Inputs: 0 (or 4) to 20 mA DC or 0 (or 2.0) to 10.0 VDC selectable.
Input Impedance: Current input: 10 ohms, Voltage input: 5K ohms.
Output Ratings:
Control Relays: SPDT, rated 10A @ 240 VAC res., 1/4 hp @120 VAC,
1/3 hp @ 240 VAC;
Alarm Relays: SPST, 3A @ 240 VAC res., 1/10 hp @ 120 VAC;
Other: 15 VDC @ 20 mA for output one and output two.
Control Type: On/off, reverse or direct acting.
Power Requirements: 100 to 240 VAC nominal, +10%-15%, 50 to 400 Hz,
single phase; 132 to 240 VDC nominal, +10%-15%.
Power Consumption: 7.5 VA maximum.
Accuracy: ±0.25% of span, ±1 least significant digit.
Display: Two 4-digit, 7 segment 0.56˝ high LED’s.
Display Resolution: 1 count.
Memory Backup: Nonvolatile memory (no batteries required).
Serial Communications: Optional RS-232 or RS-485 with Modbus
Ambient Operating Temperature / RH: 14 to 131°F (-10 to 55°C) / 0 to 90% up
to 104°F (40°C) non-condensing, 10 to 50% at 131°F (55°C) non-condensing.
Weight: 16 oz (454 g).
Front Panel Rating: Meets UL Type 4X (IP66).
Loop Power Supply (isolated): 24 VDC @ 50 mA, regulated.
Alarm On-Off Differential: 1 count.
Set Point Range: Selectable.
Power Voltage Stability: 0.05% over the power voltage range.
Temperature Stability: 100 ppm / °C typical, 200 ppm / °C maximum.
Common Mode Rejection: 140 db minimum at 60 Hz.
Normal Mode Rejection: 65 db typical, 60 db at 60 Hz.
Isolation:
Relay: 1500 VAC to all other inputs and outputs;
24 VDC Loop Power: 500 VAC to other inputs and outputs;
Process Output: 500 VAC to other inputs and outputs.
Storage Temperature: -40 to 176°F (-40 to 80°C).
Agency Approvals: UL 508, CE.
®
protocol.
Modbus®is a registered trademark of Schnieder Automation.
2
GETTING STARTED
1. Install the control as described on page 4.
2. Wire the control following the instructions on pages 5 through 7. Page 5 contains
basic wiring for the control. If using the Series MPCJR’s transmitter power supply
follow the additional directions on page 6. Wiring instructions for the 232 and 485
series communication options is included on page 7.
3. Familiarize yourself with the front key pad functions and read the menu structure
prior to starting the programming process. A programming chart with the menu
structure and spaces to write your programming values is included on pages 26
through 28. This chart can be a helpful tool to save time in programming. For further
assistance programming examples are included on pages 28 through 31.
MODEL IDENTIFICATION
Model MPCJR -
Options
Options:
232
485
RV
RC
RS-232 Modus®-RTU Serial Communications. Allows remote
computer to read and write all control parameters.
RS-485 Modbus®-RTU Serial Communications. Allows remote
computer to read and write all control parameters.
Analog retransmission of input, 0 to 10 VDC.
Analog retransmission of input, 0 (or 4) to 20 mA.
Input Ranges
Process Input Types
The 0 to 20 mA DC, 4 to 20 mA DC, 0 to 10 VDC, and 2 to 10 VDC inputs are
fully scalable from a minimum of 100 count span placed anywhere within the
range of -1999 to +9999. Decimal point position is adjustable from the zero place
(9999), tenths (999.9), hundredths (99.99), or thousandths (9.999).
3
INSTALLATION
Mount the instrument in a location that will not be subject to excessive temperature,
shock, or vibration (see Specifications for specific tolerances). All models are
designed for mounting in an enclosed panel.
Select the position desired for the instrument on the panel. Prepare the panel by
cutting and deburring the required opening.
From the front of the panel, slide the housing through the cut out. The housing
gasket should be against the housing flange before installing.
From the rear of the panel slide the mounting collar over the housing. Hold the
housing with one hand and using the other hand, push the collar evenly against the
panel until the springs are compressed. The ratchets will hold the mounting collar
and housing in place.
Figure 1 – Panel Cut Out Dimensions
Panel cut-out:
3.620 x 3.620 in,
+0.032/-0.000
(92 x 92 mm,
+0.8/-0.0)
CAUTION: It is not necessary to remove the instrument chassis
from the housing for installation. If the instrument chassis is
removed from the housing, you must follow industry standard
practice for control and protection against Electro-Static
Discharge (ESD). Failure to exercise good ESD practices may
cause damage to the instrument.
