Eaton 5P1000RC, 5P750RC, 5P1500RC Installation And User Manual

Page 1
ENGISH
Copyright © 2015 EATON All rights reserved.
5P 750VA -1.5 KVA EU_EN
Installation and
user manual
5P750RC
5P1000RC 5P1500RC
Page 2
5P 750VA-1.5 KVA US_EN
Certification Standards
Uninterruptible p ower systems (UPS) directives:
IEC 62040-1: General an d safety requirement s f o r UPS
IEC 62040-2: Electromagnetic comp atibility (EMC) requir e m e n ts
IEC 62040-3: Method of specifying the performance and test requirements
. IEC 62040-4: Environment al aspects - Requirements and reporting CE mark
CE compliance contact: Eaton I.F. – 110 rue Blaise Pascal – 38330 Montbonnot Saint Martin - France The EC Declaration of Conformity is available upon request for produc ts with a CE mark. For copies of the EC Declaration of Conformity, contact Eaton Power Quality or che ck Eaton website :
www.powerquality.eaton.com
Class B emission level CISPR 22(EN 55022) Harmonics emission: IEC 61000-3-2 Flickers emission: IEC 61000-3-3
FCC 47 CFR Part 15, Subp art B - Unintentional Radiators Class B
Special symbols
The following are examples of symbols used on the UPS or accessories to alert you to important information:
RISK OF ELECTRIC SHOCK - Observe the warning associate d with the risk of electric shock symbol.
Important instructions that mu st always be followed.
Do not discard the U P S or t h e UP S batteries in the trash. This product contain s se al e d lead acid batteries and must be disposed as it's explain in t h is manual. For more information, contact your local recycling/reuse or hazardous waste cente r.
This symbol indicates t h at you should not discard waste electrical or electronic e q uip men t (WEEE) in the trash. For proper disposal, contact your local recycling / reuse or hazardous waste cente r.
Information, advice , help.
Page 4
5P 750VA-1.5 KVA US_EN
Safety of Persons
Product Safety
Special Precautions
The system has its own power source (the battery). Consequently, the power outlets may be energized
even if the systems is disc on nected from the AC p ow er source.
Dangerous voltage levels are present within the system. It should be opened exclusively by qualified service personnel.
The system must be plugged to an earthed outlet.
The battery supplie d with the system contains smal l amou nts of toxic materials.
To avoid accidents, t he directives listed below must be observed:
- servicing of batteries should be perf ormed or supervised by personnel knowledgeable about batteries
and the required pre c au tions.
- when replacing b atteries, replace with the same type and number of bat teries or battery packs.
- do not dispose of batt e r ie s in a f ire. The batteries may explode.
- batteries constitu te a danger (electrical sho ck, burns). The short-circuit curre nt may be very high.
Precautions must be t aken for all handling:
Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect charging so u rc e p rior to connecting or d isco n n e cting battery termin als.
The UPS connection in structio ns and o peration describe d in the manual must be follow ed in the indicated
order.
A protection circuit breaker must be installed upstream and be easily accessible. The system can be disconnected from the AC power source by unplugging the input cable.
Check that the in dications on the rating plat e correspond to your AC powered system and to the actual electrical consumption of all the equipment to be connected to the system.
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall be easily accessible
Never install the sy stem near liquids or in an excessiv ely damp environment.
Never let a foreign body penetrate inside the system.
Never block the ventilation grates of the system.
Never expose the system to direct sunlight or source of heat.
If the system must be stored prior to installation, storage must be in a dry p l ac e .
The admissible storage temperature range is -15 to +50 °C / 5 to 122 °F.
The system is not for use in a computer room.
All handling operations will require at least two people (unp a ck ing , installation in rack system) .
Before and after th e installation, if the UPS remains d e-energized for a long period, the UPS must be
energized for a period of 24 hours, at least once every 6 months ( for a normal storage temperature less than 25 °C / 77 °F). This c h ar ges the battery, thus avoiding possible irreversible damage.
During the replacement of the Battery Module, it is imperative to use the same type and number of element as the original Battery Module provided with the UPS to maintain an identical level of performance and safety. In case of doubt, don' t h e sitate to contact your EATO N r e presentative.
