Eaton 5P 750, 5P 1000, 5P 1500, 5P 1550G, 5P 850G Installation And User Manual

...
ENGLISH
Tower models
5P 750 5P 1000 5P 1500 5P 850G 5P 1550G
Copyright © 2012 EATON All rights reserved.
Service and support:
Call your local service representative
620-00082-01-us (en)
1U Rack models
5P 550 R 5P 750 R 5P 1000 R 5P 1500 R 5P 850G R 5P 1550G R
Installation and user manual
Page 2
620-00082-01-us (en)
Page 3
620-00082-01-us (en)
ENGLISH
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
Important instructions that must always be followed.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed lead acid batteries and must be disposed as it's explain in this manual. For more information, contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
Information, advice, help.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries.
The 5P models that are covered in this manual are intended for installation in an environment within 0 to 40°C, free of conductive contaminant.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Certication Standards
• UPS directives: UL 1778 4th edition (UL listed).
• Performance: IEC 62040-3: 2001.
• Radiated emission: FCC CFR 47 part 15 subpart B, Class A.
• Surges withstand ability: IEEE ANSI C62.41 Category A2 (UL Listed).
Page 4
620-00082-01-us (en)
Safety of Persons
• The system has its own power source (the battery). Consequently, the power outlets may be energized even if the systems is disconnected from the AC power source.
• Dangerousvoltagelevelsarepresentwithinthesystem.Itshouldbeopenedexclusivelybyqualied
service personnel.
• The system must be properly grounded.
• The battery supplied with the system contains small amounts of toxic materials.
To avoid accidents, the directives listed below must be observed:
- servicing of batteries should be performed or supervised by personnel knowledgeable about betteries and the required precautions.
- when replacing batteries, replace with the same type and number of batteries or battery packs.
-donotdisposeofbatteriesinare.Thebatteriesmayexplode.
- batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.
Precautions must be taken for all handling:
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground.
Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance (applicable to equip­ment and remote battery supplies not having a grounded supply circuit).
Product Safety
• The UPS connection instructions and operation described in the manual must be followed in the indicated order.
• A protection circuit breaker must be installed upstream and be easily accessible. The system can be disconnected from the AC power source by opening this circuit breaker.
• Check that the indications on the rating plate correspond to your AC powered system and to the actual electrical consumption of all the equipment to be connected to the system.
• For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall be easily accessible
• Never install the system near liquids or in an excessively damp environment.
• Never let a foreign body penetrate inside the system.
• Never block the ventilation grates of the system.
• Never expose the system to direct sunlight or source of heat.
• If the system must be stored prior to installation, storage must be in a dry place.
• The admissible storage temperature range is -15 ºC to +50 ºC.
• The system is not for use in a computer room AS DEFINED IN the standard for the Protection
of Information Technology Equipment, ANSI/NFPA 75 (US installations only).
Contact Eaton resellers to order a special battery kit, if needed to meet the ANSI/NFPA 75 requirement.
Special Precautions
• All handling operations will require at least two people (unpacking, installation in rack system).
• Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be
energized for a period of 24 hours, at least once every 6 months (for a normal storage temperature less than 25 °C). This charges the battery, thus avoiding possible irreversible damage.
• During the replacement of the Battery Module, it is imperative to use the same type and number of element as the original Battery Module provided with the UPS to maintain an identical level of performance and safety. In case of doubt, don’t hesitate to contact your EATON representative.
Page 5
620-00082-01-us (en)
ENGLISH
Contents
1. Introduction ....................................................................................... 6
1.1 Environmental protection ...............................................................................................6
2. Presentation ...................................................................................... 7
2.1 Standard installations .........................................................................................................7
2.2 Tower rear panels ............................................................................................................... 8
2.3 Rack rear panels ................................................................................................................9
2.4 Control panel ................................................................................................................... 10
2.5 LCD description ............................................................................................................... 11
2.6 Display functions .............................................................................................................12
2.7 User settings ................................................................................................................... 12
3. Installation ...................................................................................... 14
3.1 Unpacking and contents check ........................................................................................ 14
3.2 Battery module connection (Tower) ................................................................................. 15
3.3 Battery module connection (Rack) ................................................................................... 15
3.4 Installation of tower models ............................................................................................ 16
3.5 Installation of rack model for 2 post (option) ...................................................................16
3.6 Installation of rack models (550 R) .................................................................................. 17
3.7 Installation of rack models ............................................................................................... 17
3.8 Installation of rack model for wall mounting ....................................................................18
3.9 Communication ports ..................................................................................................... 19
4. Operation......................................................................................... 20
4.1 Start-up and Normal operation .........................................................................................20
4.2 Starting the UPS on Battery ............................................................................................20
4.3 UPS Shutdown ................................................................................................................20
4.4 Operation on Battery Power ............................................................................................20
4.5 Return of AC Input Power ................................................................................................ 21
4.6 UPS remote control functions .........................................................................................21
5. Maintenance ................................................................................... 22
5.1 Troubleshooting ................................................................................................................ 22
5.2 Battery-module replacement ...........................................................................................23
6. Appendices ...................................................................................... 25
6.1 Technical specications ....................................................................................................25
6.2 Glossary ...........................................................................................................................27
Page 6
620-00082-01-us (en)
1. Introduction
Thank you for selecting an EATON product to protect your electrical equipment.
The 5P range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features
of your UPS (Uninterruptible Power System).
