EasyHeat Specification Sheet: EasyHeat T9EA Thermostat, Pipe Tracing Controls, 14028-001 Manuals & Guides

T9EA Thermostat
USA
2 Connecticut South Drive East Granby, CT 06026 Tel. (800) 537-4732 Fax (888) 324-2440
CANADA
99 Union St. Elmira, Ont. N3B 3L7 Tel. (519) 669-2444 Fax (519) 669-6419
Ambient Sensing Adjustable Temperature Hazardous Location
The T9EA thermostat is intended for temperature control of electric heating cables for freeze protection pipe tracing. The T9EA is suitable for indoor/outdoor hazardous locations having hostile environments.
Line Sensing unit shown
ENCLOSURE
NEMA 4, 7 & 9 Lacquer-coated Cast Aluminum
Adjustable 15°F to 140°F (-9°C to 60°C)
Calibration Accuracy
1.3°F (0.7°C)
CAPILLARY
Length Material NA Stainless Steel
Max. Exposure Temp. 160°F (71°C)
ELECTRICAL
SPDT Switch 22 amp Resistive, 125/250/480 VAC 10 – 14 AWG Terminals
APPROVALS
UL E53121 CL. I/II, Div. 1&2, Grps. B,C,D/E,F,G; Type 4 CSA LR34556 CL. I/II, Div. 1&2, Grps. B,C,D/E,F,G; CL. III; Type 4 FM 1Z1A0.AE CL. I/II, Div. 1&2, Grps. B,C,D/E,F,G
4" (101.6mm)
4.5" (114.3mm) 4" (101.6mm)
4.5"
(114.3mm)
6.56" (165.1mm)
14028-001 Rev. 4 ©2008 Easy Heat
4" (101.6mm)
Clearance for
1/4" (6.4mm) screw
(4 places)
1.22"
(30.5mm)
.
38" (9.5mm)
2" (50.8mm)
3/4" (21mm) NPT threaded opening
Ground screw/clamp
2 T9EA Thermostat Ambient Sensing Adjustable Temperature Hazardous Location
USA
2 Connecticut South Drive East Granby, CT 06026 Tel. (800) 537-4732 Fax (888) 324-2440
CANADA
99 Union St. Elmira, Ont. N3B 3L7 Tel. (519) 669-2444 Fax (519) 669-6419

INSTALLATION

MI TRACE SAMPLE INSTALLATION
Sensing Bulb
Thermostat
Power Supply
Low Point Drain
MI Cold Section
ANNUAL MAINTENANCE
MI Heater Cable
Pipe
DIRECT CONTROL
1 Remove cover. 2 Spray a coat of lubricant and rust preventative such as CRC Stor &
Lube, electrical grade, on thermostat body.
3 Replace cover.
Loading...