1.7 DELIVERY, STORAGE AND HANDLING
A. General Requirements: Deliver, store and handle products to prevent their deterioration or
damage due to moisture, temperature changes, contaminates or other causes.
B. Delivery and Acceptance Requirements: Deliver products to site in original, unopened
containers or packages with intact and legible manufacturers’ labels identifying the
following:
1. Product and Manufacturer
2. Length/Quantity
3. Lot Number
4. Installation and Operation Manual
C. Storage and Handling Requirements
1. Store the heating cable in a clean, dry location with a temperature range -67°F to
194°F (-55°C to 90°C).
2. Protect the heating cable from mechanical damage.
1.8 WARRANTY
A. Extended Warranty
1. Manufacturer shall make available a limited warranty for MI Trace cable kits and
components. Provide one (1) year warranty for all heat trace controllers.
2. Contractor shall submit to owner the results of all installation tests required by the
manufacturer.
PART 2 – PRODUCTS
2.1 MANUFACTURERS AND PRODUCTS
A. Contract Documents are based on manufacturer and products named below to establish
a standard of quality.
B. Basis of Design
1. Basis of Design Product Selections
a. Manufacturer
• Manufacturer to show minimum of thirty (30) years of experience in
manufacturing constant wattage, resistance heating cables.
• Manufacturer shall provide UL and CSA approval certificates for snow
melting. Manufacturer shall be Emerson – EasyHeat
b. MI Trace for Snow Melting
• MI Trace constant wattage, resistance heating cable kits
• MSC1 snow/icing melting controller, with MSP1 pavement sensor and/or
MSA1 aerial sensor OR SA1 controller [Select one]
2.2 PRODUCTS, GENERAL
A. Single Source Responsibility: Furnish heat tracing system for snow melting from a single
manufacturer.
B. The system (heating cable and controller) shall be UL Listed and CSA Certified for snow
melting. No parts of the system may be substituted or exchanged.
2.3 PRODUCTS
A. Metal Alloy 825 Outer Sheath, Series Resistance Cable
1. Heating cable shall be MI Trace, series resistance heating cable by EasyHeat.
2. The heating cable shall consist of solid conductors, mineral magnesium oxide
(MgO) insulation and metal alloy 825 outer sheath.
3. The heating cable shall be factory assembled with a minimum 7-foot cold lead
(unheated) length.