NOTE Calibration mode is for use by service personnel ONLY. To prevent inadvertent modification, this
mode can be accessed only by trained personnel.
Computer mode provides a computer interface which gives your system compatibility
with system monitoring and network products. For a list of products available, contact
your Eaton sales representative.
Remote Monitor mode provides the interface for the RMP, RIM, or SCM described
earlier. Port 1 operates by default in Remote Monitor mode.
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
12-13
COMMUNICATION
12.9eNotify Service
The Powerware 9315 UPS supports Eaton’s eNotify Remote Monitoring and
Diagnostic Service. The eNotify Service is included at no charge during the first year
of operation (warranty period), and also with the purchase of an Eaton PowerTrust
Support Agreement after the initial warranty expires. eNotify and support agreement
availability or specific features may vary by market; for more information, refer to:
www.powerware.com/enotify/.
12.9.1eNotify Service Features
The eNotify Service provides proactive monitoring and a monthly report detailing the
ongoing health of your Powerware 9315 UPS:
S Proactive monitoring, called Anomaly Detection, automatically analyzes the status
of the Powerware 9315 UPS on a daily basis. All data gathered from the unit,
current and historical, is analyzed at the Customer Reliability Center (CRC) for
trending issues. A set of factors, or rules, compared against your UPS’s data can
indicate a potential impending failure and trigger an appropriate anomaly
notification to a CRC Analyst. Critical events are checked for additional anomalies.
Through this service, the CRC can take pre-emptive, corrective action to ensure
the highest level of availability of your Powerware 9315 UPS.
S The Customer Monitoring Report delivers information about Eaton’s analysis of
your Powerware 9315 UPS on a monthly basis. Depending on the model, the
report provides detailed information about voltages, loads, external factors such as
temperature and humidity, the attached batteries, and system availability. All of
these factors contribute to the Relative Health Index (RHI) score that allows you to
compare your unit’s health relative to Eaton’s optimum Powerware UPS operating
levels.
t
12.9.2Installing eNotify Service
A quick start guide and self-installation wizard tool are available on both the Software
Suite CD included with the Powerware 9315 UPS documentation and on the Web at:
www.powerware.com/enotify/. For the latest updates, installation tips, and
information on connecting eNotify, visit the eNotify Web page. For installation support
or questions about the eNotify Service, contact crctriagegroup@eaton.com.
The eNotify Service relies on a ConnectUPS-X Web/SNMP Card (or Power Xpert
card) installed with the UPS sending one-way status and event e-mails to Powerware
Remote Monitoring servers that analyze and store the data. Those servers also take
the appropriate actions of sending notifications and reports. The ConnectUPS Card
gathers information from the UPS directly and from any external sensors that are
attached. The card also records all events that are generated by the UPS. This data is
stored within the non-volatile memory logs on the ConnectUPS Card.
The eNotify Service runs on common protocols and transport mechanisms, making
the connectivity between the Powerware 9315 UPS and the Powerware Remote
Monitoring servers easy to set up. By using common e-mail transport mechanism,
you do not have to open your network to proprietary or potentially unsecure protocols
and transports.
®
12-14
EATON Powerware®9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 1 www.powerware.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.