EasyHeat Specification Sheet: EasyHeat C4XC Thermostat, Pipe Tracing Controls, 14027-001 Manuals & Guides

C4XC Thermostat
Line/Ambient Sensing Fixed Temperature NEMA 4X Set-Point Application/Specication Guide
DESCRIPTION
The C4XC thermostat is intended for temperature control of a variety of electric heating cables utilized for freeze protection pipe tracing or roof/gutter deicing. The thermostat is suitable for indoor/outdoor locations having hostile, non-hazardous environ­ments. The C4XC can be used in an ambient-sensing mode (with capillary coiled, as received) or a line sensing mode (with capillary attached to pipe).
ENCLOSURE
NEMA 4X Molded Gray Fiberglass Polyester
TEMPERATURE RANGE
Fixed 40°F (4.4°C)
Calibration Accuracy 4°F (2.2°C)
CAPILLARY
Length Material 3' (0.9 m) Nickel Plated Copper
Maximum Exposure Temperature
140°F (60°C)
ELECTRICAL
SPST Switch (Closes on temp. fall at 40°F/4.4°C) 22 amp Resistive, 120/208/240 V., 50/60 Hz 18 amp Resistive, 277 V., 50/60 Hz 125 VA Pilot Duty, 120-277 V., 50/60 Hz 14 AWG Leads
APPROVALS
UL CSA
OUTLINE
6.19"
5" (127mm)
US T. (800) 537-4732 / F. (888) 324-2440 CAN T. (800) 794-3766 / F. (800) 361-4574
©2015 EASYHEAT www.easyheat.com 14027-001 Rev. 4
(157.2mm)
2.38" (60.5mm)
3.31" (84.1mm)
1.5" (38.1mm)
3" (76.2mm)
7" (177.8mm)
3/4" Conduit Entry
.22" (5.6mm) diameter
2 C4XC Thermostat Line/Ambient Sensing Fixed Temperature NEMA 4X Set-Point Application/Specication Guide
INSTALLATION MI Trace Sample Installation
Method for installing TSR, SRTrace,
ZH and FP heater cable types.
WIRING
MI Heater Cable
Sensing Bulb—Install at least 90°
Thermostat
ANNUAL MAINTENANCE
1 Remove cover. 2 Spray a coat of lubricant and rust preventative such as CRC Stor & Lube, electrical grade, on thermostat body. 3 Replace cover.
US T. (800) 537-4732 / F. (888) 324-2440 CAN T. (800) 794-3766 / F. (800) 361-4574
©2015 EASYHEAT www.easyheat.com 14027-001 Rev. 4