Before installing your 5P, please read the booklet presenting the safety instructions. Then follow the instructions in this manual.
To discover the entire range of EATON products and the options available for the 5P range, we invite you to visit our web site at www.eaton.com/powerquality or contact your EATON representative.
1.1 Environmental protection
EATON has implemented an environmental-protection policy. Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
• The cardboard we use comprises over 50% of recycled cardboard.
• Sacks and bags are made of polyethylene.
• Packingmaterialsarerecyclableandbeartheappropriateidenticationsymbol
01
PET
Materials Abbreviations Number in
the symbols
Polyethylene terephthalat PET 01
High-density polyethylene HDPE 02
Polyvinyl chloride PVC 03
Low-density polyethylene LDPE 04
Polypropylene PP 05
Polystyrene PS 06
Follow all local regulations for the disposal of packing materials.
End of life
EATON will process products at the end of their service life in compliance with local regulations. EATON works with companies in charge of collecting and eliminating our products at the end of
their service life.
Product
The product is made up of recyclable materials. Dismantling and destruction must take place in compliance with all local regulations concerning waste. At the end of its service life, the product must be transported to a processing center for electrical and
electronic waste.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations concerning batteries.
The battery may be removed to comply with regulations and in view of correct disposal.
01
PET
Page 7
620-00082-01-us (en)
ENGLISH
2. Presentation
2.1 Standard installations
Tower models
D
H
W
Description Weights
(lb/kg)
Dimensions (inch/mm) D x W x H
5P 750 22.7 / 10.3 13.6 x 5.9 x 9.1 / 345 x 150 x 233 5P 1000 24.4 / 11.05 13.6 x 5.9 x 9.1 / 345 x 150 x 233 5P 1500 35.3 / 16.01 17.5 x 5.9 x 9.1 / 445 x 150 x 233 5P 850G 21.9 / 9.9 13.6 x 5.9 x 9.1 / 345 x 150 x 233 5P 1550G 35.2 / 15.9 17.5 x 5.9 x 9.1 / 445 x 150 x 233
Rack models
H
W
D
Description Weights
(lb/kg)
Dimensions (inch/mm) D x W x H
5P 550 R 17.80 / 8.08 14.3 x 17.2 x 1.7 / 363 x 438 x 43 5P 750 R 30.60 / 13.88 20.0 x 17.2 x 1.7 / 509 x 438 x 43 5P 1000 R 32.50 / 14.72 20.0 x 17.2 x 1.7 / 509 x 438 x 43 5P 1500 R 43.50 / 19.72 21.8 x 17.2 x 1.7 / 554 x 438 x 43 5P 850G R 30.4 / 13.8 20.0 x 17.2 x 1.7 / 509 x 438 x 43 5P 1550G R 42.7 / 19.4 21.8 x 17.2 x 1.7 / 554 x 438 x 43
Page 8
620-00082-01-us (en)
2. Presentation
2.2 Tower rear panels
5P 750 / 5P 1000
8
5
2
1
4
6a
3
6b
7
9
5P 1500
5
2
1
4
6a
3
6b
7
8
9
5P 850G
3
2
1
4
7
6a
6b
5
8
5P 1550G
2
1
4
5
6a
3
6b
8
7
(1) USB communication port (2) RS232 communication port (3) Slot for optional communication card (4) Connector for ROO (remote ON/OFF)
or RPO (Remote Power OFF) control
(5) Outlets for connection of critical
equipment (Primary group)
(6a) Group 1: programmable outlets for
connection of equipment
(6b) Group 2: programmable outlets for
connection of equipment
(7) Attached 6 ft. input power cord for
AC-power source (5-15P)
(8) LED indicating site wiring fault (SWF)
alarm
(9) Ground screw
(1) USB communication port (2) RS232 communication port (3) Slot for optional communication card (4) Connector for ROO (remote ON/OFF)
or RPO (Remote Power OFF) control
(5) Outlets for connection of critical
equipment (Primary group)
(6a) Group 1: programmable outlets for
connection of equipment
(6b) Group 2: programmable outlets for
connection of equipment
(7) Socket for connection to AC-power
source
(8) Ground screw
Page 9
620-00082-01-us (en)
ENGLISH
2. Presentation
2.3 Rack rear panels
5P 550 R / 5P 750 R / 5P 1000 R
2 1 48 36b5
6a
7
9
5P 1500 R
2 1 48 73 9 6b5
6a
5P 850G R
2 1 4 87 36a 6b5
5P 1550G R
6a
2 1 473 6b
5
8
(1) USB communication port (2) RS232 communication port (3) Slot for optional communication card (4) Connector for ROO (remote ON/OFF)
or RPO (Remote Power OFF) control
(5) Outlets for connection of critical
equipment (Primary group)
(6a) Group 1: programmable outlets for
connection of equipment
(6b) Group 2: programmable outlets for
connection of equipment
(7) Attached 6 ft. input power cord for
AC-power source (5-15P)
(8) LED indicating site wiring fault (SWF)
alarm
(9) Ground screw
(1) USB communication port (2) RS232 communication port (3) Slot for optional communication card (4) Connector for ROO (remote ON/OFF)
or RPO (Remote Power OFF) control
(5) Outlets for connection equipment
(Primary group)
(6a) Group 1: programmable outlets for
connection of equipment
(6b) Group 2: programmable outlets for
connection of equipment
(7) Socket for connection to AC-power
source
(8) Ground screw