T4XA Thermostat
USA
2 Connecticut South Drive
East Granby, CT 06026
Tel. (800) 537-4732
Fax (888) 324-2440
CANADA
99 Union St.
Elmira, Ont. N3B 3L7
Tel. (519) 669-2444
Fax (519) 669-6419
Ambient Sensing Adjustable Temperature NEMA 4X
DESCRIPTION
The T4XA thermostat is intended for temperature
control of a variety of electric heating cables for
freeze protection pipe tracing or roof/gutter de-icing.
The T4XA is suitable for indoor/outdoor locations
having hostile, non-hazardous environments.
NOTE: Waiting on photography
ENCLOSURE
NEMA 4X Polyurethane-coated Die Cast Aluminum
(max. 0.6% copper)
TEMPERATURE RANGE
Adjustable
15°F to 140°F (-9°C to 60°C)
Calibration Accuracy
1.3°F (0.7°C)
CAPILLARY
Length Material
N/A Stainless Steel
Max. Exposure Temp.
160°F (71°C)
ELECTRICAL
SPDT Switch
22 amp Resistive, 125/250/480 VAC
10 – 14 AWG Terminals
APPROVALS
UL
CSA
OUTLINE
14026-001 Rev. 3
©2008 Easy Heat

2 T4XA Thermostat Ambient Sensing Adjustable Temperature NEMA 4X
USA
2 Connecticut South Drive
East Granby, CT 06026
Tel. (800) 537-4732
Fax (888) 324-2440
CANADA
99 Union St.
Elmira, Ont. N3B 3L7
Tel. (519) 669-2444
Fax (519) 669-6419
INSTALLATION
MI Trace Sample Installation
Method for installing TSR,
SRTrace, ZH and FP heater cable
types.
WIRING
ANNUAL MAINTENANCE
MI Heater Cable
1 Remove cover.
2 Spray a coat of lubricant and rust preventative such as
CRC Stor & Lube, electrical grade, on thermostat body.
3 Replace cover.