EasyHeat Specification Sheet: EasyHeat GC-1 Controller, Roof and Gutter De-Icing Controls, 40951-001 Manuals & Guides

GC-1
11399-001 REV 0
www.easyheat.com
6.0” (15.24mm)
6.4” (16.26cm)
2.8”
71.12mm
1.6”
40.64mm
3.4”
86.36mm
1.25”
31.75mm
30’
9.14m
Roof & Gutter De-Icing Controller
Description
The GC-1 roof and gutter de-icing controller is designed to energize the heating cable only when moisture conditions exist and there is risk of freezing. If the temperature is below 3°C (38°F) and the MSG-1 sensor detects moisture, the controller will apply power to the heating cable. The cable remains energized until 3 hours (hold time) after the sensor is dry.
Electrical Specifications
Functional
Activation temperature +3°C (38°F +/-1°F) Environmental Working temperature -40°C (-40°F) to 65°C
(150°F)
Storage temperature -45°C (-49°F) to 70°C
(160°F)
Humidity environment 0 to 100 %
Supply requirements
Power supply voltage 120VAC, 208VAC,
240VAC, 277VAC Frequency 60 Hz Maximum power consumption 50W
Output characteristics
Output type relay (wet contact) Contact output N.O. max. 24 Amps @
277VAC
MSG-1 characteristics
Power supply voltage 24VAC class2 Maximum Amperage 500mA Accessories
Connection Wire 30’
Screws, coated strapping,
coated clips
GC-1 CONTROLLER
US T. (800) 537-4732 / F. (888) 324-2440 CAN T. (800) 794-3766 / F. (800) 361-4574
©2008 Easy Heat www.easyheat.com 40951-001 Rev. 2
MSG-1 AND ACCESSORIES
7.62m
MSG-1
SENSOR
CONNECTION
CONT
..... .....
CONT
..... .....
2 GC-1 Roof & Gutter De-Icing Controller
Installation
GC-1 BASE INSTALL IN EXTERIOR LOCATION
MSG-1 HOUSING INSTALLATION
HEATING
CABLE
MSG-1 SENSOR
WIRE INSTALLATION
SENSOR WIRE
MSG-1
GC-1 CONTROLLER WITH SINGLE/DUAL PHASE LOAD LESS THAN OR EQUAL TO 24A
GC-1 CONTROLLER WITH LOAD HIGHER THAN 24A OR 3 - PHASE LOADS
At the beginning of the heating season and monthly during operation inspect for and remove all leaves and combustible debris from roofs gutters and downspouts. At the beginning of the heating season the MSG-1 must be inspected for physical damage and the snow sensor surface cleaned. To clean the snow sensor surface:
Wiring
MSG-1
MSG-1 CONNECTION
1. Lock-out the power supply to the GC-1.
2. Remove the MSG-1 sensor housing from the gutter.
3. With a clean wet swab clean up the surface of the snow sensor.
4. Replace the MSG-1 sensor housing in the gutter.
5. Reconnect GC-1 to the power supply.