EasyHeat Specification Sheet: EasyHeat T4XA Thermostat, Pipe Tracing Controls, 14026-001 Manuals & Guides

T4XA Thermostat
USA
2 Connecticut South Drive East Granby, CT 06026 Tel. (800) 537-4732 Fax (888) 324-2440
CANADA
99 Union St. Elmira, Ont. N3B 3L7 Tel. (519) 669-2444 Fax (519) 669-6419
Ambient Sensing Adjustable Temperature NEMA 4X
DESCRIPTION
The T4XA thermostat is intended for temperature control of a variety of electric heating cables for freeze protection pipe tracing or roof/gutter de-icing. The T4XA is suitable for indoor/outdoor locations having hostile, non-hazardous environments.
NOTE: Waiting on photography
NEMA 4X Polyurethane-coated Die Cast Aluminum (max. 0.6% copper)
TEMPERATURE RANGE
Adjustable 15°F to 140°F (-9°C to 60°C)
Calibration Accuracy
1.3°F (0.7°C)
CAPILLARY
Length Material N/A Stainless Steel
Max. Exposure Temp. 160°F (71°C)
ELECTRICAL
SPDT Switch 22 amp Resistive, 125/250/480 VAC 10 – 14 AWG Terminals
APPROVALS
UL CSA
OUTLINE
14026-001 Rev. 3
©2008 Easy Heat
2 T4XA Thermostat Ambient Sensing Adjustable Temperature NEMA 4X
USA
2 Connecticut South Drive East Granby, CT 06026 Tel. (800) 537-4732 Fax (888) 324-2440
CANADA
99 Union St. Elmira, Ont. N3B 3L7 Tel. (519) 669-2444 Fax (519) 669-6419

INSTALLATION MI Trace Sample Installation

Method for installing TSR,
SRTrace, ZH and FP heater cable
types.
WIRING
ANNUAL MAINTENANCE
MI Heater Cable
1 Remove cover. 2 Spray a coat of lubricant and rust preventative such as
CRC Stor & Lube, electrical grade, on thermostat body.
3 Replace cover.