4
WIRING
Voltage
Current
Alarm 1
Contacts
Alarms 2
Contacts
24 VDC
@ 50 mA
Isolated
Pump 1
Output
Pump 2
Output
Line Input
100 to 240 VAC
50 - 400 Hz. Single PH
132 to 240 VDC 5VA
MAX. Output Ratings:
Relay: 10A. @ 240 VAC RES.
1/4 HP @ 120 VAC
1/3 HP @ 240 VAC
Alarm: 3A. @ 240 VAC RES.
P.D. 240VA, 120/240 VAC
SW. Volt.: 15 VDC @ 20 mA
NOTE:
1. For supply connections
use No. 16 AWG or larger
wires rated for at least 75°C,
or in accordance with an
equivalent national standard.
2. Maximum ambient temperature
rating 131°F (55°C)
3. Use copper conductors only
4. Terminals 1-5, 10-12, & 21-32
are class 2 'SELV'.
15 VDC
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
323130292827
21
22 23
24 25
26
N.O.
N.O.
COM.
COM.
N.O.
N.O.
N.C.
N.C.
COM.
COM.
CURRENT
RELAY
& SSR
290-3126
COM.
Pump1
Pump2
+
-
Option RV, RC
Do not run transmitter wiring or other Class 2 wiring in the same conduit as power
leads. Use only the probe or transmitter for which the control has been
programmed. Maintain separation between wiring of sensor, auxiliary in or out, and
other wiring. See the "Secure Menu" for input selection.
Supply connections should be made in accordance with the National Electrical
Code per Article 300, and local regulations. All line voltage output circuits must
have a common disconnect and be connected to the same pole of the disconnect.
Input wiring for probe or transmitter is rated CLASS 2.
Control wiring is as shown in Figure 2 below.
Figure 2 - Wiring
5
Connect Jumper between terminals 3 and 12
Connect Transmitter Plus (+) to terminal 11
Connect Transmitter
Minus (-) to terminal 5
Level
Transmitter
WIRING FOR TRANSMITTER INPUTS USING INTEGRAL
SNUBBER
COIL OF RELAY
OR MOTOR STARTER
SWITCHED AC
(FROM CONTROLLER)
1-1/4
7/8
9/16 THICK
SNUBBER PHYSICAL
CHARACTERISTICS (TYPICAL)
4
3/8
POWER SUPPLY
Wire power and outputs as shown on previous page. Wiring for two-wire
transmitters shown below in Figure 3. All wiring shown in Figure 3 is Class 2.
Figure 3 - Transmitter Wiring
Use of a fuse (1/8W Fast-Blow) in
the loop is recommended to
protect the control input circuitry.
For three or four wire transmitters follow the wiring instructions provided with your
transmitter.
DO NOT wire the 24 Volt Power Supply across the input of the
control. Damage to the control input circuitry will result.
USE OF SNUBBERS WITH INDUCTIVE LOADS
A snubber is a resistance/capacitance device that is used to reduce or eliminate
high voltage spikes generated from inductive loads. For best effect, the snubber
should be mounted as close to the coil as physically possible. Electrical and typical
physical characteristics are shown above.
Failure to use a snubber on an inductive load may cause erratic
operation and/or premature relay contact wear.
6
WIRING FOR 485 AND 232 SERIAL COMMUNICATION OPTIONS
10
9
8
7
27 28
29
30
31
32
20
19
18
17
6
5
4
3
2
1
21
22
23
24
25
26
16
15
14
13
12
11
Terminal 29 30 31 32
Option 485 Y (receive -) Z (receive +) A (transmit -)* B (transmit +)*
Option 232 not used data out data ground data in
*For half-duplex operation wire only A and B. Do not connect to Y and Z.
Wire power and outputs as shown on page 5. Wiring for options is shown in Figure
4 below. All wiring shown below is Class 2. Shielded twisted pair is recommended
for Option 485.
DO NOT run signal wiring in the same conduit or chase as the
power wiring. Erratic operation or damage to the control
circuitry will result.
Figure 4 – Wiring for Options
7
FRONT PANEL FUNCTIONS
Key functions are as follows:
INDEX: Pressing the INDEX key advances the display to the next menu
item. May also be used in conjunction with other keys as noted below.
UP ARROW: Increments a value, changes a menu item, or selects the item to
ON. The maximum value obtainable is 9999 regardless of decimal point
placement.
UP ARROW & ENTER: Pressing these keys simultaneously brings up the
secondary menu starting at the SP 1H menu item. Pressing these keys for 5
seconds will bring up the secure menu.
DOWN ARROW: Decrements a value, changes a menu item, or selects the
item to OFF. The minimum value obtainable is -1999 regardless of decimal
point placement.
ENTER: The ENTER key is used to store the value of menu items once
they are changed to a new value. If the ENTER key is not pressed after
changing the value the item will revert to the previously stored value.
8
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.