Dwyer MP User Manual

Series MP Mini-Photohelic
®
Differential Pressure Switch/Gage
Specifications - Installation and Operating Instructions
Bulletin B-37-A
LOW PRESSURE
PORT
HIGH PRESSURE
PORT
3-1/32 [77.00]
1 [25.4]
Ø2-19/32
%%3-1/16
[77.79]
[65.88]
3-1/32 [77.00]
3-13/16 [96.84]
23/64 [36.51]
SPECIFICATIONS
GAGE SPECIFICATIONS Service: Air and non-combustible, compatible gases. Wetted Materials: Consult factory. Accuracy: +/- 5% of full scale @ 70°F (21.1°C). Gage
face mounted in vertical position.
Pressure Limits: 30 psig (2.067 bar). Temperature Limits: 20 to 120ºF (-6.7 to 49°C). Process Connections: Barbed for 3/16˝ I.D. tubing
(STD); 1/8˝ male NPT (optional). Size: 4-1/8˝ (104.78 mm) depth x 3-1/16˝ (77.79 mm) diameter.
Weight: 23 oz (652 g).
The Series MP Mini-Photohelic®differential pres-
sure switch/gage combines the time proven Minihelic SPDT switching setpoints. The Mini-Photohelic
®
II differential pressure gage with two
®
is designed to measure and control positive, negative, or differential pressures consisting of non-com­bustible and non-corrosive gases. Gage reading is independent of switch operation. Switching status is visible by LED indicators located on the front and rear of the gage.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
SWITCH SPECIFICATIONS Switch Type: (2) SPDT relays. Electrical Rating: 5A @ 120/240 VAC Resistive; 5A @
30 VDC. Electrical Connections: Screw Type Terminal Block. Accepts 22-12 AWG wire. Power Requirements: 24 VDC / 24 VAC 50/60 Hz 4 watts.
Mounting Orientation: Gage face in vertical position. Set Point Adjustment: Push Buttons. Standard Accessories: (2) mounting screws, (1) .050˝
hex allen wrench.
Agency Approvals: UL, cUL.
Phone: 219/879-8000 www.dwyer-inst.com
INSTALLATION
PANEL MOUNTED
#6 MOUNTING
SCREW
MOUNTING LUG
1. Location: Select a location free from excessive
vibration and where ambient temperature will be between 20 to 120ºF (-6.7 to 49ºC). Pressure sensing lines may be any length necessary without affecting accuracy. However, long runs of tubing will dampen readings slightly and cause an increase in response time. If pulsing pressure or vibration cause excessive pointer oscillation please contact factory for ways to pro­vide additional damping.
4. Zeroing: Before installation, the Mini-Photohelic®may
need to be zeroed before placing into operation. If zeroing is required, you must first remove the zero adjust plug, located near the bottom face of the gage, with a small blade screwdriver. (refer to Fig B.) The zero adjust screw is located directly behind the plug. Use the hex allen wrench supplied and adjust until the pointer is on zero. This must be done with both pres­sure connections vented to the atmosphere and the gage oriented in the final mounting position. Replace plug. Caution must be taken not to overtighten the plastic plug when repluging.
2. Position: The Mini-Photohelic®is calibrated and zeroed
with gage face in the vertical position at the factory. If the gage is used in any other position, it must be re-zeroed each time the position is changed. Gages with ranges under 5 in. w.c. (1.24 kPa), or equivalent, should be used only in the vertical position unless special calibra­tion was specified when ordering.
3. Mounting: The Mini-Photohelic®is normally mounted
before making electrical connections. Terminal blocks are located on the rear of the gage for electrical connec­tions.
(A) Panel Mounting: Standard installation for the Mini-
Photohelic®mounting is flush through a panel. Allow approximately 1˝ clearance for pressure tub­ing and electrical wiring. cut a 2-5/8˝ (66.68 mm) diameter hole in the panel. Insert the Mini­Photohelic®into the panel, thread #6 mounting screws into the mounting lugs and tighten.
Fig. A
LOW PRESSURE PORT
2-19/32 (65.88)
3-1/16
1 (25.40)
(77.79)
5. Pneumatic Connections: To measure positive pres-
sure, connect tubing to port marked “+” and vent “–” port to atmosphere. For negative pressure (vacuum), connect to port marked “–” and vent “+” port to atmos­phere. If gage is supplied with 1/8˝ male NPT connec­tions careful attention must be made not to over-tight­en fittings to avoid damage to the gage.
HIGH PRESSURE PORT
ZERO ADJUST PLUG
5/32 (3.97)
MOUNTING HOLE
TYP 4 PLACES
2.276 (57.81) TYP
2-11/16 (68.26) SQ
Fig. B
2-3/8
(60.33)
1-15/16 (49.21)
1-7/16
(36.51)
11/64 (4.37)
23/64 (9.13)