EasyHeat Reference Guide: Warm Tiles Troubleshooting Suggestions for Cables and Thermostats, TSHCS-FW01 Manuals & Guides

Problem
Possible Cause
Display is blank / Illegible / Unwanted characters showing
No power to thermostat
Restore power supply
FG and FGS models: The pins are not aligned and not properly
inserted. (see Figure 2 on page 4)
FG and FGS models: Align the thermostat power base; Hook the Front
Panel unit to the top of the Power Base unit, swing down and press the Front Panel into the Power Base unit slightly. Tighten the screw at the bottom of the unit. (See Figure 3 on page 4)
Power disturbance / interruption
See Step 1 on page 2.
Can't adjust the temperature setting / time
Power disturbance / interruption
See Step 1 on page 2.
Button Failure
Replace thermostat
ER 02 on display
Program cannot run with time setting proposed due to conflict of time (e.g. Leave time occurs after Return time)
Adjust program time to eliminate conflict
Test button won't cause thermostat to trip
Thermostat is in "Standby” mode. (Heating Symbol icon flashing slowly)
Wait 3 minutes, until Heating Symbol icon stops flashing and is on continuously
GFI flashing on LCD display
Ground Fault detected by thermostat
Press reset button on thermostat. If fault does not clear, switch to OFF mode, call service technician or Contact Easy Heat Technical Support.
Cold/Hot floor Floor temp set too low/high.
Increase/decrease floor temp setting.
Clock not set properly
Check Time of Day settings, watch for AM/PM
Floor temp won't reach set level
Program Set Time may be off.
Check program settings, watch for AM/PM.
Heat up time may be longer than one hour.
Set cables to come on earlier than current program
Cables may not be able to reach set level due to room heat loss
Reduce source of heat loss such as open windows, insulate floor directly under cables
Cable problem
Cables must be checked - see additional suggestions below
Floor heating doesn't turn on
Thermostat is in OFF mode
Switch to ON, or Manual or Auto Mode.
Power supply problem
Check breaker panel and wiring
Problem with sensor wire, "Sensor" flashing on LCD display
Sensor and/or connections to thermostat must be checked. See also Step 3 on Page 2.
For FG and FGS models: Ensure pins are aligned and properly inserted. (see Figure 2)
Cable problem
Cables must be checked - see additional suggestions on next page
Troubleshooting Suggestions for Cables and Thermostats
Toll Free Number: 800-537-4732 opt 5 | E-mail:
Easyheat.Technicalservices@Emerson.com
2017-06-08
1 of 7
TSHCS - FW01 Rev 0
www.easyheat.com
2 of 7
Note: A qualified Electrician, Digital Multimeter and Mega ohmmeter will be needed for Steps 2 through 5.
Step 1
To reset the Warm Tiles thermostat to factory default settings, turn off the circuit breaker in the electrical panel that supplies the Warm Tiles installation. Leave the circuit breaker off for 20 to 30 minutes. This will restore the Warm Tiles thermostat to the factory default settings. Then turn the circuit breaker back on and reset the thermostat custom temperature setting. Observe the thermostat operation to see if the thermostat is working properly. You should be able to adjust the thermostat setting and observe the floor temperature change.
Step 2
If Step 1 does not correct the problem, measure the supply voltage at the Warm Tiles thermostat. The supply voltage should be within 5% of the thermostat rated voltage. Also, the output voltage of the Warm Tiles thermostat should be measured and be within 5% of the thermostat rated voltage. Output voltage should match input voltage. To do this, turn off the circuit breaker in the electrical panel that supplies the Warm Tiles installation. Then remove the Warm Tiles heater cable leads from the Warm Tiles thermostat. Turn the circuit breaker back on and switch the thermostat to the manual position or the ON position for a nonprogrammable thermostat. When the thermostat heating symbol (Three wavy lines) appears on the LCD screen of the thermostat without flashing, measure the thermostat input and output voltage. If the heating symbol is flashing on the LCD screen, wait a few minutes for it to stop flashing then conduct the voltage tests. Please refer to Figure 1 on page 3 for thermostat wiring. An alternate method of testing the thermostat is to change out the questionable thermostat with a properly functioning thermostat. If the properly functioning thermostat operates correctly and the floor temperature change is observed, the questionable thermostat should be replaced with a new Warm Tiles thermostat.
Step 3
Check the thermostat floor temperature sensor cable by disconnecting the floor sensor cable from the thermostat, measure the sensor cable resistance in ohms using a digital multimeter. With the digital multimeter scale set at 20K-ohms, the ohms reading of the sensor wire should be between 7,000 ohms to 14,000 ohms. If the sensor cable measurement is outside the resistance range, the sensor cable should be replaced. When replacing the sensor cable, position the sensor bulb equally between two Warm Tiles heater cables.
Step 4
To identify the model number of the cable/mat that is installed in the existing floor, check the factory identification tag attached to the cold lead of the Warm Tiles cable/mat, retained within the junction box or electrical connection box, behind the thermostat. The factory identification tag lists the model number of the cable/mat and its resistance value. If the factory identification tag is missing, measure the resistance (in ohms) of the heating cable/mat using a digital multimeter and compare the measured resistance to the Warm Tiles tables on the following pages. Also, the Warm Tiles tables list the cable/mat total length, recommended heated square footage and electrical specifications. This information can be used to identify the cable/mat installed in the floor and evaluate the condition of the Warm Tiles system.
Step 5
To check the Warm Tiles cable/mat for ground fault conditions, measure the insulation value of each cable conductor to the ground braid using a mega-ohmmeter at 500 VDC. The Warm Tiles cable/mat conductor insulation measurement should be 10 mega-ohms or higher. A low mega-ohmmeter reading may indicate physical damage to the Warm Tiles cable/mat during installation.
TSHCS - FW01 Rev 0
www.easyheat.com
Figure 1: Warm Tiles Thermostats
Heating Cable
To ECB
Power Supply
Heating Cable
To ECB Sensor
Power
To Ground Connection Sensor
Heating Cable
Power Supply Cable
Sensor
3 of 7
Ground Screw
Cold Leads
(a) ET and FTS
Wire
Ground Screw
Cold Leads
(b) GT and GTS
Wire
Supply
Cold Lead
(c) FG and FGS
Wire
TSHCS - FW01 Rev 0
www.easyheat.com
Loading...
+ 4 hidden pages