Model MN-1 Mini-Node Communication Signal Converter
57/64
[22.5]
3-5/32
[80.0]
53/64
[21.2]
YELLOW LED
GREEN LED
Specifications and Operating Instructions
Bulletin E-90-MN-1
The Model MN-1 Mini-Node Communication Signal Converter is a low
cost device that converts half duplex RS 485 serial communications
signals into a signal that can be read by any computer with a USB port.
The integral USB connector and RJ-45 connector reduces set up time
by eliminating extra wiring. The Model MN-1 is powered via the USB
connection which eliminates the need for an external power source. The
compact size is great for field installation, control panels, and lab testing.
APPLICATION
SPECIFICATIONS
Power Requirements: No external power required.
Power Consumption: 0.4 W.
Isolated Voltage: 3000 VDC.
Input Impedance: 96 k .
USB Connector: A-Type (plug).
RS-485 Connector: RJ-45.
Baud Rate: 75, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400,
57600, and 115200 bps.
Compatibility: Full compliance with USB V.2.0 specification.
RJ-45 PIN
Signal Name
PIN
Reserved
1
Reserved
2
Reserved
3
SG+ (Red)
4
SG- (Green)
5
Reserved
6
Reserved
7
Reserved
8
The “SG+” connects to the “+” and the “SG-” connects to the “-” of the
RS-485 Device.
LOVE CONTROLS DIVISION
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: love@love-controls.com
Phone: 219/879-8000 www.love-controls.com
LED MODES
1. Green LED indicates unit is powered.
2. Yellow LED to indicate that data is being transferred.
USB DRIVER INSTALLATION
NOTE: Do NOT connect MN-1 to PC before extracting the driver file.
1. Insert the factory supplied CD into the CD drive of
your computer. If the CD does not start automatically,
click “Start”, “Run” & type D:/Drivers.exe then click “OK”.
2. Follow the on screen instructions to prepare for
installation of the driver.
3. A folder marked SiLabs should now appear in the
PC’s C drive.
4. Connect the MN-1 to PC.
5. The PC should automatically recognize that new
hardware has been found. If not, add hardware can
be found un the control panel.
6. Follow on screen instructions for assigning USB driver
to the MN-1.
7. Repeat steps 5 and 6 for assigning RS-485 Driver to
the MN-1.
8. Open the system folder in the control panel.
9. Click on hardware tab.
10. Open the device manager.
11. Double click on ports.
12. Verify that USB to UART Bridge Controller appears.
13. The Driver installation is complete.
MAINTENANCE
Upon final installation of the Model MN-1 Mini-Node USB to RS 485
Converter, no routine maintenance is required. A periodic check of
system calibration is recommended. The Model MN-1 is not field
serviceable and should be returned if repair is needed (field repair
should not be attempted and may void warranty). Be sure to include a
brief description of the problem plus any relevant application notes.
Contact customer service to receive a return goods authorization
number before shipping.
©Copyright 2011 Dwyer Instruments, Inc. 1/11 FR# R5-443583-00 Rev. 2
LOVE CONTROLS DIVISION
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: love@love-controls.com
Phone: 219/879-8000 www.love-controls.com