Page 4
5P 750VA-1.5 KVA US_EN
1. Introduction ................................................................................. 5
1.1 Environmental protection ............................................................. 5
2. Presentation ................................................................................. 6
2.1 Standard installations .................................................................. 6
2.2 Rear panel ............................................................................... 7
2.3 Control panel ............................................................................ 8
2.4 LCD description ......................................................................... 9
2.6 User settings ........................................................................... 10
3. Installation ................................................................................ 12
3.1 Unpacking and contents check ..................................................... 12
3.2 Battery module connection ......................................................... 13
3.3 Rack installation ...................................................................... 14
3.4 Wall mounting of rack model ....................................................... 15
3.5 Communication ports ................................................................ 16
4. Operation .................................................................................. 17
4.1 Start-up and Normal operation ..................................................... 17
4.2 Starting the UPS on Battery ......................................................... 17
4.3 UPS Shutdown ......................................................................... 17
4.4 Operation on Battery Power ........................................................ 17
4.5 Return of AC Input Power ........................................................... 18
4.6 UPS remote control functions ....................................................... 18
5. Maintenance ............................................................................... 19
5.1 Troubleshooting ....................................................................... 19
5.2 Battery-module replac e men t ....................................................... 20
6. Appendices ................................................................................ 21
6.1 Technical specifications ............................................................. 21
6.2 Glossary ................................................................................ 22
Page 4
5P 750VA-1.5 KVA US_EN
1. Introduction
Thank you for selecting an EATON product to protect your electrical equipment.
The 5P range has been d e signed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your
UPS (Uninterruptible Power System). Before installing your 5P, please read the booklet presenting the safety instructions. Then
follow the indication s in this manual. To discover the entire range of EATON products and the options available for the 5P range, we invite you to visit our
web site at www.eaton.com/powerq u ality or c ontact your EATON representative.
1.1 Environmental p r otection
EATON has implemented an environmental-protection policy. Products are developed according to an eco-design approach.
Substances
This product does no t contain CFCs, HCFCs or asbest os.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
• The cardboard we use comprise s over 50% of recycle d card b oard.
• Sacks and bags are made of polyethylene.
• Packing materials are recyclab le and bear the appropriate identification symbol
01
PET
Materials Abbreviations
Number in
01
the symbols
PET
Polyethylene terephthalate PET 01 High-density polyethylene HDPE 02 Polyvinyl chloride PVC 03 Low-density polyethylene LDPE 04 Polypropylene PP 05 Polystyrene PS 06
Follow all local regulations for the disposal of packing materials.
End of life
EATON will process products at the end of their service life in compli ance with local regulations. EATON works with companies in c h arge of collecting and eliminating our products at the end of their service life.
Product
The product is made up of recyclable materials. Dismantling and de struction must take p lace in compliance w it h all local reg u lations concerning waste. At the end of its service life, t h e p ro d u c t mu st be transported to a processing center for electrical and electronic waste.
Battery
The product contains lead-acid batteries t hat must be processed according to applicable local regulations concerning batter ie s. The battery may be removed to comply with regulations and in view of correct disposa
Page 6
5P 750VA-1.5 KVA US_EN
2. Presentation
2.1 Standard installations
Rack model
Description Weights
(kg/lb)
Dimensions (mm/inch)
D x W x H
5P750RC
14.1/31.1 370*440*86.2 / 14.6*17.3*3.4
5P1000RC
15.0/33.1 370*440*86.2 / 14.6*17.3*3.4
5P1500RC
18.4/45.5 370*440*86.2 / 14.6*17.3*3.4
D
W
H
Page 7
5P 750VA-1.5 KVA US_EN
2.2 Rear panel
5P750RC
& 5P1000RC & 5P1500RC
1)
Attached 1.8 m input power cord for AC power source
2) Slot for optional communication card
3) Primary group : Outlets for connection
of critical equipment
4) Group 1: programmable outlets for connection of equipment
5) Group 2: programmable outlets for connection of equipment
6) RS232 communication port
7) USB communication port
8) Connector for ROO (remote ON/OFF) or
RPO (Remote Power Off) control